Schneider SpaceLogic Sensors Air Quality Sensors – Analog Instruction Manual
- June 6, 2024
- Schneider
Table of Contents
Installation Instructions
SpaceLogic Sensors Air Quality Sensors Analog
Note: A subset of models shown.
Product Description
The SpaceLogic SLA Series of air quality sensors for living space is a flexible multisensor platform for use with BAS controllers designed to accept 4 to 20mA, 0 to 5Vdc, or 0 to 10Vdc outputs. Housings are available in Medium matte white and Optimum faces are available in black and white. All housing types are available with three user interface options: touchscreen, LCD with three buttons, and blank. CO2 and temperature sensors are included with all SLA Series air quality sensors. Models with VOC sensors and relative humidity sensors are also available.
Features
-
Medium matte white housing or optimum glass panel housing available in white or black
-
Field calibratable non-dispersive infrared CO2 sensor
-
Replaceable RH element available in 1% & 2% with NIST certificate
-
VOC sensor available
-
Temperature output on all models
-
61 mm (2.4″) backlit color touchscreen and LCD, three-button display options available
– Digital temperature indication (0.1° display resolution of °F or °C
– Digital humidity indication (0.1% RH display resolution)
– Digital CO2 indication (1 ppm display resolution)
– Selectable temp, RH, and fan speed setpoint (0-10V)
– Configurable screen/button lock and display timeout
– Override -
Selectable 4 to 20mA, 0 to 5V and 0 to 10V analog outputs
-
18-24 AWG screw terminals
Available Products Matrix
SpaceLogic Sensors, Air Quality Sensors – Analog Installation Instructions
Specifications
Operating Environment
Input power| Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Analog output| Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
Operating temp. range| 0 to 50 °C (32 to 122 °F)
Operating humidity range| 0 to 95% RH non-condensing
Housing material| High impact ABS plastic
IP rating| IP 30
CO2 Sensor
Sensor type| Non-dispersive infrared (NDIR), diffusion sampling
Output range| 0 to 2000/5000 ppm (selectable)
Accuracy| ±30 ppm ±3% of the measured value
Repeatability| ±20 ppm ±1% of the measured value
Response time| <60 seconds for 90% step change
VOC Sensor
Sensor type| Solid-state
Output range| 0 to 100% AQI for VOC
Accuracy| ±15% of the measured value
Output scale| 0 to 1,000 ppb of total VOC (TVOC)
AQI table*| Level| Ventilation
Recommendation
| TVOC (ppb)
61%| Greatly increased| >610
20 to 61%| Significantly increased| 200 to 610
10 to 20%| Average| 100 to 200
5 to 10%| Target value| 50 to 100
0 to 5%| Greatly increased| 0 to 50
RH Sensor
HS sensor| Thin-film capacitive, replaceable
Accuracy| ±2% from 10 to 80% RH @ 25°C (77 °F)
Hysteresis| 1.5% typical
Linearity| Included in accuracy specification
Stability| ±1% @ 20°C (68 °F) annually for 2 years
Output range| 0 to 100% RH
Temperature
coefficient
| ±0.1% RH/°C above or below 25 °C (77 °F) typical
Temperature Sensor
Sensor type| Solid-state, integrated circuit
Accuracy| ±0.2 °C (±0.4 °F) typical
Resolution| 0.1 °C (0.1 °F)
Range| 0 to 50 °C (32 to 122 °F)
Display Models
Touchscreen| 61 mm (2.4 in), color, backlit, capacitive, 240x300px
Setpoint: 0-10Vdc. Temperature, humidity, or fan speed selectable
Timeout override: Display timeout
Lockout override: Touchscreen/button lockout
LCD| 52mm (2.05 in), segmented with 3 buttons
Setpoint: 0-10Vdc. Temperature, humidity, or fan speed selectable
Timeout override: Display timeout
Lockout override: Touchscreen/button lockout
Setpoints***
Temperature setpoint| 0 to 10V output
Scale: 10 to 35 °C (50 to 95 °F) /0 to 50 °C (32 to 122 °F)
Humidity setpoint| 0 to 10V output
Scale: 0 to 100% RH
Fan speed setpoint| 0 to 10V output
Off 0V, Low 3.3V, Med. 6.7V, High 10.0V
Override
Override button| Display models feature a momentary-to-ground override button
Wiring Terminals
Terminal blocks| Screw terminals, 18-24 AWG
Screw terminal torque| 0.2 N-m (2.0 in-lbF) max.
Regulatory Information
Agency approvals| UL 916, European conformance CE:
EN61000-6-2
EN61000-6-
EN61000 Series – industrial immunity
EN 61326-1
FCC Part 15 Class B, REACH, RoHS, Green
Premium, RCM (Australia), ICES-003 (Canada),EAC (Russia)
- Air Quality Index for VOC aligns with TVOC levels for IAQ as specified by the WHO (World Health Organization).
** DIP switch selectable.
*** One setpoint type is selectable via a DIP switch on display models only.
Installation
-
Remove the cover from the base at the bottom of the device.
-
Position the sensor base vertically on the wall 1.35 m (4.5ft.) above the floor with the “UP” arrow facing upward. Locate away from windows, vents, and other sources of the draft. If possible, do not mount on an external wall, as this may cause inaccurate temperature readings.
