PANDUIT VS-AVT-C02-L03 Absence of Voltage Tester Instruction Manual
- June 9, 2024
- PANDUIT
Table of Contents
- PANDUIT VS-AVT-C02-L03 Absence of Voltage Tester
- Product Information: VeriSafe AVT
- Components
- Cleaning Instructions
- Warranty
- Safety Information
- Components
- Technical Specifications
- Dimensions
- Schematics
- Installation Considerations
- Installation Instructions
- Commissioning Checklist
- Operating Instructions
- Troubleshooting
- Maintenance
- Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
PANDUIT VS-AVT-C02-L03 Absence of Voltage Tester
Product Information: VeriSafe AVT
The VeriSafe AVT (Absence of Voltage Tester) is a product designed to ensure safe operation of electrical equipment by verifying the absence of voltage. It contains electronic circuit boards in both the Indicator and Isolation Modules, and comes with a set of redundant dry contact signal outputs for optional use with control systems. The product has two models: VS-AVT-C02-L03 and VS-AVT-C08-L10.
Safety Information
It is important to follow the instructions and warnings in the instruction
manual to ensure safe operation of the AVT. Failure to do so may result in
product failure, electrical shock, severe injury, or death. If any problems
occur during installation, operation, or maintenance of the VeriSafe AVT,
contact Panduit using one of the technical support or customer service numbers
listed in the manual.
Components
- AVT System Cable
- Indicator Module
- Isolation Module
- Instruction Label
- Sensor Lead Wires
- Output Contacts
Battery Replacement
The Indicator Module contains a lithium battery that needs to be removed
when decommissioning. To replace the battery:
- Turn off power to the AVT and disconnect all cables.
- Remove the Indicator Module from the Isolation Module.
- Locate the battery compartment on the Indicator Module and remove the old battery.
- Insert a new lithium battery with the positive side facing up.
- Reinstall the Indicator Module onto the Isolation Module.
AVT System Cable Removal
If the AVT System Cable needs to be removed:
- Turn off power to the AVT and disconnect all cables.
- Locate the AVT System Cable connector on the Isolation Module and gently pull back the locking tab.
- Remove the AVT System Cable from the Isolation Module.
O-ring Replacement
If the O-ring on the Indicator Module needs to be replaced:
- Turn off power to the AVT and disconnect all cables.
- Remove the Indicator Module from the Isolation Module.
- Locate the O-ring on the Indicator Module and remove it.
- Insert a new O-ring onto the Indicator Module.
- Reinstall the Indicator Module onto the Isolation Module.
Cleaning Instructions
To clean the VeriSafe AVT:
- Turn off power to the AVT and disconnect all cables.
- Wipe down the Indicator and Isolation Modules with a soft, dry cloth.
- If necessary, use a damp cloth with mild soap to clean the modules. Do not use abrasive cleaners or solvents.
Visual Inspection
Before using the VeriSafe AVT, perform a visual inspection to ensure that
there is no damage to the product or its components. If any damage is found,
do not use the product and contact Panduit for assistance.
Warranty
The VeriSafe AVT comes with a warranty. For more information on the warranty, refer to the instruction manual or contact Panduit.
The VeriSafe Absence of Voltage Tester is a permanently-mounted tester that is
used to verify a circuit is de-energized prior to opening an electrical
enclosure. Once installed, a push of a button enables personnel who have been
trained on the operation of the tester to verify the absence of voltage and
see an active indication when the absence of voltage is confirmed. The
Indicator Module is designed for a 30-mm notched panel knockout and the
Isolation Module can be mounted to DIN rail or surface mounted using screws.
TO REDUCE THE RISK OF INJURY, USER MUST READ INSTRUCTION MANUAL
NOTE: In the interest of higher quality and value, Panduit products are
continually being improved and updated. Consequently, pictures may vary from
the enclosed product.
NOTE: Updates to this Instruction Manual may be available. Check
www.panduit.com for the latest version of this
manual.
North America Tech Support: techsupport@panduit.com
Tel: 1-866-405-6654
EU Tech Support : techsupportemea@panduit.com
Tel: +31-546-580-452
Fax: +31-546-580-441
Asia Pacific Tech Support: TechSupportAP@ panduit.com
Telephone:
Singapore: 1-800-Panduit (7263848) Australia: 1-800-Panduit (7263848) Korea:
02-21827300
Safety Information
This manual contains information and warnings which must be followed to ensure safe operation of the AVT. If the AVT is not used as described in this manual, the safety features of the AVT might be impaired. Failure to comply with the warnings and information in this manual could result in product failure, electrical shock, severe injury or death.
Warning:
- Always de-energize power before accessing an electrical enclosure.
- Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
- Use of the AVT does not replace lockout/tagout procedures. The AVT is intended to be used in conjunction with lockout/tagout processes and only addresses the absence of voltage verification step.
- Use proper personal protective equipment (PPE) when working around sources of hazardous electrical energy.
- Do not use this product outside of the specified performance and environmental limits.
- This product must be installed by a qualified electrical worker familiar with local and national electrical codes.
- The AVT will only test for absence of voltage at the point in the circuit where it is installed. If there are other sources of power in the equipment, dangerous voltage may be present.
- Lack of red voltage presence indicators alone does not verify the absence of voltage, the Absence of Voltage test must be initiated followed by the illumination only of the green indicator to verify the absence of voltage.
