APC BV Series 11089 500VA Universal Outlet User Manual
- June 6, 2024
- APC
Table of Contents
APC BV Series 11089 500VA Universal Outlet
Safety and General Information
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during
installation and maintenance of the UPS and batteries. Inspect the package
contents upon receipt. Notify the carrier and dealer if there is any damages.
- This UPS is intended for indoor use only.
- Mains socket outlet that supplies the UPS shall be installed near the UPS and shall be easily accessible.
- UPS must be connected to an earthed mains socket outlet.
CAUTION
HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
- Battery must be replaced when they reach end of service life.
- Batteries must be replaced when the unit indicates battery replacement is necessary.
- When replacing batteries, replace with the same number and type of batteries originally installed in the unit.
Failure to follow these instructions can result in minor or moderate injury and equipment damage.
-
Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
-
When replacing battery the UPS must be OFF, and its AC inlet unplugged.
-
CAUTION .er a ni seirettab fo esopsid ton oD The batteries may explode.
-
CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the instructions.
-
Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin and eyes.
-
CAUTION A battery can present a risk of electrical shock and high short circuit current.
The following precautions should be observed when working on batteries.- Remove watches, rings or other metal objects.
- Use tools with insulated handles.
- Wear rubber gloves and boots.
- Do not lay tools or metal parts on top of batteries.
- Disconnect the charging source prior to connecting or disconnecting battery terminals.
- Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance
Radio Frequency Warning
This is a category C2 UPS product. In a residential environment, this product
may cause radio interference, in which case the user may be required to take
additional measures.
Place and Power On
-
Place the Easy UPS to avoid:
- Direct sunlight
- Excessive heat
- Excessive moisture
- Excessive dust/dirt
For operation, please place the unit on the floor.
-
Connect the battery by pulling the battery handle up, and then pushing it into the unit.
-
Connect equipment to the UPS. Avoid using extension cords.
-
Plug the Easy UPS power cord directly into a wall outlet, not into a surge protector or power strip.
-
Press the ON/OFF button to turn on the unit.
The green “Power On” indicator confirms that the Easy UPS is on and ready to provide protection. The Easy UPS should charge for at least 6 hours to ensure sufficient runtime. The unit is being charged whenever it is connected to AC power, whether the unit is turned ON or OFF.
Features
-
A ON/OFF button with indicator
-
B Input power cord *only for model with Schuko outlet
-
C Battery backup and surge protected outlets
-
D Battery connector
-
E Circuit breaker
only for model with Schuko outlet -
F AC power inlet with AC fuse
Specifications
Model | BV500I | BV650I | BV800I | BV1000I |
---|---|---|---|---|
Input | Voltage | 230 VAC | ||
Frequency | 50 Hz or 60 Hz | |||
Brownout Transfer | 170 VAC, typical | |||
Over-voltage Transfer | 280 VAC, typical | |||
Output | UPS Capacity (total) | 500VA / 300W | 650VA / 375W | 800VA / 450W |
1000VA / 600W
Voltage On Battery| 230VAC ± 10%
Frequency – On Battery| 50 Hz / 60 Hz ± 1Hz
Transfer Time| 6ms typical
Protection| AC Input Circuit Breaker*
(*only for model with Schuko outlet)
| ****
5A
| ****
5A
| ****
7A
| ****
7A
AC Input Fuse| 5A| 5A| 10A| 10A
Battery| Type (maintenance-free)| 12V, 4.5AH
lead acid
| 12V, 7AH
lead acid
| 12V, 7AH
lead acid
| 12V, 9AH
lead acid
Average Life| The battery typically lasts for three to ve years. Environmental factors impact battery life.
Elevated temperatures, high humidity, poor quality mains power, and frequent, short duration discharges will shorten battery life.
The battery in the Easy UPS Series is not user-replaceable. Contact SEIT Technical Support for a list of authorized service centers near you.
Typical Recharge Time| 6-8 Hours
Physical| Net Weight| 3.9 kg| 4.5 kg| 5.3 kg| 5.7 kg
Dimensions (Hx Wx D)| 9.25 cm x 16.05 cm x 30.5 cm
Wall Mount Installation
- Horizontal installation, use 2 screws 11.1″(282 mm) apart.