-
Pull 18 or 22 AWG cable(s) through the hole in the backplate.
-
Mount the backplate onto the wall using the screws provided.
-
Connect the wires to the screw terminals. Do not over-tighten the screws.
Wiring diagram: -
Set the DIP switches.
Switch | Function | Description |
---|---|---|
1 | Output mode | ON – 4-20mA output mode enabled |
OFF – Voltage output mode enabled
2| Voltage output range*| ON – 0-5V output range enabled
OFF 0-10V output range enabled
3| CO2 output range| ON – 0-2000 ppm CO2
output range enabled
OFF – 0-5000 ppm CO2 output range enabled
4| Automatic Baseline Calibration (ABC) for CO2| ON – ABC enabled
OFF – ABC disabled
5| Setpoint output
type
| ON – Temperature setpoint enabled (temp range selected on DIP switch 6)
OFF – RH or Fan Speed setpoint enabled (specific setpoint output type to be selected on DIP witch6)
Models without RH option select only temp or fan setpoint
6
7
| Setpoint output temperature range or RH/Fan Speed output type| Temperature
setpoint (must be enabled on DIP switch 5)
ON – Temp range 1, 50 to 95 °F
(10 to 35 °C) enabled
OFF – Temp range 2, 32 to 122 °F
(0 to 50 °C) enabled
RH or Fan Speed setpoint (must be enabled on DIP switch 5) ON – RH setpoint
enabled OFF – Fan Speed setpoint enabled Models without RH option, set to
OFF
7| Display times out and turns off after 6-10 seconds of touchscreen/ button
press| ON – Display Timeout enabled
OFF – Display Timeout disabled
8| Touchscreen touch functions and buttons are disabled| ON – Touchscreen
touch/button functions disabled
OFF – Touchscreen touch/button functions enabled
- Only used with voltage output mode enabled. Not applicable to setpoint output. Setpoint is 0-10V fixed.
7. With the sensor base fully installed, align the top of the cover to mounting tabs on top of the sensor base. Swing cover downward until it latches at the bottom
8. Install locking screw to secure cover in the closed position.
9. 400 ppm baseline calibration allows the sensor to be set at 400 ppm. Push and hold the calibration button for 3 to 5 seconds. The LED will flash green. Once the button is released, calibration is complete and the LED switches off.
Touchscreen Operation
Main Screen
The touchscreen user interface displays applicable sensor output values
(temperature, RH, CO2, and VOC), setpoint value, menu button, and CO2
stoplight status (if enabled).
Menu Screen
The menu screen opens when pressing the Menu button on the main screen.
Integrator’s submenu, occupancy/override, Fahrenheit/Celsius, settings,
setpoint submenu (temp, RH or fan, determined by DIP switch settings), and CO2
stoplight buttons are displayed on the menu screen.
Menu Button Functions
Integrator’s Submenu Press this icon to access the Integrator’s menu.
Occupied Override Button
Press this icon to provide momentary ground output to the controller
****Single Press Only
Signals occupied/override call to controller.
Fahrenheit/Celsius Switch
Press this icon to display either °C or °F.
Single Press Only
Changes units to Fahrenheit when pressed.
Changes units to Celsius when pressed.
Settings
This icon provides the ability to change the color scheme of the display.
Temp Setpoint Adjustment
Click this icon to access the setpoint change menu. Mutually exclusive with
fan speed, set by DIP switch.
Humidity Setpoint Adjustment
Click this icon to access the setpoint change menu. Mutually exclusive with
humidity and fan speed. Set by DIP switch.
Menu Button Functions (cont.)
Fan Speed
Click this icon to access the fan speed menu. Mutually exclusive with humidity
and fan speed. Set by DIP switch.
CO2 Stoplight Menu
Click this icon to toggle the CO2 Stoplight feature on and off. With CO2
Stoplight turned on, the background color of the main screen changes with the
CO2 level. This provides a visual indicator of CO2 levels to the room
occupants.
LCD Display Operation
Button Functions
Display Icons
The main screen displays sensor values for CO2, VOC (if equipped), RH (if
equipped), temperature, and Celsius/Fahrenheit.
Setpoint Function
A single 0-10V set point (temperature, RH (if equipped), or fan speed) can be selected via a DIP switch.
Temperature Setpoint Adjustment
RH Setpoint Adjustment
Fan Speed Setpoint Adjustment
Changing Celsius and Fahrenheit scales
Occupied/Override Button
China RoHS Compliance Information
Environment-Friendly Use Period (EFUP) Table
Hazardous Substances
Part Name| (Pb)| (Hg)| (Cd)| (Cr (VI))| (PBB)| (PBDE)
Electronic| X| 0| 0| 0| 0| 0
This table is made according to SJ/T 11364.
O: indicates that the concentration of a hazardous substance in all of the
homogeneous materials for this part is below the limit as stipulated in GB/T
26572.
X: indicates that concentration of a hazardous substance in at least one of
the homogeneous materials used for this part is above the limit as stipulated
in GB/T 26572
Z000057-0B
USA: +1 888-444-1311
Europe: +46 10 478 2000
Asia: +65 6484 7877
www.schneider-electric.com
© 2021 Schneider Electric. All rights reserved. All trademarks are owned by
Schneider Electric Industries SAS or its affiliated companies.