- The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of absence of voltage. Sensor leads must not be mechanically connected with each other for the device to verify connection to the circuit. Correct function of the device must be verified after installation (see commissioning checklist).
- Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND). Each conductor should have at least one sensor lead set, as shown on the schematic diagrams.
- Excess length from Sensor Leads should be trimmed; Sensor Leads should not be extended with a splice.
- Always comply with local installation codes and standards.
- The product uses a lithium battery that is a fire, explosion and severe burn hazard. Do not crush, recharge, disassemble or heat above 85° C, incinerate, or expose contents to water.
- Use only the included AVT System Cable or approved replacement cables to connect the Isolation Module and Indicator Module. Do not use a standard Ethernet cable.
- Battery, AVT System Cable and O-rings can be replaced. No other part of the product is serviceable. Do not attempt to open the Indicator Module or Isolation Module for repair or modification. When servicing this product, only use specified replacement parts.
- The section of the Indicator Module that is external to the electrical enclosure is approved for wash down when installed in an appropriate enclosure. Before a wash down operation, ensure the o-rings are in good condition, the faceplate is undamaged and fully secured to the unit and the cap is fully installed.
- The AVT System Cable must be separated from the sensor leads and other circuits in the electrical enclosure by a minimum of 0.25 inches (6 mm).
- To prevent damage to the AVT in high-vibration installations, surface mount the Isolation Module using screws and secure the Sensor Lead Wires and AVT System Cable to prevent strain on the connection points.
- If a Sensor Lead separates from the termination point to the power conductor and contacts a low impedance path to ground, the connectivity test can be defeated resulting in a false absence of voltage indication. Ensure all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact.
- The VeriSafe AVT is designed for use in 50/60Hz electrical systems. The AVT should not be installed on sections of a circuit where the AVT is exposed to high frequency energy such as variable frequency drives (VFD) or other circuit elements generating high frequency energy (waveforms exhibiting high Electro-Magnetic Interference (EMI) AC or variable frequency AC power). For more information on where to position the VeriSafe AVT in VFD applications, see the Technical Note available on Panduit.com.
Should a problem occur during installation, operation or maintenance of the VeriSafe AVT, contact Panduit using one of the technical support or customer service numbers listed on the cover of this manual. Contact Panduit if you have any product problems related to the safety function of the product. The product model number and serial number are printed on the Isolation Module and Indicator Module labels.
VeriSafe is a product containing electronic circuit boards in both the Indicator and Isolation Modules. The Indicator Module contains a lithium battery. When decommissioning, remove the battery. Do not discard the battery in the trash; take it to an appropriate battery recycling facility. The Indicator and Isolation Modules can be disposed of at an electronics recycling facility.
Components
The components of the Panduit VeriSafe Absence of Voltage Tester (AVT)
Output Contacts
The AVT includes a set of redundant dry contact signal outputs for optional
use with control systems. These contacts are located on the Isolation Module.
The outputs are normally open and close only when the green Absence of Voltage
Indicator is illuminated. By wiring to these contacts, the AVT can be used as
an input to a control system as well as log when the absence of voltage was
verified.
| Recommended Wiring
For redundant monitoring of output state
| Output Contact Specifications
- Two channel, single-pole, normally open
- Relay closure upon absence of voltage verification
- 5000 Vrms Input/Output Isolation
- Contacts rated for 30 V AC/DC
- Load Current 80 mA AC rms / mA DC
- On-Resistance 30 Ω (max)
- Compatible with up to 16 AWG (1 mm2)
- SIL3 compliant
- Duty Cycle: 10 seconds per test cycle
- Wire Range: 30AWG to 16AWG
- Wire strip length: 5.0mm (min) / 6.0mm (max)
- 4.5 in-lb [0.5 Nm] torque
---|---|---
Technical Specifications
Warning: Do not use this product outside of the specified performance and
environmental limits. Failure to comply with these specifications could result
in product failure, personal injury, or death.
Standards
UL 1436| Standard for outlet circuit testers and similar indicating
devices
---|---
CAN/CSA-C22.2 No. 160| Voltage and Polarity Testers
IEC / UL / CSA C22.2 NO. 61010-1| Safety requirements for electrical
equipment for measurement, control, and laboratory use – Part 1: General
Requirements
IEC / UL / CSA C22.2 NO. 61010-2-03| Safety requirements for electrical
equipment for measurement, control, and laboratory use – Part 2-030:
Particular requirements for testing and measuring circuits
UL 508 & CSA-C22.2 No. 14| Industrial control equipment
IEC 61508-1, -2, and -3 {SIL 3 Rating}| Safety of
Electrical/Electronic/programmable Electronic safety-related security systems
–
Part 1 General Requirements
Part 2 Requirements for Electrical / Electronic / Programmable safety related
systems Part 3 Software Requirements
FCC – CFR 47 Part 15 Subpart B| Radio frequency devices
IEC 61326-1, -3-1, -3-1: corr 1
EN 61326-1, -3-1
| Electrical equipment for measurement, control and laboratory use-EMC
requirements – Part 1 Part 3-1: Immunity requirements for safety-related
systems and for equipment intended to perform safety-related functions
(functional safety) – General industrial applications including corrigendum 1
EN 55011, CISPR 11| Industrial, scientific and medical equipment –
Radio-frequency disturbance characteristics – Limits and methods of
measurement
IEC / EN61000-3-2| Electromagnetic compatibility (EMC) – Part 3-2:
Limits — Limits for harmonic current
IEC / EN61000-3-3| emissions (equipment input current ≤ 16 A per phase)
EN 61000-6-2| Electromagnetic compatibility (EMC) – Part 6-2: Generic
standards – Immunity for industrial environments
KN 61000-6-2| In an industrial environment, General immunity Test Method
KN 61000-6-4| Preventing interference in industrial environments, Test
Method
AS/NZS CISPR 11
| Australian / New Zealand Standard – Industrial, scientific and medical
equipment—Radio- frequency disturbance characteristics—Limits and methods of
measurement
CAN – ICES-001| Industrial, Scientific and Medical (ISM) radio frequency
generators.
