SECOP Electronic Unit for BD1.4F-VSD Instructions
- June 6, 2024
- SECOP
Table of Contents
- SECOP Electronic Unit for BD1.4F-VSD
- FIG-7 Operational errors (PC or non PC option)
- FIG-1
- Installation (Fig. 3)
- Power supply (Fig. 1)
- Battery protection (Fig. 2)
- Thermostat (Fig. 1)
- Setpoint selection (Fig. 6)
- Speed selection (Fig. 5)
- Fan (Fig. 1)
- Error handling (Fig. 7)
- Fig. 2 Battery protection settings
- Fig. 4 Wire Dimensions DC
- FIG:6
- Description / Display
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SECOP Electronic Unit for BD1.4F-VSD
FIG-7 Operational errors (PC or non PC option)
Error code or LED flashes| Error type
Can be read out in the software
TOOL4COOL®
---|---
6| Thermostat failure
(If the NTC thermistor is short-circuit or has no connection, the electronic unit will enter manual mode).
5| Thermal cut-out of electronic unit
(If the refrigeration system has been too hea- vily loaded, or if the ambient temperature is high, the electronic unit will run too hot).
4| Minimum motor speed error
(If the refrigeration system is too heavily loaded, the motor cannot maintain minimum speed at approximately 1,850 rpm).
3| Motor start error
(The rotor is blocked or the differential pressure in the refrigeration system is too high (>5 bar)).
2| Fan over-current cut-out
(The fan loads the electronic unit with more than 0.65Apeak).
1| Battery protection cut-out
(The voltage is outside the cut-out setting).
FIG-1
The electronic unit is a dual voltage device. This means that the same unit
can be used in 12V or 24V power supply systems. The maximum voltage is 17V for
a 12V system and 34V for a 24V power supply system. Max. ambient temperature
is 55°C. The electronic unit has built-in thermal protection which is actuated
and stops compressor operation if the electronic unit temperature gets too
high (100°C/212°F on the PCB). It can be connected to a PC through the Secop
Gateway communication interface on the terminal D/I and C (Fig. 1).
Communication gateway modules incl. communication cables can be ordered at
Secop (code no. 105N9518).
The PC interface allows you to configure and measure compressor parameters by
using the software tool TOOL4COOL® supplied by Secop.
Installation (Fig. 3)
Mount the electronic unit directly on the compressor plug and fix it with at least 2 screws.
Power supply (Fig. 1)
The electronic unit must always be connected directly to the battery poles.
Connect the battery to + and battery minus to –. The electronic unit is
protected against reverse battery connection but can only operate in the
described polarity. A fuse must be mounted in the + cable as close to the
battery as possible. A 15A fuse must be used in 12V and 24V systems. If a main
switch is used, it should be rated to a current of min. 20A.
The wire dimensions in Fig. 4 must be observed. Avoid extra junctions in the
power supply system to prevent voltage drop from affecting the battery
protection system
Battery protection (Fig. 2)
The compressor stops and restarts again according to the designated voltage limits measured on the + and – terminals of the electronic unit. The standard settings for 12V and 24V power supply systems are shown in Fig. 2. (PC option) Other settings are (Fig. 5) optional if a connection which includes a resistor (R1) is established between terminals C and P (non PC option).
Thermostat (Fig. 1)
The thermostat is connected between terminals C and T. Either an NTC (electrical thermostat) or a mechanical thermostat can be connected. Three different thermostat modes can be chosen via communication interface or TOOL4COOL®
- Auto (both NTC and mechanical), NTC, or Mechanical. The standard setting is Auto. In case of using a NTC the set point in the range between
- 40ºC and 40ºC is set via software. When using the Auto setting in the software it is not possible to obtain NTC failures, so it is recommended to set the thermostat mode to NTC when using an NTC.
Setpoint selection (Fig. 6)
A temperature setpoint selection is possible in order to utilize the fully intergrated temperature control. To configure the temperature shut off setpoint without a communication interface a 10kΩ potentiometer can be connected between P-Input and C, as shown in Fig. 1 (R2). The po-tentiometer moves the compressor shut off set-point between -20°C and 10°C, it will restart once the temperature raised 3K (Kelvin) (eq. +1kΩ on NTC) (non PC option).
Speed selection (Fig. 5)
In factory default settings the compressor will run with a fixed speed of
4,000 rpm when the ther-mostat is switched on.
