Low Voltage AIRGUARD® Advantages

Reduced installation costs while improving the overall cable performance in harsh environments!

Strippability – No Knife!? No Saw? No Problem! The ability to strip a cable quickly without damaging the phase conductors is critical in reducing installation costs. The combination of Low Voltage AIRGUARD’S unique design and strategically placed rip cords allows it to be stripped up to three times faster than Metal Clad cables without the worry of nicked or damaged phase conductors. Low Voltage AIRGUARD cables do not require the use of a saw (as in the case of CCW cables) which results in increased personnel safety and reduces the potential for damage to the underlying core.

Chemical Resistance – Industrial plants require cable that will stand up to corrosive chemicals and hydrocarbons. Whether installing in a direct burial application, in tray, or in the air, Low Voltage AIRGUARD’s proprietary polymeric layer provides the best protection in the market for the broadest range of chemicals.

Mechanical Resistance – AIRGUARD is known for its mechanical strength. When Prysmian’s R&D engineers were designing Prysmian’s new Low Voltage AIRGUARD it was imperative that the traditional toughness of the prior medium voltage designs be passed on to the Low Voltage AIRGUARD. In crush and impact testing, it is proven to be significantly stronger than metallic armored cables.

Flame – Not propagating a fire is a critical design parameter of any cable for the industrial market. Low voltage AIRGUARD passes all the industry standard flame tests, including IEEE 1202, FT-4 and IEEE 383 210,000 BTU flame test.

VFD – Low Voltage AIRGUARD VFD cables are designed with three symmetrically placed ground wires and an aluminum or copper sheath to contain the generation of high frequency electromagnetic interference (EMI) imposed on the cable when installed in a circuit containing a Variable Frequency Drive. In the event of catastrophic cable damage, this shield, plus the 3 segmented ground wires, should contain any arcing and effectively conduct system fault current to ground.
Product Range – Low Voltage AIRGUARD is available in 600V Power, Control & Instrumentation, from #16 AWG to 1000 kcmil. Standard stocked items include instrumentation cables, control cables to 37/C, and power cables to 3/C 750 kcmil.

LSOH Option – AIRGUARD is available in Low Smoke Zero Halogen (LS0H) construction. Add “LSOH” to the part number to specify as such.

Low Voltage AIRGUARD® Product Range

Low Voltage AIRGUARD® is available in 600V Power, Control & Instrumentation, from #16 AWG to 1000 kcmil. Standard stocked items include instrumentation cables, control cables to 37/C, and power cables to 3/C 750 kcmil.
Power – Low Voltage | 3/C & 4/C | 600 Volt/1000 Volt | Onshore/Marine Rated


Product Number

| Number and Circuit Conductor Size (AWG)| Nominal Insulation Thickness (mils)| Number & Grounding Conductor Size (AWG)| Nominal Jacket Thickness (mils)| Nominal Overall Cable

O.D. (in)

| Nominal Cable Weight (lbs/ Mft)| Minimum Bending Radius (in)| ****

Ampacity (Amps)

---|---|---|---|---|---|---|---|---
20260580| 3/C #14| 30| 3 – #18| 60| 0.63| 230| 2.5| 25
20260540| 4/C #14| 30| 1 – #14| 60| 0.69| 263| 2.7| 20
20260581| 3/C #12| 30| 3 – #16| 60| 0.67| 281| 2.7| 30
20260542| 4/C #12| 30| 1 – #12| 60| 0.73| 320| 2.9| 24
20260582| 3/C #10| 30| 3 – #14| 60| 0.72| 355| 2.9| 40
20260546| 4/C #10| 30| 1 – #10| 60| 0.79| 408| 3.2| 32
20260583| 3/C #8| 45| 3 – #14| 80| 0.89| 521| 3.6| 55
20260596| 4/C #8| 45| 1 – #10| 80| 0.97| 603| 3.9| 44
20260584| 3/C #6| 45| 3 – #12| 80| 0.96| 675| 3.9| 75
20260597| 4/C #6| 45| 1 – #8| 80| 1.06| 782| 4.4| 60
20260585| 3/C #4| 45| 3 – #12| 80| 1.09| 923| 4.5| 95
20260586| 3/C #2| 45| 3 – #10| 80| 1.22| 1264| 5| 130
20260598| 4/C #2| 45| 1 – #6| 80| 1.31| 1442| 5.3| 104
*20260587| 3/C #1/0| 55| 3 – #10| 80| 1.42| 1836| 5.7| 170

VFD – Low Voltage | 3/C | 600 Volt/1000 Volt | Onshore/Marine Rated


Product Number

| Number and Circuit Conductor Size (AWG/kcmil)| Nominal Insulation Thickness (mils)| Number & Grounding Conductor Size (AWG)| Nominal Jacket Thickness (mils)| Nominal Overall Cable

O.D. (in)

| Nominal Cable Weight (lbs/ Mft)| Minimum Bending Radius (in)| ****

Ampacity (Amps)