CE| Conformity Marking for European Economic Area
RoHS| Restriction of hazardous substances
NOTE: By design and installation guidelines the VeriSafe AVT is not
impacted by the occurrence of phenomena from IEC 61000-4-16
Applications
Electrical System | For use in 1 and 3-phase AC systems |
---|---|
Voltage Detection Range | Up to 600V AC (50/60Hz)*, 600V DC; Rated |
tolerance +10%
Absence of Voltage Threshold| 3 V (See the Installation Considerations
section for additional information)
Overvoltage Category| III (600 V), IV (300 V)
Degree of Protection**| Indicator Module: For Flat Surface Mounting in a
TYPE (UL, NEMA and CSA) 1, 12, 4, 4X, 13, IP66, or IP67 Enclosure, Isolation
Module: Open Type, IP20
- Warning: The VeriSafe AVT is designed for use in 50/60Hz electrical systems. The AVT should not be installed on sections of a circuit where the AVT is exposed to high frequency energy such as variable frequency drives (VFD) or other circuit elements generating high frequency energy (waveforms exhibiting high Electro-Magnetic Interference (EMI) AC or variable frequency AC power). For more information on where to position the VeriSafe AVT in VFD applications, see the Technical Note available on Panduit.com.
**Degree of protection specified is related to the Indicator Module only. To meet the TYPE (UL, NEMA and CSA) 1, 12, 4, 4X, 13, IP66 or IP67 requirements, mount on a flat surface of an enclosure meeting the appropriate UL TYPE or NEMA rating. Verify that the seal and o-rings are clean to ensure proper sealing.
Environment
Operating Temperature| 0°C to 60°C (32°F to 140°F)*
Storage Temperature| -45°C to 85°C (-49°F to 185°F)
Humidity| 5 to 90% non-condensing; Rated 80% at 40°C, decreasing
linearly to 50% at 60°C
Pollution Degree| 3
Altitude| Up to 5000 meters (3.1 miles)
Battery
Type| Industrial 3.6V Lithium AA, see table in Maintenance section for
list of compatible batteries.
Functional Safety
Mode of operation | Continuous, High Demand |
---|---|
Failure Rate | ʎSD |
65 | 371 |
Supported Safety Integrity Levels | SIL3 |
Demand Response Time | 10.1 Seconds |
Device Type | Type A |
Systematic Capability | SC 3 |
Error Handling Response Time | 10.3 Seconds |
Reference Report | PAN 16/01-050 R003 |
Operating Modes | SIL mode only |
*Certain VeriSafe AVT Batteries have expanded operating temperatures. Please see full list of approved VeriSafe replacement batteries to expand for low operating temperature applications.
Dimensions
Isolation Module
Indicator Module
Panel Knockout
The Indicator Module is designed for use with a standard 30 mm knockout with
notch.
The notch should be positioned on top, as shown in the image.
The VeriSafe AVT indicator module can be installed into a maximum panel
thickness of 0.25” [6.35]
Schematics
Warning:
- The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of absence of voltage. Sensor leads must not be mechanically connected with each other for the device to verify connection to the circuit. Correct function of the device must be verified after installation (see commissioning checklist). Failure to comply with these instructions could result in product failure, injury or death.
- Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND). Each conductor should have at least one sensor lead set, as shown on the schematic diagrams.
- If a Sensor Lead separates from the termination point to the power conductor and contacts a low impedance path to ground, the connectivity test can be defeated resulting in a false absence of voltage indication. Ensure that all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact.
Three-Phase Delta: 3 Wire + PE
Three-Phase WYE: 3 Wire + Neutral and PE
Three-Phase WYE: 3 Wire + PE (No Neutral)
Three-Phase WYE High Resistance Ground: 3 Wire + Neutral and PE
Single-Phase: 2 Wire + PE
Single-Phase: 2 Wire + PE, Redundant Detection Lead
Single-Phase: 3 Wire + PE
Corner Grounded DELTA: 3 Wire + PE ****
High-Leg DELTA: 3 Wire + Neutral + PE
DC System: 2 Wire + PE
DC System: 2 Wire + PE, Redundant Detection Lead
Installation Considerations
This section provides guidelines for installing VeriSafe Absence of Voltage Testers (AVTs). It also addresses several common application scenarios and describes best practices.
