PATLITE NE-24A Signal Beacon Instruction Manual

June 6, 2024
PATLITE

PATLITE NE-24A Signal Beacon

PATLITE-NE-24A-Signal-Beacon-product

Notice to customer

Thank you very much for purchasing our Patlite products.

  • Request the installation and wiring to be pertormed by a professional contractor if construction work is
  • Prior to installation, read this manual thoroughly before using this product to ensure correct
  • In addition, please store this manual for future reference when performing maintenance, repairs or
  • Visit our homepage (patlite.com/) )and download the “Complete Operation Manual : NE-24A” to find out more about the operating method and features .
  • If there are any questions concerning this product, refer to the contact information at the end of this document and contact your nearest PATLITE Sales

This product conforms to EN standards and shows the CE Marking. This product has been tested and found to comply with the limits for a Class A device, pursuant to EMC DIRECTIVE. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This product must not be used in residential areas

Safety precautions

  • To prevent from short-circuits or damage, observe the following:

    • Be sure the power is disconnected before replacement or repair, including the replacement of the fuse.
    • Use this product in a properly maintained condition. (Replace or repair if the globe, case, etc. are damaged.)
  • If installing this product requires construction work, ask a specialist in order to avoid fire, or personal

  • When this product is used for security purposes, it should be inspected daily. In case a malfunction should occur, ii is recommended that you use this product together with other security

  • After installation, do not use this product to climb up onto the equipment wit Failure to comply will result in product damage and/or falling off the machinery.

Caution

  • Be sure to put a fuse in the wiring circuit between the power source and equipmentfor If a fuse is not added, it may result in product and/or equipment failure.
  • Be sure to prevent electrostatic damage due to discharge when working with this product for wiring, exchanging units, setting up parameters, etc. by discharging static electricity on your body, etc.\
  • Do not disassemble or detach during operation
  • Do not push on any internal parts when

Model number configuration

PATLITE-NE-24A-Signal-Beacon-fig1

Part names and outer apperance

PATLITE-NE-24A-Signal-Beacon-fig2

Installlation

  • The following requirements are necessary for proper installation:

    • Install the signal beacons where excessive v bration is not
    • Install the signal beacons on a sturdy
  • Provide a sealant coating around the nuts of the backside of then installation surface.PATLITE-NE-24A-Signal-Beacon-fig3

  • Provide a sealant coating around the wire exit hole, or use a Cable

  • Unlock the globe by holding and rotating it in a ounter-clockwise direction, then lift it up

  • Drill the mounting holes(04.5) from the top on the Peel off the adhesive paper from the waterproof sheet and apply it to the Affix the product to the installation suriace with screws and nuts. (3)

(Installation screws and nuts are not included with this product.)

  • After mounting the case, fit the globe by aligning the positioning  marks and lock it by rotating in a clockwise direction.
  • Installation Dimension s
    • After locking the globe, check that there is no gap between globe and body. Being a gap may cause water intrusion or falling off the globe.
  • When the Cable Gland is used, the hole must be large enough for it to fit through. The recommended Cable Gland size is as follows

Caution

  • Do not apply excessive force when mounting/removing the Failure to comply will result in damage.Use a soft cloth moistened with water to clean the globe or (Do not use thinner, benzine, gasoline or oil.)
      • The waterproof sheet must be used before installation.
  • This product has a 1mm thick waterproof sheet at the bottom of the However, because installation suriace
  • screw size: M16x1.5; screw length: shorter than 11mm; outer diameter: less than 25mm;material: plastic. (Torque: 3N•m)

Wiring

  • Remove the globe by unscrewing it in a counter-clockwise direction.
  • Connect the wires to the screwless terminal block.
  • Attach the globe by screwing it in a clockwise
  • The terminals have no

Screwless Terminal Block wiring method|
---|---
(1) Ami nus driveretc. isusedtoprytheteverslotofthe

(2)  The stripped side of the lead wire is inserted in the slot     · t

Terminal Block open, by pushing straight onto the lever slot                ‘

(3)  The driver is removed to release the_ le ver. (Check to  ake \\ .

sure the lead wire has been locked In place.) \              :tJ, er

• Strp 8.m.m of wire insulation from the wire to insert it in the Terminal Block.

• The minus driver blade should be at about 2mm by 0.5mmms rze

& Caution

·

| • Make sure the power is OFF before wiring. A short circuit may damage internal circ its.

•  Ensure the proper working voltage is used. Improper voltage will damage internal circuits.

•  Do not pull the wire out or push it into the case.

•  Be sure the wiring is done properly. Any mistake in wiring may result in damage.

•  Be sure to put a fuse in the wiring circuit between the power source and equipment for protection. If a fuse is not added, it may result in product and/or equipment failure.

•  Do not apply excessive force to the screwless terminal block during wiring. It will be the cause of the failure.

Notice| Make sure that the wires do not sag internally. There is a risk that the light intensity may be reduced by hitting the LED.

Writting example

Model NE-24A-o
Rated Voltage 24V DC (Non-polar)
Current Consumption (Max.) 26mA
Mounting Direction All Directions

Operat ng Temperature Range

(Relative Hum d ty)

| -30°C – +50°C

(Less than 90%RH, Non-condensation)

Protection Rating| IP 55·1 NEMA TYPE 4X, 13
Mass| 0.06kg
| | Model| NE-24A-o
---|---
Rated Voltage| 24V DC (Non-polar)
Current Consumption (Max.)| 26mA
Mounting Direction| All Directions
Operat ng Temperature Range

(Relative Hum d ty)

| -30°C – +50°C

(Less than 90%RH, Non-condensation)

Protection Rating| IP 55·1 NEMA TYPE 4X, 13
Mass| 0.06kg

1 Condition to sat sfy IP66/67: Only when this product is installed with a Cable Gland on a flat surface.

  • Conformity Standards

    • EMC Directive (EN61000-6-4, EN61000-6-2)
    • UL508, CSA-C22.2 14
  • Conformity requirements for the UL Standard:

  • Maximum surrounding air temperature rating of 50 °CThis product is designed for use on a flat suriace for a Type 1

  • Usea “class 2” power supply specified in the guidelines under UL1310.

  • For use in Pollution Degree

  • Conformity requirements for the CE Marking:

    •   * 

This product conforms to EN standards and shows the CE Marking. This product has been tested and found to comply with the limits for a Class A device, pursuant to EMC DIRECTIVE. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This product must not be used in residential areas.

(Note)

  •  Dimensions and specifications may change without notice due to continual product improvemen t.
  • PATLITE and the PATLITE logo is a trademark, or registered trademark of the PATLITE Corporation of Japan and each country.

(Importer for EU)

PATLITE Europe GmbH Am Soeldnermoos 8, D-85399 Hallbergmoos, Germany

Documents / Resources

| PATLITE NE-24A Signal Beacon [pdf] Instruction Manual
NE-24A Signal Beacon, NE-24A, Signal Beacon
---|---

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals