Elexant 4010i
Installation Instructions
DESCRIPTION
The nVent RAYCHEM Elexant 4010i is a compact, full-featured, touchscreen- based, single-point heat-tracing controller. It provides control and monitoring of Electric Heat Tracing (EHT) circuits for both freeze protection and process temperature maintenance. This controller can monitor and alarm on high and low temperature, high and low current, ground-fault levels, voltage, and supports a host of additional features to offer the utmost in control and monitoring of EHT.
TOOLS REQUIRED
• 3 mm head flat blade screwdriver for IO terminal
• 5 mm head flat blade screwdriver for power terminals
APPROVALS
Hazardous Locations (SSR Variants)
Class I, Division 2, Group A, B, C, D T4 Type 4X
Class I, Zone 2, AEx nA nC [ia Ga] IIC T4 Gc
Ex ec nC [ia Ga] IIC T4 Gc
IP64 (FW) IP66 (SW)
DEMKO 18 ATEX 2091 X
UL21UKEX2316X
II 3 (1)G Ex ec nC [ia Ga] IIC T4 Gc
IP64 (FW) IP66 (SW)
IECEx UL 18 .0098X
Non-Hazardous Locations (EMR & SSR Variants)
Enclosure Type 4X
IP64 (FW) IP66 (SW)
I.S Temperature Sensor Inputs (Optional) Associated Apparatus Entity Parameters
Um = 305VAC
Uo = 5.4V
Io = 0.083A
Ca = 65uF
La = 2mH
VARIANTS (NOT ALL VARIANTS ARE AVAILABLE IN ALL REGIONS)
Type | Description |
---|---|
4010i-EMR-FW | Elegant 4010i controller in an 8 in x 10 in FRP enclosure with |
window and 2-pole 32A EMR. Controls a single circuit with a 2-pole
electromechanical relay. (Approved for non-hazardous locations only)
4010i-SSR-FW| Elegant 4010i controller in an 8 in x 10 in FRP enclosure with
window and 2-pole 32A 277V SSR. Controls a single circuit with a 2-pole solid-
state relay. (Approved for Class I, Div. 2/Zone 2 locations)
4010i-EMR-SW| Elegant 4010i controller in an 8 in x 10 in a stainless steel
enclosure with window and 2-pole 32A EMR. Controls a single circuit w ith a
2-pole electromechanical relay. (Approved for non-hazardous locations only)
4010i-SSR-SW| Elegant 4010i controller in an 8 in x 10 in a stainless steel
enclosure with window and 2-pole 32A 277V SSR. Controls a single circuit with
a 2-pole solid-state relay. (Approved for Class I, Div. 2 /Zone 2 locations)
4010i-EMR-IS-FW| Elegant 4010i controller in an 8 in x 10 in FRP enclosure
with window and 2-pole 32A EMR. Controls a single circuit with a 2-pole
electromechanical relay. Includes intrinsically safe barriers on RTD inputs.
(Approved for non-hazardous locations only. RTDs may be placed in Class I,
Div.2/Zone 2 , Div.1/Zone 1 locations)
4010i-SSR-IS-FW| Elegant 4010i controller in an 8 in x 10 in FRP enclosure
with window and 2-pole 32A 277V SSR. Controls a single circuit with a 2-pole
solid state relay. Includes intrinsically safe barriers on RTD inputs.
(Approved for Class I,
Div. 2/Zone 2 locations, RTDs may be placed in Class I, Div. 2/Zone 2, Div. 1/Zone 1 location)
4010i-EMR-IS-SW| Elegant 4010i controller in an 8 in x 10 in a stainless steel
enclosure with window and 2-pole 32A EMR. Controls a single circuit with a
2-pole electromechanical relay. Includes intrinsically safe barriers on RTD
inputs. (Approved for non-hazardous locations only. RTDs may be placed in
Class I, Div. 2/Zone 2 , Div. 1/Zone 1 locations)
4010i-SSR-IS-SW| Elegant 4010i controller in an 8 in x 10 in a stainless steel
enclosure with window and 2-pole 32A 277V SSR. Controls a single circuit with
a 2-pole solid-state relay. Includes intrinsically safe barriers on RTD
inputs. (Approved for Class I, Div. 2 /Zone 2 locations, RTDs may be placed in
Class I, Div. 2/Zone 2, Div.1/Zone 1 locations)
4010i-Mod| Elegant 4010i Module (replacement)
4010i-Mod-IS| Elegant 4010i Module with IS Barrier (replacement)
WARNING:
This component is an electrical device that must be installed correctly to
ensure proper operation and to prevent shock or fire.