General Information
Before installing the AVT, identify all sources of electrical energy in the
equipment. Install the AVT at the point in the circuit where you would
normally test for voltage. The AVT will only test for voltage at the point
where it is installed. If there are multiple energy sources or multiple test
points, consider using multiple AVTs.
The AVT may be installed on the supply (line) or load side of an electrical
disconnect. When the AVT is installed, mark the test location on the yellow
Instruction Label. Apply this label to outside of enclosure near the Indicator
Module.
The Voltage Presence indicators only illuminate red when hazardous AC voltage
is detected. The absence of voltage test will verify absence of any voltage
(AC and DC) before the Absence of Voltage Indicator is illuminated green.
The AVT is required to be solidly grounded and bonded to the protective
conductor terminal of the enclosure. Review the Schematics section of this
Instruction Manual. Although the absence of voltage threshold is 3.0 V,
residual voltages should be less than 1.3 V to ensure optimal reliability.
When installing an AVT, care should be taken to ensure that Sensor Leads used
to connect the AVT to the circuit conductors and to ground shall not be any
longer than necessary and shall be routed to avoid sharp edges, pinch points
or mechanical damage. Do not extend the sensor leads with a splice.
Always follow instructions in this Instruction Manual. Do not exceed specified
environmental or performance limits.
Effect on Short Circuit Current Rating (SCCR)
AVTs listed to UL 1436 are required to operate as a secondary circuit that is
isolated from the circuit conductors by use of a transformer, optical
isolator, or limiting impedance, or other similar means. This is intended to
reduce the risks of both electric shock and thermal hazard. These isolation
circuits allow very limited current flow, if any, through the AVT.
The VeriSafe AVT is suitable for use on circuits delivering up to 300,000 rms
symmetrical A at 600 V.
Use of Overcurrent Protection
Installation of an AVT with overcurrent protection is neither required nor
recommended. UL 1436 requires AVTs to be constructed so that internal
component failures will not expose the AVT to available short circuit currents
from the main power supply during normal operation and under single-fault
conditions. The VeriSafe AVT Isolation Module uses high impedance to limit
voltage and current flow through the device to safe levels. In addition, the
VeriSafe AVT has been tested to withstand transient overvoltage up to 6 kV. In
the United States and Canada, the sensor leads of the AVT can be treated as a
feeder circuit per NEC article 240.21(B)(1)(b) Exception (NFPA 70: 2017) and
Canadian Electrcial Code 14-100(b) respectively. This rule allows a tap of no
more than 10 feet on a feeder circuit without the need for overcurrent
protection. Additionally, overcurrent protection for leads over 12” is not
applicable for VeriSafe AVTs in UL 508A environments.
In certain regions and countries, additional overcurrent protection is
required to conform to standards such as AS/NZS3000. When required, the
VeriSafe AVT can be installed safely with overcurrent protection. When
installing overcurrent protection with the VeriSafe AVT, it is important to
install one overcurrent protection device for each of the six sensor leads.
Overcurrent protection should not be installed with the two green ground
leads. Do not install multiple lead wires on one overcurrent protection device
in a configuration that would leave lead wire pairs electrically connected in
the event that the overcurrent protection is in the open state.
Termination Recommendations
The VeriSafe AVT is provided with a total of (8) 14 AWG (2 mm2) sensor leads
(two sensor leads for each phase conductor and ground connection point).
Sensor leads for each phase and ground must not be mechanically connected to
each other for the AVT to function properly (see step 7 in the Installation
Instructions). The second lead on each phase provides the ability for the AVT
to verify that it is in contact with the circuit conductors (each phase and
ground) when the absence of voltage test takes place. It is also part of the
mechanism that is used to “test-the-tester” to validate that the AVT is
functioning. There is no maximum distance limitation between the two leads on
each phase, however there should not be any circuit elements installed between
them. Do not extend the sensor leads with a splice. Use approved connection
methods and follow local codes and standards when terminating the sensor
leads.
AVT sensor lead terminations should be made via a tap to the circuit conductor
using connectors, terminal strips, or power distribution blocks, etc. which
are rated for the application. It is generally preferred to use connection
methods that do not pierce or otherwise compromise the integrity of the
conductor. Connectors that require conductors to be cut or spliced can be used
but may limit the SCCR.
Connectivity Test
Each time the absence of voltage test is initiated, the VeriSafe AVT performs
a series of diagnostics and checks in addition to testing for absence of
voltage. One step in this sequence involves a “connectivity test.” The purpose
of the connectivity test is to ensure that each detection lead is in contact
with a conductor.
The VeriSafe AVT is designed with two Sensor Leads for each phase conductor.
The two leads for each conductor have different functions. The Detection Lead
is used to detect voltage and the Termination Lead is used to verify that the
Detection Lead is in contact with a conductor. The Termination Lead does not
detect voltage. There are no labels distinguishing the Detection and
Termination Leads because it is critical that they are both properly
terminated. If the Detection Lead is not contacting a conductor, the
connectivity test will fail and prevent the AVT from returning a
Green Absence of Voltage indication.
The connectivity test is performed by measuring the discharge time of a
capacitor inside the Isolation Module that is electrically connected to the
detection lead. If the Detection Lead is electrically connected to the
Termination Lead, the discharge time will be inside the desired range and the
test will pass. If the Detection Lead is not in contact with a conductor, the
discharge time will be outside of the desired range and the test will fail. If
the connectivity test fails on any Detection Lead, the green absence of
voltage indicator on the AVT will not illuminate.
