Carrier 42EP Hydronic Extra Slim Ducted Fan Coil Units Instruction Manual
- June 4, 2024
- Carrier
Table of Contents
Carrier 42EP Hydronic Extra Slim Ducted Fan Coil Units
UNIT SIZE | A | B | C |
---|---|---|---|
42EP-SIZE 0 | 914 | 170 | 50 |
42EP-SIZE 1 | 1114 | 170 | 50 |
42EP-SIZE 2 | 1314 | 170 | 50 |
UNIT SIZE | A | B |
---|---|---|
42EP-SIZE 0 | 914 | 190 |
42EP-SIZE 1 | 1114 | 190 |
42EP-SIZE 2 | 1314 | 190 |
UNIT SIZE | A | B |
---|---|---|
42EP-SIZE 0 | 914 | 190 |
42EP-SIZE 1 | 1114 | 190 |
42EP-SIZE 2 | 1314 | 190 |
UNIT SIZE | A | B |
---|---|---|
42EP-SIZE 0 | 914 | 190 |
42EP-SIZE 1 | 1114 | 190 |
42EP-SIZE 2 | 1314 | 190 |
PRECAUTIONS
Only specially trained and qualified technicians and installers who have been
fully trained on the product concerned are authorized to install, to
commission and service this equipment.
In particular it is obligatory to disconnect all power supplies to the unit
and its accessories before carrying out any work.
Operating limits
Cooling mode
| Cooling mode – Operating Limits
---|---
Water circuit| Min. inlet Temperature >5°C ethylene / propylene
glycol rate < 40% Water side pressure < 15,5 bar (1550 kPa)
Ambient temperature and humidity| T < 27°C / 65% relative humidity or
humidity weight < 14,7 g/kg dry air
Supply air temperature| T > 12°C with maximum ambient humidity
conditions (14,7 g/kg dry air)
Heating mode
| Heating mode – Operating Limits
---|---
Water circuit| Max. inlet Temperature < 80°C ethylene / propylene
glycol rate < 40% Water side pressure < 15,5 bar (1550 kPa)
Ambient temperature and humidity| T < 40°C
Supply air temperature| T < 60°C with supply plenum and spigots
application
Operating environment
The 42EP has been designed for indoor application in ‘urban’ conditions having
a non-corrosive, dust-free and non-marine environment.
- The concentrations of the following chemicals must not be exceeded in any event:
- SO2 < 0,02 ppm
- H2S < 0,02 ppm
- NO, NO2 < 1 ppm
- NH3 < 6 ppm
- N2O < 0,25 ppm
Do not install a unit where flammable gases or products of an acidic or alkaline character may be present. The copper/aluminium coil or components inside the unit could suffer irreparable corrosion damage in their presence.
Recommended coil water quality
At installation handover, and then periodically every year, it is advised to
analyse the water for bacteria (detection of Ferro-bacteria, H2S-producing and
sulphate-reducing bacteria) and chemicals (in order to avoid problems due to
corrosion and scaling).
The water circuit must include all the necessary elements for the treatment of
the water: filters, additives, intermediate exchangers, purges, drains,
isolating valves, etc., according to the analysis results.
- The results must be in accordance with the values shown below:
- Total hardness in mmol/l: 1 < mmol/l < 1,5
- Chloride [CL-] <10 mg/litre
- Sulphate [SO4 2-] <30 mg/litre
- Nitrate [NO3 -] =0 mg/litre
- Dissolved iron [Fe]: Fe <0,5 mg/litre
- Dissolved oxygen [O2]: 4< [O2] < 9 mg/litre
- Carbon dioxide [CO2] CO2 <30 mg/litre
- Resistivity [R]: 20< R< 50 Ohm·m
- pH: 6,9 < pH < 8
Clearances required
- Base unit: Fig.1
- With rectangular flange: Fig.2
- With compact plenum: Fig. 3
- With large plenum: Fig. 4
NOTE : All information’s about dimensions and weights are available in the PSD documentation on Carrier Web portal
Receiving a shipment installation methods
When receiving a shipment, check the condition of the goods and report any damage in transit to the shipping company. Do not unpack the units until just before they are due to be installed, and make sure they are as close as possible to the installation site when unpacking them. Do not place heavy articles of any sort on them.
