ICPDAS tM-AD8C 8 Channel Isolated Current Input Module User Guide

June 6, 2024
ICPDAS

ICPDAS tM-AD8C 8 Channel Isolated Current Input
Module

ICPDAS tM-AD8C 8 Channel Isolated Current Input Module

Congratulations on purchasing the tM-AD8C – the most popular automation solution for remote monitoring and control applications. This Quick Start Guide will provide information needed to get started with the tM-AD8C. Please also consult the User Manual for detailed information on the setup and use of the tM-AD8C.

INSIDE BOX

In addition to this guide, the shipping box includes the following items:

  • tM-AD8C

  TECHNICAL SUPPORT

ICP DAS Website

http://www.icpdas.com/

Understanding the Hardware Specifications and Wiring Diagrams

Before installing the hardware, you should have a basic understanding of hardware specifications and the wiring diagrams.

System Specifications:

ICPDAS tM-AD8C 8 Channel Isolated Current Input Module FIG
2 I/O Specifications:
Wire Connection:
  Pin Assignment:

Booting the tM-AD8C in Init Mode

Make sure the switch placed in the “Init” position.

Connecting to the PC and the Power Supply

The tM-Series series is equipped with an RS-485 port for connection to a 232/USB converter to PC

ICPDAS tM-AD8C 8 Channel Isolated Current Input Module FIG
7

Installing the DCON Utility

The DCON Utility is an easy-to-use tool designed to enable simple configuration of I/O modules that use the DCON protocol.

The DCON Utility can be obtained from the companion CD or from the ICPDAS FTP site:
CD:\Napdos\8000\NAPDOS\Driver\DCON_Utility\setup\
http://ftp.icpdas.com/pub/cd/8000cd/napdos/driver/dcon_utility/

Step 2: Follow the prompts to complete the installation

After the installation has been completed, there will be a new shortcut to the DCON Utility on the desktop.

Using the DCON Utility to Initialize the tM-Series Module

The tM-Series is an I/O module based on the DCON protocol, meaning that you can use the DCON Utility to easily initialize it.

Step 1: Run the DCON Utility

ICPDAS tM-AD8C 8 Channel Isolated Current Input Module FIG
9   Step 2: Use the COM1 port to communicate with the tM-Series

Click the “COM Port” option from the menu and a dialog box will be displayed that will allow you to set the communication parameters as described in the table below.

ICPDAS tM-AD8C 8 Channel Isolated Current Input Module FIG
10  Step 3: Search for the tM-Series module

ICPDAS tM-AD8C 8 Channel Isolated Current Input Module FIG
11   Step 4: Connect to the tM- Series

After clicking on the name of the module in the list, a dialog box will be displayed. ICPDAS tM-AD8C 8 Channel Isolated Current Input Module FIG
12  Step 5: Initialize the tM-Series module

Rebooting the tM-Series  Module in Normal Mode

Make sure the INIT switch is placed in the “Normal” position.

Starting the Module Operation

After rebooting the tM-Series module, search for the module to make sure the settings have been changed. You can double click on the name of the module in the list to open the configuration dialog box.

ICPDAS tM-AD8C 8 Channel Isolated Current Input Module FIG
14

Modbus Address Mapping

Address Description Attribute
30001 ~ 30004 Counter value of digital input R
40481 Firmware version (low word) R
40482 Firmware version (high word) R
40483 Module name (low word) R
40484 Module name (high word) R
40485 Module address, valid range: 1 ~ 247 R/W
40486 Bits 5:0

Baud rate, valid range: 3 ~ 10 Bits 7:6

00: no parity, 1 stop bit

01: no parity, 2 stop bit

10: even parity, 1 stop bit

11: odd parity, 1 stop bit

| R/W
40488| Modbus response delay time in ms, valid range: 0 ~ 30| R/W
40489| Host watchdog timeout value, 0 ~ 255, in 0.1s| R/W
40492| Host watchdog timeout count, write 0 to clear| R/W
10033 ~ 10036| Digital input value of channel 0 ~ 3| R
10065 ~ 10068| High latched values of DI| R
10073 ~ 10076| High latched values of DO| R
10097 ~ 10100| Low latched values of DI| R
10105 ~ 10108| Low latched values of DO| R
00001 ~ 00004| Digital output value of channel 0 ~ 3| R/W
00129 ~ 00132| Safe value of digital output channel 0 ~ 3| R/W
00161 ~ 00164| Power on value of digital output channel 0 ~ 3| R/W
00193 ~ 00196| Counter update trigger edge of channel 0 ~ 3| R/W
00513 ~ 00518| Write 1 to clear counter value of channel 0 ~ 3| W
00257| Protocol selection, 0: DCON, 1: Modbus| R/W
00258| 1: Modbus ASCII, 0: Modbus RTU| R/W
00260| Modbus host watchdog mode 0: same as I-7000

1: can use AO and DO command to clear host

watchdog timeout status

| R/W
Address| Description| Attribute
---|---|---
00261| 1: enable, 0: disable host watchdog| R/W
00264| Write 1 to clear latched DIO| W
00265| DI active state, 0: normal, 1: inverse| R/W
00266| DO active state, 0: normal, 1:inverse| R/W
00270| Host watchdog timeout status, write 1 to clear host

watchdog timeout status

| R/W
00273| Reset status, 1: first read after powered on, 0: not the

first read after powered on

| R

Note: For tM DIO modules, Modbus registers starting at 00033 or 10033 can be  used to read the digital input values. For M-7000 DIO modules, they are 00033 or 10001.

Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. * E-mail: [email protected]