Other fixed compressor speeds and start speeds in the range between 2,000 and
4,000 rpm can be obtained when changing the speed settings in the software (PC
option) or resistor R1 (non PC option). A start delay in the range from 0-240
sec. (factory default 4 sec.) after thermostat cut-in can also be chosen. By
default the compressor will start with a speed of 2,500 rpm for the first 30
seconds.
Fan (Fig. 1)
A fan can be connected between the terminals +(F) and F. Connect fan plus to
+(F) and fan minus to F. The output voltage between the ter-minals +(F) and F
is always regulated to 12V, a 12V fan must be used for both 12V and 24V po-wer
supply systems. The fan output can supply a continuous power of 6Wavg. A
higher current draw is allowed for 2 seconds during start. Fan settings can be
adjusted via TOOL4COOL®. Per factory default a missing fan is not detected,
but the detection is configurable via communica-tion interface or TOOL4COOL®.
The unit has to be restarted when fan related set-tings have been changed. If
a fan is used without changing the TOOL4COOL® settings, the fan will run but
no error signal will be sent in case of fan failure. It is also possible to
set a start delay on the fan in the range from 0 – 240 sec. which is only
applied if the fan is not running when the compressor starts. Factory default
setting for fan start delay is 0 seconds. Fan speed can be adju-sted from 40 –
100%.
Error handling (Fig. 7)
If the electronic unit detects an operational error, it is accessible via the
software (PC option). Er-ror codes are defined as shown in Fig. 7.
A 10mA LED can alternatively be connected bet-ween the terminals D/I and +. In
case the elect-ronic unit records an operational error, the diode will flash a
number of times. The number of fla-shes depends on what kind of operational
error was recorded. Each flash will last ¼ second. After the actual number of
flashes there will be a delay with no flashes. The sequence for each error
recording is repeated every 4.2 seconds (non PC option).
Fig. 2 Battery protection settings
Voltage (0.1 steps) | Min. value | Default | Max. value |
---|
12V ± 0.3V DC,
all values
| Cut out V DC| 9.6| 10.4| 17
Cut in diff. V DC| 0.5| 1.3| 10
24V ± 0.3V DC,
all values
| Cut out V DC| 19| 21.3| 27
Cut in diff. V DC| 0.5| 1.3| 10
Fig. 4 Wire Dimensions DC
Size| Max. length 12V operation| Max. length 24V operation|
---|---|---|---
Cross section [mm2]| AWG
[Gauge]|
[m]| [ft.]| [m]| [ft.]|
2.5| 12| 2.5| 8| 5| 16|
4| 12| 4| 13| 8| 26|
6| 10| 6| 20| 12| 39|
10| 8| 10| 33| 20| 66|
R1 [kΩ]| Duty Cycle [%]| Speed [RPM]| Cut in level [V]|
Cut out level [V]| Cut in level [V]| Cut out level [V]|
---|---|---|---|---|---|---|---
open| 0| Maintain| Maintain current value. Can be changed via Modbus
220| 3| –| Maintain current value. Can be changed via Modbus
130| 6| –| Maintain current value. Can be changed via Modbus
91| 9| –| Maintain current value. Can be changed via Modbus| ECO
68| 12| –| Maintain current value. Can be changed via Modbus| ECO off
51| 15| | 9.6 – 34 V DC| Solar
43| 18| | Default| Solar off
36 | 21 | Reset battery only | |
---|---|---|---|
30 | 24 | Reset battery and speed to default value | |
--- | --- | --- | --- |
27 | 27 | 4000 | Maintain current value. Can be changed via Modbus |
--- | --- | --- | --- |
22 | 30 | 4000 | 10.9 |
20 | 33 | 4000 | 11.4 |
18 | 36 | 4000 | 12.4 |
15 | 39 | 4000 | 13.4 |
13 | 42 | 3500 | Maintain current value. Can be changed via Modbus |
--- | --- | --- | --- |
12 | 45 | 3500 | 10.9 |
11 | 48 | 3500 | 11.4 |
9.1 | 51 | 3500 | 12.4 |
8.2 | 54 | 3500 | 13.4 |
7.5 | 57 | 3000 | Maintain current value. Can be changed via Modbus |
--- | --- | --- | --- |
6.2 | 60 | 3000 | 10.9 |
5.6 | 63 | 3000 | 11.4 |
5.1 | 66 | 3000 | 12.4 |
4.3 | 69 | 3000 | 13.4 |
3.9 | 72 | 2500 | Maintain current value. Can be changed via Modbus |
--- | --- | --- | --- |
3.3 | 75 | 2500 | 10.9 |
2.7 | 78 | 2500 | 11.4 |
2.2 | 81 | 2500 | 12.4 |
1.8 | 84 | 2500 | 13.4 |
1.5 | 87 | 2000 | Maintain current value. Can be changed via Modbus |
--- | --- | --- | --- |
1.0 | 90 | 2000 | 10.9 |
0.68 | 93 | 2000 | 11.4 |
0.36 | 96 | 2000 | 12.4 |
0.051 | 99 | 2000 | 13.4 |