Supply voltage
Check that the supply voltage and frequency correspond to the values of the
unit to be installed.
NOTE: All performances data certified by Eurovent are based on 50Hz
application. Carrier doesn’t ensure the same performances when the unit
operates at 60Hz; the RPM and power input of the fan-motor are usually higher.
WARNING: Failure to take proper account of the above advice and
unauthorised modification of the electrical connections will render the
Carrier warranty on the product null and void.
SAFETY CONSIDERATIONS
WARNING: Switch off the main electrical power supply to the unit and accessories (if installed) before doing any work on the unit.
General
Installing, commissioning and servicing of the various component (unit,
control system, hot and cold water system, air distribution system) can be
dangerous unless certain aspects of the installation, such as the presence of
mains electricity and hot or cold water in the air conditioning equipment, are
taken into account. Only specially trained and qualified technicians and
installers who have been fully trained on the product concerned are authorised
to install, commission and service this equipment.
During service work, it is essential to apply all recommendations and
instructions given in service leaflets, on labels or in the instructions
delivered with the equipment, and to comply with any other relevant
instructions.
- Definition of the pictograms used:
- Electrical danger Fig. 5
- Caution hand hazard Fig. 6
- General danger Fig. 7
Comply with all safety rules and regulations currently in force. Wear eye protectors and work with hand gloves and any individual protection equipment following local legislation. Take care when moving or positioning of the equipment.
Protection against electrocution
Only personnel qualified to perform electrical and maintenance work may make
electrical connections. In particular it is obligatory to disconnect all power
supplies to the unit and its accessories before carrying out any work.
Disconnect the main power supply with an isolating device (not supplied by
Carrier).
IMPORTANT: The components, which make up the different control loops
described in this manual include electronic items. As such, they may generate
or be harmed by electromagnetic interference unless they are installed and
used in accordance with these instructions. The components making up these
control systems conform to the requirements of electromagnetic compatibility
in residential, commercial and light industrial areas. They also comply with
the low-voltage directive.
If the product is supplied without a Carrier control device, verification of
EMC conformity is the responsibility of the installer.
General installation conditions
IMPORTANT: The Carrier numeric controller, power module, or in general units fitted with controls loops must have an isolating device upstream (for example a double-pole circuit breaker). If necessary, an easily operated emergency stop device (such as a punch-button switch) must cut off the power to all equipment. The installation must be equipped with a device to protect against earth faults. The disconnect device must simultaneously disconnect the two poles (phase and neutral), and have a distance of at least 3 mm between the contacts, in compliance with the installation instructions. The mains power cable must have 3 conductors (blue, brown, green/yellow) and its cross section and type must comply with the specifications set out by the applicable EN or IEC standard. Refer to the selection sheet or the name plate to determine the maximum input current. These devices are not supplied by Carrier.
- In general terms, the following rules must be applied:
Upstream over current protection Standard units without electrical heater and controllers
Fuse rating recommendation
Unit size| Fuse type| Fuse rating [A]
0| ****
gG
| ****
4
1
2
Standard units with electrical heaters and no controllers Fuse rating recommendation
Standard units with electrical heaters and no controllers
Fuse rating recommendation
Unit size| Electrical Heater size [W]| Fuse type| Fuse rating [A]
0
| 500| gG| ****
4
800
1
| 500
800
1000| ****
6
2
| 500
800
1000
1600| 8
- Electrical connections must be made according to the wiring diagram provided with the unit and the installation and operation manual of the controller.
- Units must be provided with over-current protection upstream (not supplied by Carrier).
- Daisy chain is forbidden (supply others units from the terminal block of one of them, cf Fig. 8).
- The power disconnection device must be clearly labelled to identify which items of equipment are connected to it.
- The wiring of the components which make up the different control systems and the communication buses must be carried out in accordance with the latest rules and regulations by professional installers.
- The power supply cable must be doubly insulated and fixed using a cable clamp. A hole is provided for this purpose in the plastic Carrier controller housing. The cable must be clamped on the outer insulation.
- The control loop components must be installed in an environment, which conforms to their index of protection (IP).
- The maximum level of pollution is normally pollutant (level 2) and installation category II.
