GARO LS4, LS4 Compact Public Charging Installation Guide
- June 8, 2024
- GARO
Table of Contents
- GARO LS4, LS4 Compact Public Charging
- SAFETY INFORMATION
- GENERAL INFORMATION
- INSTALLATION
- NORMAL USE
- TECHNICAL SPECIFICATIONS
- SERVICE INFORMATION
- WARRANTY CONDITIONS
- WARRANTY FORM
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
- 2. The modbus RS-485 communication settings is: Baud 9600, 8bit, 1 stop bit,
GARO LS4, LS4 Compact Public Charging
SAFETY INFORMATION
- The LS4 stations are designed exclusively for charging electric vehicles.
- All installation must be carried out by an authorized installer and comply with local country installation regulations. If any questions, please contact your local electrical authority.
- Refer to local standards and regulations not to exceed charging current limitations.
- To even out the load, it is important to rotate the phases when connecting several of LS4 stations to the same system. Note that 1-phase charging is common in electric vehicles and L1 (left side) and L2 (right side) in the LS4 is used for this purpose.
- Ventilation signal from EV is not supported. This means that test of “State D” is not possible.
- Adapters for charging connectors are not allowed to be used.
- Cord extension sets for charging cable is not allowed to be used.
- Do not use private power generators as a power source for charging.
- Incorrect installation and testing of the LS4 stations could potentially damage either the vehicles battery and/or the LS4 itself.
- Do not operate the LS4 stations in temperatures outside its operating range – see technical specifications.
GENERAL INFORMATION
-
Each LS4 station is pre-programmed from factory and tested according to the specification from customer. There is no need for any programming or setup by installer during installation.
-
Each LS4 station is individually marked with a unique
“M-number” so that the installer can identify each LS4 station. The M-number label is located at upper right hand side corner behind the front door. When contacting GARO support, please have the M-number available. -
LS4 stations that are pre-configurated for backend-solution have the ChargeBoxID (CBID) labeled under the M-number label.
INSTALLATION
-
Mount the LS4 and install the supply cable. See picture 1-4.
Phase-rotation is recommended in order to achieve even load on all phases when several LS4 stations are installed to same mains. For example:
1st LS4: L1, L2, L3
2nd LS4: L3, L1, L2
3rd LS4: L2, L3, L1
And so on….
Note: When DLM is pre-configurated from factory, follow the marked phase order label at incoming terminals. All pre-configured LS4 contains the information about this inside the cabinet
The gasket at the bottom of the LS4 need to tighten properly around the mains cable in order to avoid dirt, dust, bugs etc to enter the LS4. See picture 4.
Note! The touch protection cover need to fix with attached screws to ensure proper earth bonding to the touch protection cover. -
In cases with LS4 stations connected in a grid, install TP cable CAT6 with RJ45 connectors between each LS4 station and the provided ethernet router/switch (located ie. in the LS4 master. Se example of ethernet wiring diagram picture 5, 6.
In cases with LS4 stations connected in a grid, installation of the LS4 stations need to follow the installation order in the attached Master/slave file. See table 1. -
In cases with external energy meter (for DLM function), connect the energy meter communication terminals A- and B+ to LS4 Master station terminals 200 A-) and 201
(B+). The energy-meters modbus adress must be set to2. The modbus RS-485 communication settings is: Baud 9600, 8bit, 1 stop bit,
no parity
-
Turn on the electric power.
-
Test the LS4 station on both sides with a EVSE-tester or an EV. In cases where authorization (by RFID tag or similar) is needed to start charging please contact the backend administrator.
-
Fill in the warranty form completely.
Example of Master/Slave form for LS4 stations connected in a grid
Role | Serialnumber / M-number |
---|---|
Master | M00001 |
Slave 1 | M00002 |
Slave 2 | M00003 |
Slave 3 | M00004 |
Slave 4 | M00005 |
Slave 5 | |
Slave 6 | |
Slave 7 | |
Slave 8 | |
Slave 9 | |
Slave 10 |
NORMAL USE
Connect the charging cable to the EV.
If authorization is activated, please hold a valid RFID-tag against the RFID
reader on the side of the LS4 you want to use or use the operator app to
authorize charging.
Charging will start instant if the EV is ready for charging. See your EV
charging manual.
When finishing charging, follow the EV’s instructions.
After charging: Release the charging cable from your EV and place the charging
cable at designated place.