FIG:6
Set point [°C] | R2 [Ω] |
---|---|
-20 | 0 |
-19 | 330 |
-18 | 670 |
-17 | 1000 |
-16 | 1330 |
-15 | 1670 |
-14 | 2000 |
-13 | 2330 |
-12 | 2670 |
-11 | 3000 |
-10 | 3330 |
-9 | 3670 |
-8 | 4000 |
-7 | 4330 |
-6 | 4670 |
-5 | 5000 |
-4 | 5330 |
-3 | 5670 |
-2 | 6000 |
-1 | 6330 |
0 | 6670 |
1 | 7000 |
2 | 7330 |
3 | 7670 |
4 | 8000 |
5 | 8330 |
6 | 8670 |
7 | 9000 |
8 | 9330 |
9 | 9670 |
10 | 10000 |
The communication port of the electronic unit (terminal D/I and C) has two functions:
-
Communication mode (PC option):
The first 15 seconds after power-up/wake up, both devices (compressor & PC) try to establish a communication.
In case a successful connection is made, the port will stay in communication mode until next power up/wake up. -
Diode output mode (non PC option):
After 15 seconds with no communication link successfully established, the unit switches to diode output mode.
No communication is possible until next power up/wakes up.
To ensure a trouble-free connection using TOOL4COOL®, the following method is
recommended:
Change the default TOOL4COOL® network setup to allow TOOL4COOL® to search for
the electronic unit every 3 seconds. While TOOL4COOL® is searching, power up
the electronic unit and wait for a connection.
The following shows how to arrange this setup.
Preconditions:
The electronic unit is physically connected via the gateway to the PC, but the
power to the electronic unit is not yet switched on.
In the example to the right, the electronic unit is connected to the COM1
network.
Note:
The Secop LIN gateway has two LEDs that allow debugging of the communication:
RED LED (TX): blinks when TOOL4COOL® sends a command to the electronic unit.
This must blink every second while TOOL4COOL® is trying to establish a
connection with the electronic unit.
GREEN LED (RX): blinks when the electronic unit responds to a TOOL4COOL®
command.
The node address of the electronic unit must match the command from TOOL4COOL®
(The network setting above tells TOOL4COOL® to search for unit node address 1
every 3 sec.).
Description / Display
Step | Description / Display |
---|---|
1 | Do not power up the electronic unit at this stage. If already powered |
up, remove the
supply voltage and allow 5s to power off.
2| Start TOOL4COOL®
3| In case the network is already connected, disconnect it first via
right-click on the specific COM-Port and option Disconnect in context menu.|
4| Allow up to 5s to release the COM-Port from the net- work, then select Connect Network
(below the File menu).
| **
5| Select the correct port from the dropdown menu, in this example COM1
is used.| **
6| Cick Configure.| **
7**| Change Last network node address to 1 and change Refresh rate to
3.
Leave the other settings at their default value and click OK twice.
Now TOOL4COOL® will only try to establish a connection to an electronic unit with address 1, but every 3 seconds. This will ensure that the connection is established within the 15 second time limit after powering up the unit.
Leave all other options unchanged.
| **
8| Power up the electronic unit
9**| The first time the unit is connected, TOOL4COOL® needs to obtain the
parameter file from the unit before a connection is shown by the red arrow.
Allow a few minutes for this task to complete.
You also can read the current status by selecting the network and then select the tab Unit Status.
| ****
10| Look under Error/Message
In this example, no errors or messages appear and the unit is working properly.
11| If the parameter file was already loaded into TOOL4COOL®, a connection should be visible in less than 10 seconds.
A red arrow is added before the network name to indicate that a unit is ready.
| ****
Click the red arrow to open the menu of the electronic unit.
Secop accepts no responsibility for possible errors in catalogs, brochures, and other printed material. Secop reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary to specifications already agreed. All trademarks in this material are the property of the respective companies. Second and the Secop logotype are trademarks of Secop GmbH. All rights reserved. www.secop.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>