- The low-voltage wiring (communication bus) must be kept physically separate from the power wiring.
- In order to avoid interference with the communication links
- Keep low-voltage wiring away from power cables and avoid using the same cable run (a maximum of 300 mm in common with the 230 V a.c., 30 A cable).
- Do not pass low-voltage wires through loops in the power cables.
- Do not connect heavy inductive loads to the same electrical supply (circuit breaker) used by the controllers, power modules or speed controllers.
- Use the screened cable type recommended by Carrier and make sure all cables are connected to the controllers and power modules.
Caution for the control of the unit
IMPORTANT: It is not permitted to connect several units to the same control device (electronic NTC controller, WTC controller, or any other third party controller). Carrier electronic Thermostat type A&B for AC motors require additional accessory board to allow master/slave function. Carrier electronic Thermostat type C&D for EC motors can be connected up to 10 units, refer to thermostat installation manual instructions.
Conformity
Déclaration of conformity UE
This unit complies with the provisions of European Directives:
- 2006/42/EC (Machinery)
- 2014/30/EU (EMC)
- 2011/65/EU (RoHS)
- Electronic Equipement Regulations 2012
- 2009/125/EC (Eco Design) and reglement 327/2011/EU
- REGLEMENT (CE) no 1907/2006 (REACH)
INSTALLATION OF THE UNIT
Preliminary checks
For all procedures, switch off the unit power supply at the isolator provided
for the purpose during installation (isolator not supplied by Carrier).
CAUTION: After disconnecting power supply, keep the unit idle for
15-20min to cool heating circuit temperature
- Disconnect the power supply and connection cables.
- Close the isolating valves on the manifolds.
- Disconnect the flexible water pipes by unscrewing the gas connectors.
WARNING: Since the flexible water pipes do not have drain valves, a receiver must be provided to allow the cooling coil to be drained.
- Disconnect the supply air ducts.
- Disconnect the flexible condensate drain pipe. Drain the siphon into a suitable vessel.
- Support the unit lightly and release it by unscrewing the four nuts on the threaded hangers. Lower or lift the unit carefully according to unit type (floor or ceiling).
Installing the unit in the false ceiling / False floor
The positioning of the unit must not create an obstacle that may lead to an
unequal distribution and/or return flow of the air. The ceiling/floor must be
sufficiently even to allow a simple installation without danger from the
unit. The supporting structure must be able to carry the unit weight and
prevent deformation, breaks or vibrations during operation.
INSTALLATION PRECAUTIONS: During the installation process, remove all debris
and construction material from the ducts to prevent any damage to the unit.
Installation procedure
NOTE: The fan-coil units are delivered upside down when stacked on a pallet.
- Place the unit close to where it will be installed. For installation in a false floor/ceiling use a hydraulic lift and a folding ladder to make the task easier (Fig. 9).
- Check that the clearances around the unit are sufficient to allow easy maintenance. Please refer to the diagram that shows the service clearances.
- Mark the position of the threaded hangers on the floor/ceiling (if several units need to be installed, it may be advisable to produce a drilling template). The method of fixing the threaded hangers (not supplied by Carrier) depends on the ceiling/floor type (maximum diameter of the threaded hangers is 10 mm). Once the threaded hangers are fixed to the ceiling, tighten the first nuts.
‘Without filter’ unit must be connected to an air ductwork. It is not allowed
to operate the unit without any filter and with a free inlet at the same time.
Lift/place the unit and align it on the threaded hangers, insert the second
nuts and tighten them slightly
NOTE: At this point do not tighten the nuts fully and do not clamp the
unit up to the ceiling or on the floor (leave a space between the
ceiling/floor and the unit). The nuts will be adjusted finally, when the unit
has been connected to the pipework and ducts and levelled.
Level the unit according images section (Fig.10).
Adjust the hanger nuts so that the unit is inclined 0.5% towards the
condensate drain pan. In the other direction (air flow direction) the unit
must be perfectly level (Fig.10).
Condensate drain pipe (Fig. 11): Use a flexible pipe with an inside diameter
of 16 mm and provide a constant fall of 20 mm/m over the whole horizontal pipe
run. Install a 50 mm (minimum) siphon to prevent gases and odors from flowing
back into the ceiling/floor void.