LED light indication | When | Cause of error |
---|---|---|
Firm | No car connected | Charging station available and ready for charging |
Car connected | State B: Car connected but not yet ready for charging | |
Car connected | State C: Car connected and ready for charging, but charging |
station requires authentication to start charging (Free Charging =
“OFF”).
Blinking (3 blinks)| When car connects| The charging station detects that the
cable is connected, but is yet to detect the car.
Blinking (30 second blink)| Whenever during operation| Charging station have
received command from backend to start charging and is waiting for car to
connect.
Firm| Car connected| Charging is ongoing (state C)
Car connected| Charging is paused (state B)
Blinking| Whenever during operation| Charging station/point is reserved for a
specific user
Firm| Whenever during operation| DC fault monitor may be defect.
Whenever during charging| Residual Circuit Current Breaker (RCCB) triggered.
Whenever during charging| DC fault detected.
Whenever during charging| Circuit breaker (MCB) triggered – Overload / short
circuit
Whenever during charging| Type 2 connector motor locking was released/unlocked
(the cable can be removed)
When connecting car| The socket outlet can not engage locking mechanism to
lock the connector.
When connecting car| Charging cable is damaged.
light on RIGHT side| Whenever during operation| The right side charge
controller have lost connection to left side charge controller.
Firm (3 seconds)| When RFID is presented| RFID card is not valid or not
approved by backend.
Blinking| Whenever during operation| Charging station/point is deactivated.
Blinking| When RFID is presented| Charging station is verifying the RFID in
backend cloud service.
LED light indication| When| Cause of error
---|---|---
NO LIGHT|
Charging station and internal meters are powerless.
| The upstream circuit breaker have been triggered.
4-pole main circuit breaker inside the bottom of charging station
is deactivated.
Charging station is powerless (no LED light), but the internal meters have
power.| 1-pole main circuit breaker inside the bottom of charging station is
deactivated.
The 12V power supply unit is deactivated (Green LED-light [DC OK] on 12V
supply unit is not lit).
Upper PCB is not receiving power (DC 12V).
The 12V power supply unit has power, but the charging controller/controllers
still do not indicate green on LED-light [Ready]. When operating normally, the
LED-light should show blinking green.
NO LIGHT on right side|
Directly after powering up station. Left side has LED-light lit, but not right side. No access to left controller web interface.
| Right controller is not receiving power (green LED-light [Ready] on
controller is not blinking). Left controller is operating normally and [Ready]
is blinking.
The cable (USB–>Micro USB) connecting the two controllers is
damaged or has bad connection.
LED light indication | Measure 1 | Measure 2 |
---|---|---|
Firm | No error | Have you tried everything without success? Contact installer |
or GARO Support (please have M-number available)
Check car settings that can influence charging, i.e gear in parking mode,
doors closed, car locked etc.
Present a valid RFID to the RFID card reader (look for RFID symbol), start
charging via mobile app or contact charging station operator to start charging
remote via backend.
If the charger is supposed to work without RFID/app authentication, contact
the backend operator and ska them to verify that “Free charging” is set to ON.
Blinking (3 blinks)| Connect the charging cable to the vehicle, or verify that
cable is connected correctly. If no success, try a different charging cable if
available.
Blinking (30 second blink)| Connect the charging cable, or verify that cable
is connected correctly.
Firm| No error| Have you tried everything without success? Contact installer
or GARO Support (please have M-number available)
No error
Blinking| No error (contact backend operator if this is not the desired mode)
LED light indication| Measure 1| Measure 2
---|---|---
Firm| If the orange “alarm” LED indicator on the charge controller is firm
lit, then the charge controller needs to be replaced.|
Have you tried everything without success? Contact installer or GARO Support (please have M-number available)
Firm Red light will always generate an alarm to the backend operator.
Reset the RCCB inside the charging station.
Verify that the 8-pole quick connection on the charge controller is properly
connected.
Verify correct grounding and phases in building electrical system
When car is connected: Disconnect charging cable from the charging station,
then the LED indication shall return to GREEN.
Reconect charging cable to start charging. The charging
will restart automatically after 15 minutes if cable is not disconnected.
Reset circuit breaker.
Check internal wiring and components for possible reasons for short circuit.
Verify allowed maximum current in backend charger configuration
(OperatorCurrentLimit).
Check motor locking wiring and connection for damages. Verify that locking
mechanism rod and arm are not stuck.
Verify that the connector is properly inserted into the socket. Light force
may be applied.
Verify that there are no foregin objects inside the socket outlet, hence
blocking the connector.
Verify that the motor locking is properly installed and without visual
damages.
Check charging cable and connectors for damages. Test with another cable if
available.
Verify that CP and PP connection pins and wires are not loose or having bad
connection.
Verify grounding of charging station.
light on RIGHT side| Check the cable (USB to micro-USB) connecting the two
controllers. Replace cable if needed.|
Have you tried everything without success? Contact installer or GARO Support (please have M-number available)
If replacing cable does not solve the issue, the charge controller needs to be
replaced.
Firm (3 seconds )| Verify that the RFID token is approved by backend (contact
backend operator).
| Verify that the RFID token is stored in charger internal memory / whitelist
(requires certified technician)
Blinking| Contact backend operator and ask for remote activation.
Blinking| No error|
LED light indication| Measure 1| Measure 2
---|---|---
NO LIGHT| Reset circuit breaker in upstream switchboard.|
Have you tried everything without success? Contact installer or GARO Support (please have M-number available)
Check mainbreaker, reset it if it is deactivated.
Check mainbreaker (1-pole 10A), reset it if it is deactivated.
Verify that 12V power supply unit is receiving 220V AC power via terminals L &
N.
Disconnect red/black cables from the power supply unit terminals marked “+/-“.
If the power supply unit when red/black cables were disconnected, then it has
deteced an earth fault in one of the DC powered components (controllers, upper
PCB, router/switch etc.) inside the charging station.
If LED-light [DC OK] remains turned off, consider replacing the 12V power
supply unit.
Check red/black cable and connection between DC terminal and upper PCB quick
connection (located on far left side of upper PCB in the charging station).
Verify that the controller has 12 V DC power supplied (4-pole quick connection
on down-side of controller -> terminal 1 & 2 from the left) and that the LED-
light [Ready] is blinking green. If power supply is ok, but no blinking green,
then consider replacing charging controller.
NO LIGHT on right side| Verify that the cable (micro-USB on left controller
and USB-A on right controller) is properly connected and not damaged. Try
replacing with a new cable.| Have you tried everything without success?
Contact installer or GARO Support (please have M-number
available)
LED light indication | Indication / fault code in Web UI | OCPP fault code |
---|---|---|
Firm | IDLE (available) – (A) Vehicle not connected |
IDLE (available) – (B) Vehicle connected not ready
IDLE (available) – (C) Vehicle connected ready
Blinking (3 blinks)| IDLE (available) – (A) Vehicle not connected
Blinking (30 second blink)| AUTHORIZED (available) – (A) Vehicle not connected
Firm| CHARGING (occupied) – (C) Vehicle connected ready|
CHARGING (suspendedEV) – (B) Vehicle connected not ready
Blinking| | Reserved
Firm| RCD triggered| groundFailure
Residual current detected via sensor| groundFailure
MCB of type 2 socket triggered| overCurrentFailure
Actuator unlocked while charging| connectorLockFailure
Plug locking failed| connectorLockFailure
Possible CP and PR wiring issue.| otherError
|
Blinking| UNAVAILABLE (unavailable)| Unavailable
TECHNICAL SPECIFICATIONS
- Product type All LS4 models
- Standards / Directives IEC 61851-1 and IEC 61439-7
- EMC Classification: 2014/30/EU
- Installation method: Ground / Wall
- Installation environment: Indoor / Outdoor
- Location type: Non-restricted Access
- Rated Voltage: 1-phase 230VAC 50Hz / 3-phase 400VAC 50Hz depending on model
- Rated Current (configurable) 63A, 32A 1-phase or 3-phase
- Installation systems: TT, TN and IT* systems
- Charging type: Mode 3
- Charging method AC Charging
- Protection class: IP44
- Mechanical impact resistance: IK10
- Temperature range: -25C – +40C
- Weight: 22,5 – 24,5kg depending on model
- Standard cable length (fixed cable version): Standard 4m
- Rated current withstand 10kA
- Rated short-time withstand current 10kA
- Rated conditional short-circuit current of an assembly 10kA
- Short-circuit protective device type Type C
- Rated impulse withstand voltage 4kV
- Rated insulation voltage 230/400V
- Rated current of each circuit 32A
- Rated diversity factor RDF=1
- Pollution degree: 3
- EMC environmental condition A and B
- RFID Frequency Band 13.56MHz
- RFID output power 250mW
SERVICE INFORMATION
Care and maintenance GARO charging station LS4:
The warranty will only remain valid if service is performed. Service is
performed once a year and must be documented. General authorization EL is
required to perform service, i.e. only a qualified electrical contractor
should perform the service. The service is performed by inspecting the
charging station’s exterior and interior parts, manipulating components and
conducting a functional inspection.