IMPORTANT: If the detection lead is not properly terminated to a power conductor and comes in contact with a low impedance path to ground, the discharge time could be inside the desired range and the connectivity test would pass. This would be a multi-fault scenario, but is possible if terminations are not made properly and secured. An AVT installed on a single- phase system might only have one Detection Lead terminated to a power conductor. If the Detection Lead were to become loose and make contact with a low impedance path to ground, the connectivity test would pass. However, voltage would not be detected because the termination lead does not detect voltage and the Detection Lead is no longer in contact with the power conductor. This could result in a green absence of voltage indication, even though the power conductor is energized. This would be less likely to occur with split-phase or three-phase systems as all Detection Lead terminations would need to fail and each detection lead would have to make contact with a low impedance path to ground at the time of the test. However, even the loss of a single detection lead termination on a multi-phase system could result in the scenario described above, if voltage was only present on a single phase.
Utilization of the commissioning test described in this Instruction Manual will verify proper functionality of the AVT at the time of installation. The failure modes described in this section would be the result of Sensor Lead terminations not being maintained over time and Sensor Leads not being secured to the power conductors at time of installation. The likelihood of this scenario can be reduced by securing the Sensor Leads to the power conductor or another nearby rigid feature to prevent movement in the event that the termination point failed. Sensor Leads can be secured using cable ties, clamps, mounts or tape. The sensor leads should be secured at multiple locations, including near the termination point. Additionally, the Schematics section of this Instruction Manual provides redundant detection schematics for both single-phase and DC installations to provide a redundant Detection Lead on the power conductor.
Warning:
Secure Sensor Leads to prevent accidental contact with ground.
Installation Instructions
Warning:
- The AVT must be installed correctly and grounded as described in this Instruction Manual to provide proper indication of absence of voltage. Sensor leads must not be mechanically connected with each other for the device to verify connection to the circuit. Correct function of the device must be verified after installation (see commissioning checklist).
- Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND). Each conductor should have at least one sensor lead set, as shown on the schematic diagrams.
- Excess length from Sensor Leads should be trimmed; lead wires should not be extended with a splice.
- Always comply with local installation codes and standards.
- Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
- If a Sensor Lead separates from the termination point to the power conductor and contacts a low impedance path to ground, the connectivity test can be defeated resulting in a false absence of voltage indication. Ensure that all sensor leads are terminated properly and secured to the power conductor or other nearby rigid feature to prevent movement if the termination fails to remain intact.
Before installation, verify that after power is removed from the circuit to be monitored. The potential measured between each line and ground should be less than 1.3 V, including voltages on the line from auxiliary systems.
| 1. Insert the Indicator Module in the 30mm knockout hole,
align anti- rotation notch. Ensure the rubber washer is on the outside of the
enclosure.| 2. Install the panel nut
with the flange towards the inside surface of the enclosure.| 3. Tighten the panel nut until both it and the sealing washer
make full contact with the enclosure surface. Then, tighten an additional ¼
turn. Tighten the panel nut with fingers only, do not overtighten.
---|---|---|---
| 4. Snap the Isolation Module on the DIN rail. Alternately,
the Isolation Module can be mounted to any surface using three, #8 pan head
screws or another compatible fastener. Surface mounting with screws is
recommended for high-vibration
environments.
| 5. Insert the end of the AVT System Cable with the right-angle connector
in the back of the Indicator Module. Press firmly into the opening until you
feel it latch. Pull back on the connector to verify that it has properly
latched.
6. Insert the other end of the AVT System Cable in the
connector on the bottom of the Isolation Module.
System Cable should be secured using cable mounts or other means to provide
strain relief and prevent damage. Verify that the enclosure door will open and
close without straining the System Cable.
| 7. Terminate the sensor and ground leads. Secure the sensor leads to the conductors and insulate the connections.
- Use of ferrules or terminals is recommended.
- Sensor leads for each phase and ground must not be in direct contact with each other for the AVT to function properly as shown in the figure.
- Sensor leads of the same label designation should be terminated on the same conductor (L1, L2, L3, GND). Each conductor should have at least one sensor lead set, as shown on the schematic diagrams.
- There is no maximum distance limitation between the two leads on each phase, however there should not be any circuit elements installed between them.
- Do not extend the sensor leads with a splice.
- Use approved connection methods and follow local codes and standards when terminating the sensor leads.
- Secure the sensor leads to the conductors to prevent the leads from contacting ground if the termination fails.
- Refer to the Installation Considerations section for additional information.
| 8. Route Sensor Leads and AVT System Cable to avoid sharp edges, pinch points and prevent mechanical damage.
Secure the Sensor Leads with cable ties, clamps, mounts or tape to provide strain relief and prevent movement in the event that the termination point failed.
Insulate the terminations.
|
9. Install Instruction Label directly under or next to the Indicator Module on the exterior of the enclosure (see Note 1). Mark the label to indicate where in the circuit the AVT is installed.
| 10. Install the Cap Label with the appropriate language, if other than English.| 11. Install the battery. See Battery Replacement section of the manual for further details.|
Note 1: The Instruction Label is UL approved for application to galvanized and stainless steel, ABS, polycarbonate, and polyester painted surfaces. It is up to the installer to verify proper bond to other surface types.
Commissioning Checklist
IMPORTANT: The AVT installation test is sensitive to the capacitance of electrical systems. Repeat the Commissioning Checklist when changes to the electrical system are made that add capacitance to the AVT test location.
-
De-energize the circuit that is being monitored by the AVT.
-
Visually inspect the AVT:
- AVT system cable: Verify cable is locked into place on both the Indicator Module and Isolation Module.
- Indicator module: Ensure o-ring is in place. Check that retaining nut is secure. Verify battery is installed and battery cap is locked into place.
- Isolation module: Ensure module is secured to subpanel or DIN rail.
- Sensor leads: Gently pull on each Sensor Lead to ensure termination is secure. Verify that the Sensor Leads are secured to the power conductors or other nearby rigid feature to prevent movement and contact with a ground if the termination fails to remain intact. Verify no wiring is exposed and all terminations are properly insulated. Verify panel is clean and wiring debris is removed from panel. Verify that leads are connected as described in the appropriate wiring diagram from the Schematics section, including verifying that each conductor has two lead wires of matching label designation attached. Verify leads on each phase are not mechanically connected to each other.
- Instruction label: Verify that the label is placed near the isolation module and marked to indicate where the AVT is installed.
-
Record changes to panel documentation.
-
Close panel and secure doors/covers.
-
Press the Test Button to initiate the test. The yellow Caution Indicator should flash rapidly to indicate the test is in progress followed by the Absence of Voltage Indicator illuminated green.
-
Review the Operating Instructions section of this manual before proceeding.
Warning: Always follow your company’s safety procedures when energizing equipment. To avoid electric shock, use proper personal protective equipment when working on or near electrical hazards. -
Energize the system being monitored by the AVT.
-
Verify that the red Voltage Presence Indicators are illuminated.
-
Press the Test Button on the Indicator Module to initiate the absence of voltage test.
-
Look for the yellow Caution Indicator to flash repeatedly before turning to a solid indication.
You should not see the green indicator illuminate when power is energized. -
De-energize the circuit that is being monitored by the AVT.
-
Verify that Voltage Presence Indicators are not illuminated.
-
Press the Test Button on the AVT Indicator Module to begin the absence of voltage test. Look for the yellow Caution Indicator to flash and then the green Absence of Voltage Indicator should illuminate.
Operating Instructions
Warning:
- To avoid electric shock, always de-energize power before entering an electrical enclosure.
- Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
- Use proper personal protective equipment (PPE) when working around sources of hazardous electrical energy.
- Lack of red voltage presence indicators alone does not verify the absence of voltage, the Absence of Voltage test must be initiated followed by the illumination only of the green indicator to verify the absence of voltage.
The AVT should only be operated by individuals who have been trained on the operation of the tester and can demonstrate knowledge of the following criteria:
- Familiar with requirements and information in the Instruction Manual and understand the function of the AVT, meaning of the indicators and markings, and limitations of the Voltage Presence Indicators
- Aware of where the AVT is installed in the electrical system and any additional electrical hazards that may be present in the system that are not detectable by the AVT
- Able to recognize electrical hazards and familiar with lockout/tagout procedures
Test Button: Initiates test
Absence of Voltage Indicator: I lluminates green when the Absence of
Voltage is verified
Caution Indicator: Flashes yellow rapidly to indicate test in process,
illuminates solid to indicate the test has failed and flashes after a solid
illumination to indicate the reason for failure
Voltage Presence Indicators: Three red indicators illuminate when the
presence of hazardous AC voltage is detected. Lack of red voltage presence
indicators alone does not verify the absence of voltage.
Voltage Presence Indicators
- When voltage is detected in one or more phases, the appropriate Voltage Presence Indicators will illuminate.
- Lack of red voltage presence indicators alone does not verify the absence of voltage. To test for absence of voltage, push the Test Button.
| | **
---|---|---
Absence of Voltage Test
** Each time the Test Button is engaged, the absence of voltage test sequence
will be activated. The test sequence includes running a self-check, using a
known voltage source to test the tester to verify that the AVT is functioning,
testing for AC and DC voltage phase-to-phase and phase-to-ground, and
verifying the sensor leads are in contact with the circuit conductors
- De-energize the circuit according to company safety procedures.
- Verify that lockout/tagout devices have been applied to all applicable energy sources and the Voltage Presence indicators are not illuminated.
- Press the Test Button to initiate the absence of voltage test.
- The Caution Indicator will begin to flash. This indicates that the test is in progress.
- When the absence of voltage is verified, only the green Absence of Voltage Indicator will illuminate.
- If the absence of voltage is not verified, the Caution Indicator will illuminate for about five seconds followed by a series of flashes. The number of flashes will help diagnose why the test failed. Refer to the Troubleshooting section for additional information.
|
Troubleshooting
Warning:
- Always de-energize power before accessing an electrical enclosure.
- Always follow safety and lockout/tagout procedures when working on or near electrical systems and equipment.
- Use proper personal protective equipment (PPE) when working around sources of hazardous electrical energy.
- Battery, AVT System Cable and O-rings can be replaced. No other part of the product is serviceable. Do not attempt to open the Indicator Module or Isolation Module for repair or modification. When servicing this product, only use specified replacement parts.