WARNING: After drain pipe connection, control clamping of the drain pipe
and be sure there is no water leakage.
If several units are connected to a common collector, a device must be
installed (Fig. 13). Before operating the unit, ensure that the water flows
into the internal condensate drain pan by pouring some water into it. If
problems are detected, check the drain pipe slope and look for possible
obstructions. In all cases the connection duct(s) at the unit outlet must be
insulated to prevent any condensation on the walls.
NOTE: The pressure losses of these ducts must be compatible with the unit
performance. The duct must be as smooth as possible. Avoid sharp bends. Check
that there are no leaks or kinks, and that there is no dirt or installation
debris inside the ducts. Debris within the ducts might damage the fan wheel
and the damper in the air diffusers.
Once installation is complete – i.e. when the unit is attached to the
ceiling/floor, air ducts are complete, water manifolds are in position with
stop valves ready on the connection stubs, and electrical installation is
prepared; then connect the water pipe (1/2” gas screw connector).
WARNING: Be sure that the coil protective caps are removed before
connecting the water pipes (see Fig.19).
NOTE: Each fan-coil units shall be connected with water flexible pipes in
order to avoid any damage due to vibrations.
Ensure that a gasket (not supplied by Carrier) is installed between the screw
connector and the stop valve.
When all units are installed, open the stop valves on the manifolds, bleed and
then pressurize the circuits. To bleed the coils, slightly loosen the purge
screws. The installation can then be started
NOTE: Do not switch on the power until all connections are made and
earthed.
COMPONENTS AND MAINTENANCE
Fan motor assembly removal
- Remove the filter access door in case of units with inlet plenums.
- Remove the filter.
- Remove the bottom panel (ceiling unit) / top panel (floor unit).
- Disconnect the fan power supply and control (0-10V) cables.
- Remove 4 fixing screws and recover the fan assembly.
Refer to Fig. 12 for more details
NOTE: Be careful not to touch the fan blades during the removal process
to avoid unbalancing the fans
Heaters removal
CAUTION: Do not touch the live metal heater elements when the electric heater is connected to the power supply.
- For units with the electric heater option, disconnect the power supply cable to the heater. Withdraw the cable through the cable gland.
Refer to Fig. 13 for more details
WARNING: In case of customer supplied controller, it is the
responsibility of the installer to set up an additional protection relay
corresponding to the electrical heater capacity.
WARNING: With the optional electric heater a minimum air flow must be
maintained else it may damage the unit (see tables below).
Heaters power supply (W)| __
500
| __
800
| __
1000
| __
1600
---|---|---|---|---
Unit size
0| 2Volts| 3Volts| NA| NA
1| 2Volts| 3Volts| 3Volts| NA
2| 2Volts| 3Volts| 3Volts| 3Volts
Drain pan removal
CAUTION: After disconnecting power supply, keep the unit idle for
15-20min to reduce heating circuit temperature.
Ceiling units
- Disconnect in place by a collar (the collar is not supplied by Carrier).
- Remove the bottom panel.
- Retrieve the drain pan by sliding it from the support.
- During the drain pan removal and maintenance, lay the end of the coil on the metal support plate to prevent any damage to the casing.
- Control clamping of the drain pipe and be sure there is no water leakage.
Floor units
- Disconnect the flexible condensate drain pipe held in place by a collar (the collar is not supplied by Carrier).
- Remove the top panel.
- Remove the coil
- Retrieve the drain pan by sliding it from the support.
- During the drain pan removal and maintenance, lay the end of the coil on the metal support plate to prevent any damage to the casing.
- Control clamping of the drain pipe and be sure there is no water leakage.
Water Coil removal procedure
CAUTION: After disconnecting power supply, keep the unit idle for
15-20min to reduce heating circuit temperature.
Ceiling units
- Close the isolating valves on the manifolds.
- Empty the coil by purging (see Fig. 14)
- Remove the flexible water pipes.
- Remove the valve actuators taking care to identify the cooling and heating valves.
- Disconnect the flexible condensate drain pipe held in place by a collar (the collar is not supplied by Carrier).
- Remove the two-way or four-way water flow control valve bodies. Depending on the unit configuration the four-way valve coupling may be fitted with a heating/ cooling changeover switch. If so, do not remove it.
