solarV LS1024B Solar Charge Controller User Manual
- June 5, 2024
- solarV
Table of Contents
solarV LS1024B Solar Charge Controller
Thank you for selecting the Land Star B series solar charge controller.
Please read this manual carefully before using the product and pay attention
to the safety information.
Overview
Landstar B series is a PWM common positive solar charge controller that adopts the most advanced digital technique. The multiple load control modes enable it can be widely used on solar home system, traffic signal, solar street light, solar garden lamp, etc. The features are listed below:
Features
Adopt high quality components of ST,IR and Infineon, make sure product lifespan
- Terminals have UL and VOE certification, the product is more safer and more reliable 100% input and output in the environment temperature range
- 3-Stage intelligent PWM charging, Bulk, Boost/Equalize, Float
- Support 3 charging options: Sealed, Gel , Flooded and User
- RS485 communication interface and Modbus communication protocol
- Battery temperature compensation function
- Energy statistics function
- Multiple load control modes
- Extensive Electronic protection
Product Features
1 | Remote Temperature(RTS)Port* | 6 | Mounting Hole |
---|---|---|---|
2 | PV Terminals | 7 | Button |
3 | Battery Terminals | 8 | Load status indicator |
4 | Load Terminals | 9 | Battery status indicator |
5 | RS485 communication Port | 10 | Charge status indicator |
Wiring
NOTE: The LS-B series is a positive ground controller. Any positive
connection of solar, load or battery can be earth grounded as required.
NOTE:While wiring the controller do not close the circuit breaker or fuse
and make sure that the leads of “+” and ” -” poles are connected correctly.
NOTE: A fuse which current is 1.25 to 2 times the rated current of the
controller must be installed on the battery side with a distance from the
battery not greater than 150 mm.
NOTE: If an inverter is to be connected to the system, connect the
inverter directly to the battery, not to the load side of the controller
Indicator and button
Indicator
Button
- The load is turned ON/OFF via the button when the working mode is Manual Control.
- Clear the faults for the load overload and short circuit
SETTING
-
USB to RS485 converter cable: CC- RS485-RS485-150U
PC software website: www.epever.com(PC Software for the Solar Charge Controller) -
USB to RS485 converter cable: CC- RS485-RS485-150U OTG cable: OTG-12CM
Phone APP software website (support Andriod system only) www.epever.com (Andriod APP for the Solar Charge Controller) -
USB to RS485 converter cable:CC-RS485-RS485-200U-MT)
)Battery types
Battery Voltage Control Parameters
Below parameters are in 12V system at 25 °C, please double the values in 24V
system
Battery type | Sealed | Gel | Flooded | User |
---|---|---|---|---|
Over Voltage Disconnect Voltage | 16.0V | 16.0V | 16.0V | 9~ 17V |
Charging Limit Voltage | 15.0V | 15.0V | 15.0V | 9~ 17V |
Over Voltage Reconnect Voltage | 15.0V | 15.0V | 15.0V | 9~17V |
Equalize Charging Voltage | 14.BV | — | 14.BV | 9~ 17V |
Boost Charging Voltage | 14.4V | 14.2V | 14.BV | 9~ 17V |
Float Charging Voltage | 13.BV | 13.BV | 13.BV | 9~17V |
Boost Reconnect Charging Voltage | 13.2V | 13.2V | 13.2V | 9~ 17V |
Low Voltage Reconnect Voltage | 12.BV | 12.6V | 12.BV | 9~ 17V |
Under Voltage Warning Reconnect Voltage |
12.2V
|
12.2V
|
12.2V
|
9~17V
Under Voltage Warning Voltage| 12.0V| 12.0V| 12.0V| 9~ 17V
Low Voltage Disconnect Voltage| 11.1V| 11.1V| 11.1V| 9~17V
Discharging Limit Voltage| 10.BV| 10.6V| 10.BV| 9~ 17V
Equalize Duration| 120min| —| 120 min| 0~ 180 min
Boost Duration| 120min| 120min| 120 min| 10~ 1B0 mir
NOTE:
- When the battery type is sealed, gel, flooded, the adjusting range of equalize duration is 0 to180min and boost duration is 10 to180min.
- The following rules must be observed when modifying the parameters value in user battery type (factory default value is the same as sealed type):
A. Over Voltage Disconnect Voltage > Charging Limit Voltage” Equalize Charging
Voltage ” Boost Charging Voltage ” Float Charging Voltage > Boost Reconnect Charging Voltage.
B. Over Voltage Disconnect Voltage > Over Voltage Reconnect Voltage.
C. Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ” Discharging Limit Voltage.
D. Under Voltage Warning Reconnect Voltage > Under Voltage Warning VoltageDischarging Limit Voltage.
E. Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage.
CAUTION: Please refer to user guide or contact with the sales for the detail of setting operation.