2 | nVent.com/RAYCHEM
GENERAL
Supply voltage | 100Vac to 277Vac, +/–10%, 50-60Hz |
---|---|
Internal power consumption | < 24W |
Electromagnetic Compatibility | IEC 61326-1:2012 / EN 61326-1:2013 |
ENVIRONMENTAL
Protection| Type 4X, IP64 (FRP enclosure)
Type 4X, IP66 (stainless steel enclosure)
---|---
Materials| Fiber-Reinforced Plastic (FRP) or stainless steel (SS304)
Ambient operating temperature| –40°C to 60°C (–40°F to 140°F)
Ambient storage temperature| –55°C to 85°C (–67°F to 185°F)
Relative humidity| 0% to 90%, noncondensing
Environment| PD2, CAT III
Max altitude| 2,000 m (6,562 ft)
CONTROL
Relay Type| Double-pole, mechanical (EMR versions)
Double-pole, solid-state (SSR versions)
---|---
Voltage, maximum| 277Vac nominal, 50/60Hz
Current, maximum| 32A @ 40°C, de-rated to 24A @ 50°C and further de-rated to
16A @ 60°C (EMR) 32A @ 40°C, de-rated to 24A @ 50°C and further de-rated to
16A @ 60°C (SSR)
TEMPERATURE SENSOR INPUTS
Quantity| Three temperature inputs each of which can be individually set to
one of the types below.
---|---
Types|
---|---
100Ω platinum RTD| 3-wire, α=0.00385 ohms/ohm/°C Can be extended with a
3-conductor shielded cable of 20Ω maximum per conductor
100Ω nickel-iron RTD| 2-wire, α=0.00599 ohms/ohm/°C Can be extended with a
2-conductor shielded cable of 20Ω maximum per conductor
100Ω nickel RTD| 2-wire, α=0.00618 ohms/ohm/°C Can be extended with a
2-conductor shielded cable of 20Ω maximum per conductor
Thermocouple| Requires an external 4-20mA converter
4-20mA current loop, ±0.05mA, 24Vdc loop power provided in the device,
external loop power can also be used
Intrinsic Safety Barriers included on RTD Inputs when using IS models.
RTD Intrinsic Safety Associated Apparatus Entity Parameters
Uo (Maximum Output Voltage): 5.4V | La (Maximum External Inductance): 2mH |
---|---|
Io (Maximum Output Current): 0.083A | Ca (Maximum External Capacitance): 65uF |
Po (Maximum Output Power): 0.449W |
DIGITAL INPUTS
Quantity| Two multi-purpose inputs for connection to external dry (voltage
free) contact or DC voltage
---|---
Rating| 100 Ω max loop resistance or 5-24Vdc @ 1 mA maximum
OUTPUTS
Alarm Relay | Form-C dry contact: | 100Vac to 277Vac, 3A, 50/60Hz |
---|---|---|
Auxiliary Output | 24Vdc, max load of 250 mA @ 40°C, de-rated to 165 mA @ 60°C |
CONNECTION TERMINALS
Power Supply Input | Screw terminals, 24 – 5 AWG (0.2 – 16.8 mm 2 ) |
---|---|
Heating Cable output | Screw terminals, 24 – 5 AWG (0.2 – 16.8 mm |
2 )Three box lugs, 14 – 2 AWG (2.0 – 33.6 mm 2 )
Torque Range for Screw Terminals| 1.2 – 1.5 Nm
Sensor / Other terminals| Cage clamp terminals, 28 – 12 AWG (0.08 – 3.3 mm 2 )
Minimum Conductor Temp. Rating| 80°C
MOUNTING
FRP enclosure with EMR| Surface mounting with four holes on 6.0 in x 10.9 in
(152 mm x 278 mm) centers Hole diameter: 0.3 in (8 mm)
---|---