- Remove the bottom panel.
- Retrieve the drain pan by sliding it from the supporyt.
- Remove the coil
- After replacement, ensure that all gaskets are changed (new gaskets fitted) and that the inlet and outlet connections to the coil are made correctly using an appropriate sealing compound applied to the valve body. Bleed all air from the coil during refilling.
Floor units
- Close the isolating valves on the manifolds.
- Empty the coil by purging (see Fig. 14)
- Remove the flexible water pipes.
- Remove the valve actuators taking care to identify the cooling and heating valves.
- Disconnect the flexible condensate drain pipe held in place by a collar (the collar is not supplied by Carrier).
- Remove the two-way or four-way water flow control valve bodies. Depending on the unit configuration the four-way valve coupling may be fitted with a heating/ cooling changeover switch. If so, do not remove it.
- Remove the top panel.
- Remove the coil
- After replacement, ensure that all gaskets are changed (new gaskets fitted) and that the inlet and outlet connections to the coil are made correctly using an appropriate sealing compound applied to the valve body. Bleed all air from the coil during refilling.
WARNING: Take care when tightening the valve body to the coils (15 Nm is
sufficient) to ensure they are not damaged.
CAUTION: Coil inlet/outlet and cooling/heating side positions
Water inlets/outlets, all sizes: Fig. 14.
WARNING: Carefully observe the direction indicated by the arrow on the
valves, based on the valve type.
Spigots Duct connection
These are manufactured from aluminium sheet metal. They are encased inside the
unit. The ducts should be fixed to these spigots using circular collars or
adhesive. Screws and rivets should not be used.
WARNING: In order to guarantee good air tightness, the duct should
overlap the whole of the spigot.
Make sure that the maximum supply air temperature does not exceed 60°C.
Do not lift or support the unit using the spigots, place loads on the spigots
during installation or operation.
Rectangular flanges duct connection
When connecting rectangular flanges to the inlet and the outlet make sure that the duct is pushed closely the unit.
Optional filter and filter access
Description
The Carrier unit is fitted with G3 filter as standard. The G3 filter is
compliant to M1 fire rating (according to NFP 92-507 standard).
Air filter replacement
Air filters should be changed regularly. Filter life depends on the rate at
which the filter becomes clogged, which depends upon the cleanliness of the
working environment.
If clogged filters are not changed they can increase the air pressure drop,
trapped dust particles may be given off and entrained in the air supply, and
the general performance of the unit may be degraded (as the air flow reduces).
NOTE: When installing a unit in a ceiling/floor void, check that no
T-bars will obstruct filter access and removal.
Fresh air controller
Fresh air controller with (adjustable) constant air volume
The unit can be fitted with three ranges of constant and adjustable fresh air
flow. The 3 ranges are 15 to 50 m3/h, 50 to 100 m3/h and 100 to 180 m3/h.
The diameter of the spigot housing the fresh air flow controller is 125 mm.
The fresh air controller can be modified on site by unscrewing and
repositioning the damper of the controller. See fig 17.
IMPORTANT: If the unit is fitted with a return air temperature sensor,
the constant fresh air flow rate must not exceed 50% of the supply air flow
delivered by the unit at minimum speed.
NOTE: To operate correctly the constant fresh air flow controller
requires a differential pressure in the range of 60 Pa to 210 Pa.
Fresh air controller with variable air volume
The unit can be equipped with a variable fresh air flow controller from 0 to
55 l/s (0 to 200 m3/h).
This is connected to the numeric Carrier controller and can regulate the fresh
air intake in using a fixed rate set by the installer that can be
reconfigured as required.
NOTE: With the variable fresh air flow controller the upstream pressure
in the fresh air duct must be 180 Pa. It is available as an accessory.
Fresh air filtration
If the unit is provided without any filter or in the return plenum, it is the
responsibility of the installer to check if the fresh air is filtered
beforehand.
Optional water flow control valves
These valves are either two-way or four-way type (three-way with integral
bypass). The body of the valve is designed to withstand a 15,5 bar (1550 kPa)
bar operating pressure.
With this option, the couple (valve + actuator) is usually normally closed
(NC).Thus, the water flow is null in case of power cut. To fill the
installation, to equalize the water circuits and to purge the units, the
actuators must be connected to the power supply and the valves must be opened
via the controller (thermostats or BMS).