The AVT checks for proper connection of the sensor and ground leads, verifies the battery voltage level is acceptable for proper operation and verifies that the tester is working properly with a series of self checks. If it fails any of these tests, it will indicate a failed test by illuminating the Caution Indicator for approximately 5 seconds. The AVT includes functionality to diagnose and communicate the reasons for test failure with flashing of the Caution Indicator. If the test fails, illumination of the Caution Indicator will be followed by a number of brief flashes ranging from 1-7. The number of flashes can be used to determine why the absence of voltage test failed.
Number of
Flashes
| Description| Recommended Actions
---|---|---
1| Battery voltage too low to run the test| Replace the battery and re-test.
2| Voltage detected above the threshold| Warning: This indicates that the
enclosure is energized.
Follow safety procedures and use the appropriate PPE when investigating the
source of voltage.
If panel has a stored energy source, wait several minutes then re-test to see
if energy has dissipated.
4| Proper installation of the sensor leads could not be verified| Warning:
The enclosure may be energized.
Follow safety procedures and use the appropriate PPE when verifying the enclosure is de-energized before performing additional troubleshooting.
Refer to the Installation Instruction section and verify that the sensor leads are installed properly, and that the device is grounded properly.
If installation is confirmed and the 4-flash code persists, check for high system capacitance and/or inadequate load during AVT test. Contact Panduit Technical Support for additional troubleshooting.
3, 5, 6, 7, or 8| Hardware failure| Contact Panduit Technical Support for additional troubleshooting.
If the Caution Indicator does not illuminate after pressing the Test Button:
- Verify that the battery tray is fully engaged in the housing with the cap installed.
- Replace the battery. If the battery voltage is too low, the Indicator Module will not operate.
- Verify that the AVT System Cable is fully engaged in the connectors on the Indicator and Isolation Modules. The Indicator Module will not function if it is not connected to the Isolation Module.
Should a problem occur during installation, operation or maintenance of the VeriSafe AVT, contact Panduit using one of the technical support or customer service numbers listed on the cover of this manual. Contact Panduit if you have any product problems related to the safety function of the product. The product model number and serial number are printed on the Isolation Module and Indicator Module labels.
Maintenance
Warning:
- The product uses a lithium battery that is a fire, explosion and severe burn hazard. Do not crush, recharge, disassemble or heat above 85° C, incinerate, or expose contents to water.
- The AVT will not work with a standard alkaline 1.5Volt AA battery. Use only approved batteries listed in table shown in the Maintenance section of this instruction manual.
- Battery, AVT System Cable and O-rings can be replaced. No other part of the product is serviceable. Do not attempt to open the Indicator Module or Isolation Module for repair or modification. When servicing this product, only use specified replacement parts.
Battery Replacement
Follow these steps to replace the battery. Table 1 provides a list of
batteries approved for use with the AVT. Do not discard the battery in the
trash; take it to an appropriate battery recycling facility.
Manufacturer| Model Number| Size| Description|
Operating Temperature
---|---|---|---|---
Tadiran| TL-5903| AA, ER14505| 3.6 Volt Lithium Battery| 0°C to 60°C (32°F to
140°F)
Xeno Energy| XLP-060F
Saft| LS14500
Titus| ER14505M| -25°C to 60°C (-13°F to 140°F)
Ultralife| ER14505M
1. Grip the Indicator Module Cap.|
2. Twist the Indicator Module cap counterclockwise approximately 90 degrees, until you feel a stop.
| 3. Remove the cap.| 4. Grip the battery tray and
slide it out until you feel a stop. The battery tray is not intended to be
fully removed.
---|---|---|---
5. Remove used battery.
Dispose according to local procedures.
Install a new battery. The positive terminal should face the operator.
|
6. Slide the battery tray
back in the housing.
A self test is initiated when the battery tray is inserted and connection is
made between the battery and AVT electronics.
|
7. Replace the cap.
|
8. Twist cap clockwise to lock
into place.
Record the date the battery was replaced in equipment documentation.
AVT System Cable Removal
|
- ****Grip the Retention Spring on both sides.
- **** Pull down on the Retention Spring approximately 1/16 inch [1.5 mm].
| ****3. Continue holding the Retention Spring down while pulling back on
the right-angle connector to release the AVT System Cable.
---|---|---
O-ring Replacement
Cap closure O-ring|
Sealing O-ring
---|---
The O-rings can be replaced if they become dry or brittle. In critical sealing applications, such as wash down environments, it is recommended that the O-rings be replaced every 5 years. Apply a light coating of silicone grease to the O-rings to promote sealing and extend O-ring life. Order Panduit SKU VS- AVT-ROR for replacement O-rings.
Cleaning Instructions
The Indicator Module can be cleaned with a damp cloth or isopropyl alcohol
based cleaner. Do not use abrasives or high alkaline cleaners. Do not leave
cleaners on the device for a long period, rinse immediately. Do not apply
cleaners in direct sunlight or elevated temperatures.
The section of the VeriSafe Indicator Module that is external to the
electrical enclosure is approved for wash down as specified by NEMA 4 and IP66
standards. Before a wash down operation, ensure the O-rings are in good
condition, the faceplate is not damaged and fully secured to the unit, and the
cap is fully installed.