- Allow 5/16’’ (8 mm), of the screw to protrude from the wall.
Status Indicators
LED | Audible Alarm | Condition |
---|---|---|
On | Off | On-line – The Easy UPS is supplying AC power to the |
connected equipment
Constant Tone| On Line Overload – The power being used by the connected
equipment has exceeded the capacity of the unit.
Disconnect some equipment.
Constant beeping (every 1/2 second)| Over-temperature – The unit is overheating and will operate in AVR mode for 5 minutes. The Easy UPS will shut down if the temperature is not lowered. Disconnect some of
the connected equipment.
On
(Off during 4 beeps)
| 4 beeps repeated
every 30 seconds
| On-Battery – The Easy UPS is supplying battery power.
Flashing| Constant beeping (every 1/2 second)| Low Battery – The
Easy UPS is supplying battery power and the battery is near a total discharge
state.
Constant tone| Bad Battery Detected – The battery needs to be charged, or
is at end of life.
Off| Short beep every 4 seconds| Low Battery Shutdown – During On
Battery operation
the battery power was almost completely exhausted, and the Easy UPS is waiting for AC power to return to normal.
Constant Tone| On Battery Overload – The connected equipment requires more power than provided by the Easy UPS battery.
Unplug devices one at a time to remove overload.
If the problem is not corrected, contact SEIT Technical Support
Charger Detected Fault – Easy UPS has an internal problem, and is no longer powering the load.
Contact SEIT Technical Support
Long beep every 4 seconds| Over-temperature Protected – The Easy UPS has overheated and has shut down. Unplug connected devices one at a time or wait for a few hours for system to cool down.
Operational Features
Automatic Voltage Regulation (AVR)
Automatic Voltage Regulation boosts/trims the AC voltage when it drops/exceeds
levels.
This allows the equipment plugged into the unit to operate during low/high
voltage conditions, conserving the battery power in the event of a power cut.
The Easy UPS will switch to battery power if the input voltage level becomes
too low/high for the Automatic Voltage Regulation to compensate, or if the AC
power is distorted.
Troubleshooting
The Easy UPS will not turn on
The Easy UPS has not been turned on. | Press the ON/OFF button. |
---|---|
The Easy UPS is not connected to AC power, | Make sure the power cord is |
securely connected to the
there is no AC power available at the wall| wall outlet, and that there is AC
power available at the
outlet, or the AC power is experiencing a| wall outlet.Where applicable, check
that the wall
brownout or over voltage condition.| outlet is switched on.
The battery is disconnected.| Refer to the Place and Power On on page 2.
Connected equipment loses power
A Easy UPS overload condition has occurred.| Remove all nonessential equipment connected to the outlets. One at a time reconnect equipment to the Easy UPS.
Charge the battery for 24 hours to make sure it is fully charged. If the overload condition still occurs, replace the battery.
---|---
The Easy UPS battery is completely discharged.| Connect the Easy UPS to AC
power and allow the battery to recharge for ten hours.
Connected equipment does not accept the step-approximated sine waveform from
the Easy UPS.| The output waveform is intended for computers and peripheral
devices. It is not intended for use with motor driven equipment.
The Easy UPS may require service.| Contact Schneider Electric Technical
Support for more in depth troubleshooting
The ON/OFF button is green and ashing every 30 seconds. 4 beeps repeated every 30 seconds.
The Easy UPS is operating on battery power.| The Easy UPS is operating
normally on battery power. At this point the user should save all open les,
and shutdown the computer. When AC power is restored the battery will
recharge.
---|---
The ON/OFF button ashes green and constant beeps every 1/2 second.
The Easy UPS battery has approximately empty and will shutdown| The Easy UPS
battery is near a total discharge state. At this point the user should save
all open les, and shutdown the computer. When AC power is restored the
battery will recharge.
---|---
The Easy UPS has an inadequate battery runtime
The battery is not fully charged.
The battery is near the end of useful life and should be replaced.
| Leave the Easy UPS connected to AC power for ten hours while the battery charges to full capacity.
As a battery ages, the runtime capability decreases.
---|---