---|---|---|---|---|---|---|---|---
20260539| 3/C #14| 30| 3 – #18| 60| 0.63| 247| 3.9| 25
20260541| 3/C #12| 30| 3 – #16| 60| 0.67| 297| 4.2| 30
20260544| 3/C #10| 30| 3 – #14| 60| 0.725| 374| 4.5| 40
20266649| 3/C #8| 45| 3 – #14| 80| 0.89| 542| 5.5| 55
20266650| 3/C #6| 45| 3 – #12| 80| 0.97| 701| 5.9| 75
20260550| 3/C #4| 45| 3 – #12| 80| 1.09| 960| 6.7| 95
20260551| 3/C #2| 45| 3 – #10| 80| 1.23| 1309| 7.5| 130
20267132| 3/C #1/0| 55| 3 – #10| 80| 1.41| 1872| 8.6| 170
20262625| 3/C #2/0| 55| 3 – #10| 80| 1.51| 2273| 9.2| 195
20262626| 3/C #3/0| 55| 3 – #8| 80| 1.62| 2766| 9.9| 225
20262624| 3/C #4/0| 55| 3 – #8| 80| 1.8| 3398| 10.9| 260
20127514| 3/C 250| 65| 3 – #8| 110| 2.02| 3903| 12.3| 290
20172246| 3/C 350| 65| 3 – #7| 110| 2.24| 5220| 13.6| 350
20127513| 3/C 500| 65| 3 – #6| 110| 2.51| 6940| 15.3| 430

PRODUCT NOTES:
‡ Per 2014 NEC TABLE 310.15(B)(16) “Allowable Ampacities of Insulated Conductors Rated up to and including 2000 Volts, 60°C through 90°C (140°F through 194°F), Not More Than Three Current-Carrying Conductors”
*Cables not marked “-HL” (per UL 2225, overall cable diameter must be 1.00 inch or less to be marked “-HL”)

Matching Glands for Low Voltage AIRGUARD

Power – Low Voltage | 3/C & 4/C | 600 Volt/1000 Volt | Onshore/Marine Rated

Cable Product Number| Cable Description| Non-Potted Gland Class 1 Division 2| Putty Sealing Gland Class 1 Division 2
---|---|---|---
20260580| 3/C #14 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20260540| 4/C #14 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20260581| 3/C #12 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20260542| 4/C #12 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20260582| 3/C #10 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20260546| 4/C #10 AWG| 494NE10V| 3/4″ NPT| 424BT04| 1″ NPT
20260583| 3/C #8 AWG| 494NE15V| 1″ NPT| 424BT04| 1″ NPT
20260584| 3/C #6 AWG| 494NE15V| 1″ NPT| 424BT04| 1″ NPT
20260585| 3/C #4 AWG| 494NE21V| 1-1/4″ NPT| 424BT05| 1-1/4″ NPT
20260586| 3/C #2 AWG| 494NE21V| 1-1/4″ NPT| 424BT05| 1-1/4″ NPT
20260587| 3/C #1/0 AWG| 494NE32V| 2″ NPT| 424BT06| 2″ NPT

VFD – Low Voltage | 3/C | 600 Volt/1000 Volt | Onshore/Marine Rated

Cable Product Number| Cable Description| Non-Potted Gland Class 1 Division 2| Putty Sealing Gland Class 1 Division 2
---|---|---|---
20260539| 3/C #14 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20260541| 3/C #12 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20260544| 3/C #10 AWG| 494NE10V| 3/4″ NPT| 424BT03| 3/4″ NPT
20266649| 3/C #8 AWG| 494NE15V| 1″ NPT| 424BT04| 1″ NPT
20266650| 3/C #6 AWG| 494NE15V| 1″ NPT| 424BT04| 1″ NPT
20260550| 3/C #4 AWG| 494NE21V| 1-1/4″ NPT| 424BT05| 1-1/4″ NPT
20260551| 3/C #2 AWG| 494NE21V| 1-1/4″ NPT| 424BT05| 1-1/4″ NPT
20267132| 3/C #1/0 MCM| 494NE32V| 2″ NPT| 424BT06| 2″ NPT
20262625| 3/C #2/0 MCM| 494NE32V| 2″ NPT| 424BT06| 2″ NPT
20262624| 3/C #4/0 KCM| 494NE38V| 2-1/2″ NPT| 424BT07| 2-1/2″ NPT
20127514| 3/C #250 KCM| 494NE38V| 2-1/2″ NPT| 424BT07| 2-1/2″ NPT
20172246| 3/C #350 KCM| 494NE45V| 3″ NPT| 424BT08| 3″ NPT
20127513| 3/C #500 KCM| 494AG09V| 3″ NPT| 424BT09| 3-1/2″ NPT
20147056| 3/C #750 KCM| 494AG09V| 3″ NPT| TBD| TBD