BRISTAN OPTS3650ELC Exposed Shower Valve with Lever Handle Installation Guide
- June 5, 2024
- BRISTAN
Table of Contents
OPTS3650ELC Exposed Shower Valve with Lever Handle
Installation Guide
IMPORTANT
The installer, when you have read these instructions please ensure you leave
them with the user.
Please keep this booklet for future reference.
General Information
This product has been tested to the TMV2 scheme which complies with the BS EN
12871999 (LP) and BS 11111999 (HP) thermostatic mixing valve standards.
It also satisfies the requirements of the water supply (water fittings)
regulations 1999 and current bylaws
BS 6700 recommends the temperature of stored water should never exceed 65°C. A
stored water temperature of 60°C is considered sufficient to meet all normal
requirements and will minimize the build-up of limescale in hard water areas.
Important: Nominally equal (balanced) inlet supply pressures are
recommended for optimum performance with mixer showers.
This shower valve should be installed in compliance with the Water Regulations
If in doubt, contact a registered plumber or your Local Water Authority or the
Secretary of The Institute of Plumbing, address as follows;
The Institute of Plumbing,
64 Station Lane,
Hornchurch,
Essex, RM12 6NB
Tel 01708 472791
Guide to designations
Hp | High Pressure |
---|---|
LP | Low Pressure |
S | Shower |
Recommended Usage
Domestic| √| Light Commercial| √
Light Commercial| √| Health Care| √
Conditions of Use for Type 2 (Thermostatic Mixer) valves
| High Pressure| Low Pressure
---|---|---
Maximum Static Pressure (Bar)| 10| 10
Flow Pressure. Hot & Cold (Bar)| 0.5 to 5| 0.1 to 1
Hot Supply Temperature CC)| 55 to 65| 55 to 65
Cold Supply Temperature CC)| Equal to or Less
than 25| Equal to or Less
than 25
Note: Valves operating outside these conditions cannot be guaranteed by the
Scheme to operate as Type 2 valves.
The valves designation of use, LP if tested against BS EN 1287, HP if tested
against BS EN 1111, and HP & LPif tested against both standards.
If a water supply is fed by gravity
then the supply pressure should be verified to ensure the conditions of use
are appropriate for the valve.
The minimum supply pressure for LP Tub application is 0.2 bar.
Recommended outlet tern operates
The BuldCert TMV scheme recommends the following set the maximum mixed water
outlet temperatures for use in all premises
44°C Bath fill but see notes below
41Cfor Showers.
41°C for Washbasins
38°C for Bidets
The mixed water temperatures must never exceed 46°C.
The maximum mixed water temperature can be 2°C above the recommended maximum
set outlet temperatures.
Note: 46°C is the maximum mixed water temperature from the bath tap. The
maximum temperature takes account of the allowable temperature tolerances
inherent in thermostatic mixing valves and temperature losses in metal baths.
Warning: It is not a safe bathing temperature for adults or children.
The British Burns Association recommends 37 to 375C as a comfortable bathing
temperature for children. In premises covered by the Care Standards Act 2000,
the maximum mixed water outlet temperature is 43C
The thermostatic mixing valve (TMV) will be installed in such a position that
maintenance of the TM/ and its valves and the commissioning and testing of the
TM/ can be undertaken.
The fitting of isolation valves is required as close as is practical to the
water supply inlets of the thermostatic mixing valve.
The fitting of strainers is recommended as close as is practicable to the
water supply inlets of the thermostatic mixing valve.
Commissioning
Commissioning notes for Thermostatic Mixing Valves
The first step in commissioning a thermostatic mixing valve is to check the
following:
- The designation of the thermostatic mixing valve matches the application
- The supply pressures are within the valves operating range
- The supply temperatures are within the valves operating range.
- Isolating valves (and strainers preferred) are provided
If all these conditions are met, proceed to set the temperature as stipulated
in the Maintenance section.
The mixed water temperature at the terminal fitting must never exceed
46°C.
lt is a requirement that all TMV2 approved valves shall be verified against the original set temperature results once a year When commissioning/testing is due the following performance checks shall be carried out
- Measure the mixed water temperature at the outlet.