For the replacement of these components refer to the chapter 4.9.4.
Optional balancing valves
Two-way valve with water flow balancing function is embedded with a
differential pressure controller (with or without pressure test points to
control the water flow settings). The setting of the valve is shown in Fig.
16.
The manual control knob (16a) is ready fitted to protect valve stem and pre-
set mechanism and facilitates manual control of valve during commissioning.
Setting procedure:
- Remove control knob from the valve (16a)
- Loosen knurled nut (16b).
- Adjust the desired dial setting with the white knob (16c) – see table below.
- Retighten knurled nut by hand (16d).
WARNING: The valves have to be open when flushing or pressure testing the
system. Strong pressure impacts can damage closed valves.
Differential pressure across the valve’s control path is not allowed to exceed
400 kPa.
230 V – Actuators
Two types of valve actuators are provided: electro thermal actuator (on/off
control) or modulating actuator (3-point).
The actuator supply is 230 V a.c.
24 V – Actuators
Three types of valve actuators are provided: one electro thermal actuator
(on/off control) or two modulating actuators (3-point or 0-10V).
Both modulating actuators can be operated manually with a hexagonal key. The
0-10V command voltage range of the modulating actuator can also be adjusted.
The actuator supply is 24 V a.c.
NOTE: 24V actuators are not compatible with Carrier controllers
(Thermostats A/B/C/D, WTC & NTC).
Actuator replacement procedure
The actuators on both the chilled water and the hot water valves may be
replaced in case of failure.
WARNING: Do not connect on the same neutral wire the valve actuator 24
Vac and the controller.
- Disconnect the power supply to the unit before carrying out any work on a unit.
- Disconnect the actuator power supply cable.
- 230 V type actuator used with the Carrier numeric controller: Disconnect the actuator power supply cable fitted with a quick connector.
- 230 V actuator used with an electronic thermostat: Remove the plastic protection cover held in place with two screws. Disconnect the actuator power supply cable connected to the quick connector. This can be done by pressing down the spring tongue using a screwdriver and pulling out the wire from the appropriate terminal.
- Uncouple the faulty actuator. Refitting is by the reversal of the procedure described above.
WARNING: Ensure that the actuator is firmly screwed to the valve body (maximum torque 15 N·m).
Valve body replacement procedure
- Disconnect the power supply before carrying out any work on a unit.
- Close the isolating valves on the manifolds.
- Remove flexible water pipes.
- Remove the valve actuators taking care to identify the cooling and heating valves.
- Disconnect the flexible condensate drain pipe which is held in place by a collar (the collar is not supplied by Carrier).Remove the two-way or four-way water flow control valve bodies. Depending how the unit is configured, the four-way valve coupling may be fitted with a heating/cooling changeover switch, if so do not remove it.
- Fit the new valve body to the coil (fit new gaskets). Reconnect the flexible condensate drain pipe which is held in place by a collar (the collar is not supplied by Carrier).
- Check that there are no leaks and reconnect the power to the unit.
WARNING: When replacing a valve always ensure that the direction of flow through the valve is as shown by the arrow on the valve body. If the direction of flow is wrong, the valve body will deteriorate rapidly and the flow control will be distorted.
Flexible pipe option
- Minimum bending radius:
- Non-insulated pipes 72 mm
- Insulated pipes 106 mm.
Optional water sensor
- A water temperature sensor can be provided. It has to be installed on the water circuit as described below:
- For 2-pipe coil: the sensor shall be installed on a cooling water pipe (for change-over function). The sensor is installed on a part where the water flow is continuous.
- For 4-pipe coil: the sensor shall be installed on a heating water pipe (for cold-draft function that prevents the operation of the unit when the heating network is off).
NOTE: In case of unit with an electrical box (for Carrier Thermostats), a “switch” is provided as an option instead of the water sensor.
Optional condensate pump
Check the sealing of the hydraulic connection of the condensate pump and
condensate recovery.
- The meaning of the electrical wires is described below:
- Brown – Blue wires: Electrical supply 230V 50/60Hz
- Black – Grey wires: Alarm contact Normally Closed (NC) 250V/8A maxi.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>