If the charging station is connected to a web portal or otherwise controlled
from an external system via a service provider, the service personnel must
contact the service provider before a scheduled service. This is to be able to
carry out all steps in the service, but also to avoid automatic error reports
being sent from the charging station when service starts that may lead to
other service personnel being called out at great expense. Normally the
instructions for the charging station indicate whether it is connected to a
superior service.
If you have questions about service or a need for service, please contact your
GARO retailer.
FORM FOR ANNUAL SERVICE AND MAINTENENCE
- Plant ID:
- Name:
- Date:
Check point for annual service and maintenence:|
Status/Value| Comment/remark
---|---|---
Visual check outside cabinet| |
LED indication lit| |
Check cables, connectors, connector pins| |
Check sockets| |
Check color, foil and instructions| |
Check external antenna (when installed)| |
Check fastening/fixing to ground/wall| |
Cean LS4 outside surface| |
Check locking mechanism| |
Check both RCCB by pressing “T” button. Check that LED
indication switches to red color for both sides
| |
Function test by GARO test-equipment or similar| |
Check that electrical power is delivered by indications on test
equipment
| |
Check RFID reader (when available). Indication by 2 or 3 flashes from LED:s| |
Check Type 2 socket locking function (Type 2 socket versions)| |
Turn off the electrical power| |
Check gaskets| |
Check torque for mains terminals| |
Check torque for LS4 fixing screws towards ground/wall| |
Check torque for connectors on contactors, relays, energymeters and DC-PSU| |
Check connectors on CCU module| |
Measure the earthing resistans (Ohm) on EV sockets/cables with a multimeter| |
Clean inside when necessary| |
Turn on the electrical power| |
Check charging function on both sides| |
WARRANTY CONDITIONS
EU Countries (except Sweden)
- The product benefits from manufacturer´s warranty. The applicable warranty period must be stated in purchase documents from your supplier.
- The product must be installed by a certified installer / contractor.
- Proper installation, storage and operation conditions must be obtained.
- Warranties apply only to products installed in their original installation location.
- Installation, use, care, and maintenance must be normal and in accordance with instructions.
- Warranty requires a dated, fully filled in Warranty form by an certified installer/contractor. If the original installation date cannot be verified, then the warranty period begins ninety (90) days from the date of product manufacture (as indicated by the model and serial number).
- Warranty does not cover damage occurred by incorrect use of equipment, use of any non-original spare parts, lack of maintenance or faults caused by disassembly of the product or unauthorized persons intervention,
- Warranty does not cover software or update thereof.
- Warranty does not cover aesthetic deficiencies caused by negligent manipulation or accidents (breaks or damage to the carcass).
- Warranty does not cover damage caused by external overvoltage from either grid or car/charging object.
- Warranty does not cover damage caused by force major like for example but not limited to: floods, winds, fires, lightning, accidents, sabotage, military conflicts, terrorism, volcanos, earthquakes or corrosive environments.
WARRANTY FORM
LS4 Model: M no:
Electrical installation data
Group fuse (A):
Supply cable dimension:
Function Test
Testbox / EV (model)
Date:
Sign Installer:
Company Name:
Owner / Customer Name:
Installation adress:
3pcs LS4 connected with TP CAT6 cable to router/switch
5pcs LS4 connected with TP CAT6 cable to router/switch
Example of DLM meter installation
- Q1 = Main breaker
- F3 = Fuse Charge Controller and Powersupply
- P1 = Energymeter Left Outlet
- P2 = Energymeter Right Outlet
- FB1 = RCCB Left Outlet
- FB2 = RCCB Right Outlet
- FC1 = Fuse Left Outlet
- FC2 = Fuse Right Outlet
- QA1 = Contactor Left Outlet
- QA2 = Contactor Right Outlet
- XN1 = N Neutral terminal
- XPE1 = PE Terminal Protection Earth
- T1 = Powersupply DC
- CC1 = Charge Controller (Master)
- CC2 = Charge Controller (Slave)
- RFID1 = Left Receiver
- RFID2 = Right Recevier
- TC = Led light Topcard
- EB1 = Heater Cold Options
- XD1 = Left charging connector
- XD2 = Right charging connector
- K3 = Contactor for Heater Cold Options