FRP enclosure with SSR| Surface mounting with four holes on 5.6 in x 11.0 in
(143 mm x 279 mm) centers Hole diameter: 0.3 in (8 mm)
Stainless steel enclosure with EMR| Surface mounting with four holes on 6.0 in
x 11.0 in (152 mm x 279 mm) centers Hole diameter: 0.3 in (8 mm)
Stainless steel enclosure with SSR| Surface mounting with four holes on 5.6 in
x 11.0 in (143 mm x 279 mm) centers Hole diameter: 0.3 in (8 mm)
CONNECTIONS AND INDICATORS
A. TB1 Wiring
Terminals | Function |
---|---|
1 | TS1 (White) |
2 | TS1 (Red) |
3 | TS1 (Red) |
4 | TS2 (White) |
5 | TS2 (Red) |
6 | TS2 (Red) |
7 | TS3 (White) |
8 | TS3 (Red) |
9 | TS3 (Red) |
10 | No Connect |
11 | No Connect |
12 | No Connect |
B. TB2 Wiring
Terminals | Function |
---|---|
1 | TC3+ |
2 | TC2+ |
3 | TC1+ |
4 | TC3– |
5 | TC2– |
6 | TC1– |
7 | – No Connect |
8 | SSR– |
9 | SSR+ |
10 | DIGITAL INPUT COM |
11 | DIGITAL INPUT 1 |
12 | DIGITAL INPUT 2 |
13 | RS485 IN+ |
14 | RS485 IN– |
15 | RS485 COM |
16 | RS485 OUT+ |
17 | RS485 OUT– |
18 | RS485 COM |
C. TB1 Wiring
Terminals | Function |
---|---|
1 | 24V+ OUT |
2 **** | – No Connect |
3 **** | Output Relay |
4 | 24V COM |
5 | External Jumper Required |
6 | External Jumper Required |
7 **** | Alarm_NC |
8 **** | Alarm _COM |
9 **** | Alarm_NO |
D. TB4 Wiring
Terminals | Function |
---|---|
1 **** | END |
2 **** | POWER IN (L1) |
3 **** | POWER IN (L2/N) |
4 **** | LOADOUT (L1) |
5 **** | LOADOUT (L2/N) |
WARNING: Shock Hazard.
Disconnect from live voltage prior to accessing terminals
E. Status LEDs
Status:| Indicates the status of Elexant 4010i
module
---|---
Off| No power
Green| Normal operation, no internal faults
Red| Device Reset
Flash R/G| Unlocked/Calibrated
Output| Shows status of switched output
---|---
COMM
Flash Green | Receive Active |
---|---|
Flash Red | Transmit Active |
Alarm
Red | Illuminates when an alarm is present |
---|
F. USB Connector
G. Ethernet Connection![nVent RAYCHEM Elexant 4010i Heat Trace Controller
- Shock](https://manuals.plus/wp-content/uploads/2022/03/nVent-RAYCHEM- Elexant-4010i-Heat-Trace-Controller-Shock-550x326.png)
MOUNTING THE ELEXANT 4010i CONTROLLER
- SSR version should ideally be mounted to channel strut to maximize heat sink ventilation.
- EMR version can be mounted against a flat surface using the attached mounting feet.
- Secure the enclosure using the upper and lower mounting slots in the heat sink or the mounting feet using hex head screws, flat & lock-washers washers or equivalent hardware.
SSR version
SAE ¼” x 2″ long (Grade 2, 5, 8 : Torque to 4 ft-lb, 7 ft-lb, 9ft-lb
respectively)
Metric 6 mm x 50 mm (Grade 4.6, 8.8 : Torque to 6-Nm 12-Nm respectively)
EMR version
SAE ¼” x ¾” long
Metric 6 mm x 20 mm
[inches] mm
INPUT POWER
The input power connection is made at the screw terminals on TB-4.
Refer to the Connections section on page 3 for terminal block details.