Load Set Mode
-
Manual Control(default ON)
The load is turned ON/OFF via the button. -
Light ON/OFF
Time Control
Control the load on/off time through setting real-time clock
Protections
-
PV Over Current
When the charging power of the PV array exceeds its rated power, it will be charged at the rated power. -
PV Short Circuit
When not in PV charging state, the controller will not be damaged in case of a short-circuiting in the PV array. -
PV Reverse Polarity
When the polarity of the PV array is reversed, the controller may not be damaged and can continue to operate normally after the polarity is corrected. -
Battery Reverse Polarity
Fully protected against battery reverse polarity; no damage to the controller will result.
Correct the miswire to resume normal operation. -
Battery Over Voltage
When the battery voltage reaches the over voltage disconnect voltage, it will automatically stop battery charging to prevent battery damage caused by over- charging. -
Battery Over Discharge
When the battery voltage reaches the low voltage disconnect voltage, it will automatically stop battery discharging to prevent battery damage caused by over-discharging. (Any controller connected loads will be disconnected. Loads directly connected to the battery will not be affected and may continue to discharge the battery.) -
Battery Overheating
The controller can detect the battery temperature through an external temperature sensor. The controller stops working when its temperature exceeds 65 °C and begins working when its temperature is below 55 °C. -
Load Overload
When the load is overloading (The overload current is” 1.05 times the rated load current), the controller will automatically cut off the output. If the load reconnects automatically five times (delay of 5s, 10s, 15s, 20s, 25s), it needs to be cleared by pressing the Load button restarting the controller, switching from Night to Day (nighttime> 3 hours). -
Controller Overheating
The controller is able to detect the temperature inside the battery through an optional remote sensor. The controller stops working when its temperature exceeds 85 °C and begins to working when its temperature is below 75 °C. -
TVS High Voltage Transients
The internal circuitry of the controller is designed with Transient Voltage Suppressors (TVS) which can only protect against high-voltage surge pulses with less energy. If the controller is to be used in an area with frequent lightning strikes, it is recommended to install an external surge arrester.
Troubleshooting
Faults| Possible reasons
PY array disconnection
Battery voltage is
lower than BV
| Troubleshooting
---|---|---
Charging LED|
indicator off during|
daytime when| Confirm that PV and battery wire
sunshine falls on| connections are correct and tight
PV modules|
orooerlv|
Wire connection is| Please check the voltage of battery. At
correct, the| least BV voltage to activate the
controller is not| controller.
workino.|
| Check if battery voltage is higher than
OVD(over voltage disconnect voltage),
green slowly| Battery over voltage
fiashino| | and disconnect the PY.
Battery indicator red on solid| Battery over discharged| When the battery
voltage is restored to
or above LVR(low voltage reconnect voltaoe), the load will recover
| | The controller will automatically turn the
Battery indicator| Battery| system off. But while the temperature
red slowly flashing| Overheating| decline to be below 55 ‘C, the controller
| | will resume.
| | When heat sink of controller exceeds
Charge, Load and| Controller| 85°C, the controller will automatically cut
Battery(orange)indi| Overheating| input and output circuit. When the
cater fiashing| | temperature below 75°C ,the controller
| | will resume to work.
| | (DPlease reduce the number of electric
Load indicator red slowly fiashing|
Load Overload
| equipments.
® Restart the controller.
@wait for one night-day cycle (night
| | time>3 hours).
| | (DCheck carefully loads connection, clear
Load indicator red fast flashing|
Load Short Circuit
| the fault.
® Restart the controller.
@wait for one night-day cycle (night
| | time>3 hours).
Technical Specifications
Item | LS1024B | LS2024B | LS3024B |
---|---|---|---|
System nominal voltage | 12/24VDC Auto | ||
Battery Types | Sealed/Gel/Flooded/User | ||
Rated charge current | 10A | 20A | 30A |
Rated discharge current | 10A | 20A | 30A |
Working Voltage range of controller | 8-32V |
Max . PV open circuit
voltaae
| 50V
Self-consumption| S8.4mA/12V;S7 .8mA/24V
Charge circuit voltage droo| S0.28V
Discharge circuit voltage
drop
| S0.20V
Temperature compensate coefficient| -3mV/°C/ 2V (default)
Working environment
temoerature
| -35 “C – +50 ‘C
Relative humidity| S95% (N.C.)
Enclosure| IP30
Grounding| Common Positive
Dimension
| 138.6×69.3
x37mm
| 159.6×81.4
x47.8mm
| 200.6×101.3
x57mm
Mounting dimension| 126mm| 147x50mm| 190x70mm
Mounting hole size| <1>4.3| <1>4.3| <1>4.5
Terminal| 4mm’| 10mm’| 10mm’
Weight| 0.13kg| 0.3kg| 0.5kg
Disclaimer
-
This warranty does not apply under the following conditions:
-
Damage from improper use or use in an unsuitable environment.
-
PV or load current, voltage or power exceeding the rated value of controller.
The controller is working temperature exceed the limit working environment temperature. -
User disassembly or attempted repair the controller without permission.
-
The controller is damaged due to natural elements such as lighting.
-
The controller is damaged during transportation and shipment.