Visual Inspection
Periodically inspect the AVT and replace any damaged parts, cables or
terminations.
Inspect the Sensor Lead terminations to ensure they are tight, the leads are
secure and do not show signs of damage. Inspect the AVT System Cable to ensure
it is locked into place on both ends, is secure and does not show signs of
damage. Inspect the Indicator Module to ensure O-rings are not dry or brittle
and that the retaining nut and cap are in place.
The procedure described in the Commissioning Checklist can be performed at any
time.
Warranty
Panduit Limited Product Warranty
- Limited Product Warranty. For purposes of this Limited Product Warranty, “Panduit products” mean all Panduit-branded products that Panduit sells. Unless a different time period is set forth in the Panduit product manual, user guide or other product documentation, Panduit warrants that the Panduit product, and each part or component of the Panduit product, will comply with Panduit’s published specifications and will be free from defects in material and workmanship for a period of 1 year from the date of invoice from Panduit or its authorized distributor, not to exceed 18 months from the original date of shipment from Panduit’s facility.
- Firmware. Unless otherwise provided in a separate license agreement, and subject to the limitations for third-party products set forth below, Panduit warrants that any firmware contained in any Panduit products, when used with Panduit-specified hardware and when installed properly, will perform in accordance with the Panduit published specifications for a period of 1 year from the date of invoice from Panduit or its authorized distributor, not to exceed 18 months from the original date of shipment from Panduit’s facility. Any exceptions to this 1 year warranty period will be identified in the Panduit product manual, user guide or other product documentation. Panduit does not warrant that the operation of the firmware will be uninterrupted or error-free, or that the functions contained therein will meet or satisfy Buyer’s intended use or requirements. Any warranties, if any, that Panduit provides for any standalone software that Panduit sells will be stated in the applicable End User License Agreement.
- Remedies. Panduit’s sole and exclusive obligation and Buyer’s exclusive remedy under this warranty is Panduit’s repair or replacement of the defective Panduit product. Panduit shall have sole discretion as to which of these remedies Panduit will provide to Buyer. Buyer requested on-site warranty service is not covered and will be at Buyer’s sole expense, unless authorized in writing by Panduit in advance of the commencement of the on-site warranty service. Panduit has the right to either examine the Panduit products where they are located or, in its sole discretion, issue shipping instructions for return of the product. Where applicable, Buyer must return the defective product, part or component, transportation prepaid to Panduit’s customer service department accompanied by Panduit’s Return Material Authorization. If Panduit confirms that there is a defect that is covered by this warranty, the repaired or replaced Panduit product will be warranted for the remainder of the warranty period applicable to the originally shipped Panduit product, or for a period of 90 days from the date of shipment to Buyer, whichever is longer.
- No Warranty for Third-Party Products. Panduit makes no representations and disclaims all warranties of any kind, express or implied relative to any third-party product or services, including any third-party software or firmware, which may be incorporated into a Panduit product and/or resold or sublicensed by Panduit. To the extent any warranties extended to Panduit by the third-party manufacturer are transferable, Panduit will transfer such warranties to Buyer and any enforcement of such third-party warranties shall be between the Buyer and the third-party. Panduit does not warrant the compatibility of the Panduit products with the products of other manufacturers or Buyer’s application except to the extent expressly represented in Panduit’s published specifications or written quotation.
- Exclusions. Before using, Buyer shall determine the suitability of the Panduit product for his intended use and Buyer assumes all risk and liability whatsoever in connection therewith. The warranties contained herein shall not apply to any Panduit products that have been subjected to misuse, neglect, improper storage, handling, installation or accidental damage or modified or altered by persons other than Panduit or persons authorized by Panduit. In addition, the firmware warranty does not cover any defects resulting from Buyer-supplied firmware or unauthorized interfacing, operation outside of the environmental specifications for the products, or improper or inadequate site preparation or maintenance by Buyer. Panduit products are not designed, intended or authorized to be used in medical applications or as components in medical devices that are used to sustain or support human life. Should Buyer purchase or use a Panduit product for any such unintended or unauthorized medical application, Buyer shall indemnify and hold Panduit harmless from any liability or damage whatsoever arising out of the use of Panduit products in such medical applications.
- LIMITATION ON LIABILITY. THE WARRANTIES PROVIDED HEREIN ARE BUYER’S SOLE AND EXCLUSIVE WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR USE ARE DISCLAIMED. TO THE EXTENT PERMITTED BY LAW, IN NO EVENT SHALL PANDUIT BE LIABLE FOR ANY LOSS OR DAMAGES ARISING FROM ANY PANDUIT PRODUCT WHETHER DIRECT, INDIRECT, CONSEQUENTIAL, INCIDENTAL OR SPECIAL, INCLUDING WITHOUT LIMITATION ANY CLAIM FOR LOSS OF DATA, LOSS OF ACTUAL OR ANTICIPATED REVENUE, PROFITS OR SAVINGS.
- General. This Limited Product Warranty applies to the Panduit products only and not to any combination or assembly of the Panduit products. Nothing in this Limited Product Warranty shall be construed to provide Buyer with a warranty for any system implementation using Panduit products. The Panduit Certification Plus System Warranty is available for projects that are installed by Panduit Certified Installers, meet various requirements and are registered with Panduit in accordance with the terms of the Panduit Certification Plus System Warranty.
References