The incoming ground connection should be terminated on the field terminal
block located on the mounting plate.
LOAD CONNECTIONS
Connections made to the load using screw terminals on TB4.
All variants use the same output connection.
Refer to the Connections section on page 3 for terminal block details.
Load ground terminations are to be made on the field terminal block located on
the mounting plate.
3-WIRE RTD CONNECTIONS
Terminate RTD field wires to terminal block TB1.
Refer to the Connections section on page 3 for terminal block details.
Terminate cable shields on the field terminal block located on the mounting
plate.
2-WIRE RTD CONNECTIONS
Terminate RTD field wires to terminal block TB1.
Refer to the Connections section on page 3 for terminal block details.
Terminate cable shields on the field terminal block located on the mounting
plate.
4-20 MA CONNECTIONS
Wiring for 4-20 mA connections are made directly to the terminal block TB2.
Refer to the CONNECTIONS section on page 3 for terminal block details.
Terminate cable shields on the field terminal block located on the mounting
plate.
ALARM RELAY
The multi-purpose alarm relay is energized in the normal state (No Alarms) and
is configured as Fail-Safe.
The alarm relay connections provide a Form-C dry contact, rated at 277 V max
(3 A).
Refer to the CONNECTIONS section on page 3 for terminal block details.
RS-485 IN
Wiring for RS-485 communications must be made directly to the terminal block
TB2.
No shield wires should be terminated on the terminals of TB2.
Refer to the Connections section on page 3 for terminal block details.
Terminate cable shields on the field terminal block located on the mounting
plate.
For best performance, an additional third signal ground wire is connected between COM and the signal ground of the upstream device. This wiring method will reduce noise-induced through ground potential differences.
RS-485 OUT
Wiring for RS-485 communications must be made directly to the terminal block
TB2.
No shield wires should be terminated on the terminals of TB2.
Refer to the Connections section on page 3 for terminal block details.
Terminate cable shields on the field terminal block located on the mounting
plate.
TB2
RS-485 OUT
To next device or install a 120-ohm termination resistor
Note: Install a 120-ohm termination resistor as shown if this is the last
device in the communications bus
ETHERNET
An Ethernet connection is made via the RJ45 connector using a CAT 5E cable, terminated with an RJ45 connector.
DIGITAL INPUTS
Digital Inputs| Multi-purpose input for connection to external dry
(voltage free) contact or DC voltage.
---|---
Rating| 100 Ω max loop resistance or 5-24 Vdc @ 1 mA maximum
Refer to the CONNECTIONS section for terminal block details.
AUX 24V OUTPUT
This 24VDC output may be used to power peripheral equipment if required. The
connection is made using TB3.
Refer to the CONNECTIONS section on page 3 for terminal block details.
USB CONNECTOR
The USB connector on the front of the unit can be used to import and export User setting configurations for ease of programming units and uploading of new firmware.
INTRINSIC SAFETY RTD CONNECTIONS – IF EQUIPPED
For models that include Intrinsic Safety barriers for the RTD connections, the terminal block TB1 will be blue. Each RTD wiring pair is to be considered a separate circuit.
RTD1 Circuit: TB1-1, TB1-2, TB1-3
RTD2 Circuit: TB1-4, TB1-5, TB1-6
RTD3 Circuit: TB1-7, TB1-8, TB1-9
Associated Apparatus Entity Parameters
Uo (Maximum Output Voltage): 5.4V
Io (Maximum Output Current): 0.083A
Po (Maximum Output Power): 0.449W
La (Maximum External Inductance): 2mH
Ca (Maximum External Capacitance): 65uF
The output current of this associated apparatus is limited by a resistor such
that the output voltage-current plot is a straight line drawn between the
open-circuit voltage and short-circuit current.
Intrinsically Safe RTD Terminal Connection
Specific Conditions of Use
This associated apparatus is intended for connection only to simple apparatus
as defined in:
• Article 504.2 and installed and temperature classified in accordance with
Article 504.10(D) of the National Electrical Code (ANSI/NFPA 70)
• Clause 3.5.5 and installed and temperature classified in accordance with
Clause 16.4 of IEC 60079-14
• Section F3 in Appendix F and installed and temperature classified in
accordance with Section F4.2 in Appendix F of the Canadian Electrical Code,
Part 1 (C22.1)
• Or other local codes, as applicable.