- Carry out the cold water supply isolation test by isolating the l4) cold water supply to the TMV, wait for five seconds, if water is still flowing check that the temperature is below 46°C
If there is no significant change to the set outlet temperature (+/-2 C or
less change from the original settings) and the fail-safe shut off is
functioning, then the valve is working correctly and no further service work
is required
Notes: If there is a residual flow during the commissioning or the annual
verification (cold water supply isolation test), then this is acceptable
providing the temperature of the water seeping from the valve is no more than
2°C above the designated maximum mixed water outlet temperature setting of the
valve.
Temperature readings should be taken at the normal flow rate after allowing
for the system to stabilize. The sensing part of the thermometer probe must be
fully submerged in the water that is to be tested.
Any TMM that has been adjusted or serviced must be re-commissioned and re-
tested in accordance with the instructions in the Maintenance section.
The installation of thermostatic mixing valves must comply with the
requirements of the Water Supply Water Fittings) Regulations 1999.
In-Service Testing
Purpose
The purpose of in-service tests is to regularly monitor and record the
performance of the thermostatic mixing valve. Deterioration in performance can
indicate the need for service work on the valve and/or water supplies.
Procedure
Using the same measuring equipment or equipment to the same specification as
used in the commissioning section, adjust the temperature of the mixed water
In accordance with the manufactures instructions and the requirement of the
application, Carry out the following sequence.
a) Record the temperature of the hot and cold water supplies.
b) Record the temperature of the mixed water at the largest draw-off flow
rate.
c) Record the temperature of the mixed water at a smaller draw-off flow rate.
which shall be measured.
If the mixed water temperature has changed significantly from the previous
test results (eg >1K), record the change and before re-adjusting, the mixed
water temperature checks
a) That any in-line or integral strainers are clean.
b) Any in-line or integral check valves or other anti-back siphonage devices
are in good working order
c) Any floating valves are fully open. With an acceptable mixed water
temperature, complete the following procedure:
a) Record the temperature of the hot and cold water supplies
b) Record the temperature of the mixed water at the largest draw-off flow
rate.
c) Record the temperature of the mixed water at a smaller draw-off flow rate,
which shall be measured
d) Isolate the cold water supply to the mixing valve and monitor the mixed
water temperature
e) Record the maximum temperature achieved as a result of (d) and the final
stabilized temperature
f) Record the equipment, thermometer, etc used for the measurements. f at step
(e) the final mixed water temperature is greater than 41C and/or the maximum
temperature exceeds the corresponding value from the previous results by more
than about 2K. the need for service work is indicated
Note: In-service tests should be carried out with a frequency, which
identifies a need for service work before an unsafe water temperature can
result In the absence of any other instruction or guidance, the procedure
described in Annex F of D 08 may be used.
Annex F of D 08 (informative)
Frequency of In-service tests
General
In the absence of any other instruction or guidance on the means of
determining the appropriate frequency of in-service testing the following
procedure may be used:
a) 6to 8 weeks after commissioning carry out the tests in ‘In-Service Tests’
b) 12 to 15 weeks after commissioning carry out the tests in detail in ‘In-
Service Tests’ Depending on the results of the above tests, several
possibilities exist
a) If no significant changes (e.g. <1K) in mixed water temperatures are
recorded between commissioning and 6 to 8 week testing, or between
commissioning and 12 to 15 weeks of testing the next in-service test can be
deferred to 24 to 28 weeks after commissioning
b) If small changes (e.g 1to 2K) in mixed water temperatures are recorded in
only one of these periods, necessitating adjustment of the mixed water
temperature, then the next in-service test can be deferred to 24 to 28 weeks
after commissioning.
c) If small changes (e.g. 1to 2K) in mixed water temperatures are recorded in
both these periods, necessitating adjustment of the mixed water temperature.
then the next in-service test should be carried out at 18 to 21 weeks after
commissioning.
d) If significant changes (eg > 2K) in mixed water temperatures are recorded
in either of these periods, necessitating service work, then the next in-
service test should be carried out at 18 to 21 weeks after commissioning.
Bristan Group Ltd.
Birch Coppice Business Park
Dordon
Tamworth
Staffordshire
B781SG
Web: wwwbrstan.com
Email: enquire@bristan.com
A Masco Company
Follow us on…
In the interests of continuous product improvement. Bristan reserves the right to alter product specifications without notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>