When connecting to simple apparatus, the cable length shall not exceed 3000m
(9842ft).
Associated apparatus must be installed in an enclosure suitable for the
application in accordance with the National
Electrical Code (ANSI/NFPA 70) for installation in the United States, the
Canadian Electrical Code for installations in Canada, or other local codes, as
applicable.
The associated apparatus must be connected to a suitable ground electrode per
the National Electrical Code (ANSI/ NFPA 70), the Canadian Electrical Code or
other local installation codes, as applicable. The resistance of the ground
path must be less than 1 ohm.
Where multiple circuits extend from the same piece of associated apparatus,
they must be installed in separate cables or in one cable having suitable
insulation. Refer to Article 504.30(B) of the National Electrical Code
(ANSI/NFPA 70) and Instrument Society of America Recommended Practice ISA
RP12.06 for installing intrinsically safe equipment.
Intrinsically safe circuits must be wired and separated in accordance with:
-
Article 504.20 of the National Electrical Code (ANSI/NFPA 70)
-
Clause 16.2 of IEC 60079-14
-
Section F4.2 in Appendix F of the Canadian Electrical Code, Part 1 (C22.1)
-
or other local codes, as applicable.
This associated apparatus has not been evaluated for use in combination with another associated apparatus.
Control equipment must not use or generate more than 305 V RMS (Um) or dc with respect to earth. -
The enclosure of the device shall be fitted with a locking mechanism such that it is only accessible with the use of a tool.
-
Provisions shall be made, external to the apparatus, to provide the transient protection device to be set at a level not exceeding 140% of the rated voltage at the input terminals of this apparatus.
-
To maintain an internal pollution degree 2 environments, after opening the enclosure, make sure there is no visible condensation or dust. Power the device and let it heat up for 5 minutes before closing the enclosure door.
-
Only install in areas with a low risk of mechanical impact.
-
4010i-Mod and 4010i-Mod-IS replacement modules must be installed into existing ATEX/UKEx/IECEx Zone 2 certified Elexant 4010i enclosures.
WARNING: Explosion Hazard – Substitution of components may impair
suitability for Class I, Division 2 hazardous and non-hazardous locations
WARNING: Explosion Hazard – Do not disconnect equipment unless power has been
switched off or the area is known to be nonhazardous
WARNING: Explosion Hazard – To prevent the risk of electrostatic discharge,
only clean the equipment enclosure with a damp cloth
The Elegant 4010i contains no user-serviceable parts. Contact your nVent representative for service and a Return Authorization number if required.
North America
nVent
899 Broadway
Redwood City, CA 94063
United States
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com
Europe, Middle East, Africa
nVent
Romeinse straat 14
3001 Leuven
Belgium
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
thermal.info@nVent.com| Asia Pacific
Tel +86.21.5426.2937
Fax +86.21.2412.1688
cn.thermal.info@nVent.com
---|---
Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
thermal.info@nVent.com| Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
thermal.info@nVent.com
©2022 nVent. All nVent marks and logos are owned or licensed by nVent
Services GmbH or its affiliates. All other trademarks
are the property of their respective owners. nVent reserves the right to
change specifications without notice.
RAYCHEM-IM-H59271-Elexant4010i-EN-2202
nVent.com/RAYCHEM
Documents / Resources
|
nVent RAYCHEM Elexant 4010i Heat Trace
Controller
[pdf] Instruction Manual
Elexant 4010i, Heat Trace Controller, Elexant 4010i Heat Trace Controller
---|---
|
nVent RAYCHEM Elexant 4010i Heat Trace
Controller
[pdf] Instruction Manual
4010i-EMR-FW, 4010i-SSR-FW, 4010i-EMR-SW, 4010i-SSR-SW, Elexant 4010i Heat
Trace Controller, Elexant 4010i, Heat Trace Controller, Trace Controller,
Controller
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>