LUXPOWERTEK 7.6K Hybrid Inverter User Manual

June 5, 2024
LUXPOWERTEK

7.6K Hybrid Inverter

Version:EN-UM-1.0-01
USER MANUAL
HYBRID INVERTER 7.6K/8K/9K/10K/11K/12K

CONTENTS

About This Manual

01

4 Operation Guide

21

1 Safety

01

4.1

Operation Mode

21

1.1 Safety Instruction
2 Brief Introduction
2.1 System Solution
3 Installation

01

4.2 LCD settings

21

03

4.2.1 Information Searching

21

4.2.2 Settings Guidance

23

03

4.3 Monitor System

27

04

4.5 Parallel System Setup Guidance

27

3.1 Packaging List & Storing 3.2 Select Location 3.3 Install the Inverter 3.4 Connection
3.4.1 Connection Overview
3.4.2 PV Connection 3.4.3 Battery Connection

04

5 Start-up and shut down the inverter

30

04

5.1

Start up the inverter

30

06

5.2 Shut down the inverter

30

07

07

6 Troubleshooting & Maintenance

30

08

6.1

Troubleshooting

30

09

6.1.1 Introduction to LED Displays

30

3.4.4 Communication Connection

10

6.1.2 Maintenance

30

3.4.5 Grid/UPS Connection

12

6.1.3 Troubleshooting Based On LCD Displays

31

3.4.5.1 240V Single-phase Connection

13

7 Fan replace

34

3.4.5.2 240V/208V Split phase Connection

13

3.4.6 Work with Gen set

14

3.4.7 European model wiring diagram

15

3.4.8 Meter and CT Connection

17

3.4.8.1 Connect the Meter

18

3.4.8.2 Connect the CT

19

3.4.8.3 DRMs Connection

19

3.4.8.4 Balancing Resistor Configuration – SW1

20

3.4.8.5 Wireless Communication Module Connection

20

1. Safety
1.1 Safety Instruction
General Safety Instructions
The inverter has been designed and tested strictly according to international safety regulations. Read all safety instructions carefully prior to any work and observe them at all times when working on or with the inverter. The operator must be qualified personnel and the installation must be capable with relevant national or international standards or regulations. Incorrect operation or work may cause:
– injury or death to the operator or a third party; or – damage to the inverter and other properties belonging to the operator or a third party.
Important Safety Notifications
There are many safety issues need to be carefully notified before, during and after the installation, and also in future operation and maintenance, following is important safety notifications to operator, owner and user of this product in appropriate usage.
Dangers of High Voltages and Large Current
Beware of high PV voltage. Please turn-off the DC switch of PV Panel output before and during the installation to avoid electric shock. Beware of high grid voltage. Please turn-off the AC switch of grid connection before and during the installation to avoid electric shock. Beware of large current of the battery output. Please turn-off the battery module before and during the installation to avoid electric shock. Do not open the inverter when it’s working to avoid electric shock and damages from live voltage and current from the system. Do not operate the inverter when it’s working, only the LCD and buttons can be touched in limited cases by qualified personnel, other parts of the inverter can be touched when the inverter is under a safe state(e.g. fully shut-down). Do not connect or disconnect any connections (PV, battery, grid, communication etc.) of the inverter when it’s working. Make sure the inverter is well grounding, an operator should make sure itself is good protected by reasonable and professional insulation measurements (e.g. personal protective equipment (PPE)). Inspect relevant existed wiring on-site of the installation is under good condition before installation, operation or maintenance. Inspect the connections are good between inverter and PV, battery and grid during installation to prevent damages or injuries caused by bad connections.
01

Avoid misoperation and Inappropriate Usage
All the work of this product (system design, installation, operation, setting and configuration, maintenance etc. must be carried out by qualified personnel as required. All connections must be in accordance with local and national regulations and standards. Only when permitted by utility grid, the inverter and system can interconnected with the utility grid. All the warning table or nameplate on the inverter must be clearly visible and must not be removed, covered or pasted. The installation should choose a right position and location as required in this manual with consideration to safety of users’ in future operation. Please keep the children away from touching or misoperation the inverter and relevant system. Beware of burning hurt, the inverter and some parts of the system could be hot when working, please do not touch the inverter surface or most of the parts when they are working. During inverter working states, only the LCD and buttons could be touched.
Please carefully read this manual before any work carried out on this inverter, after the installation, please keep this manual carefully stored and easy to access at any time. The qualified personnel should have had training in the installation and commissioning of the electrical system as well as dealing with hazards, also they should have the knowledge of the manual and other related documents. As the installer or operator they are required to be familiar with local regulations and directives.
02

2. Brief Introduction
2.1 System Solution
This product and relevant system is suitable for following system applications (system diagram): A. Solar and energy storage hybrid system B. Energy storage system without solar

3. Installation
3.1 Packaging List & Storing
Packaging List
When the packaging is unpacked, the inner components should be the same as described in below packaging list.

User Manual X1

Communication Port Cover X4

Wi-Fi Module X1

CT X2

RJ45 Terminal X4

C. On-grid solar system without battery (hybrid ready)

D. Off-grid and back-up applications

Reserved Battery&UPS
Interfaces
E. Hybrid system with zero export funtion F. Parallel system for Hybrid

Router

Viewer

Grid

Hybrid Inverter X1

Expansion Screw and Tube X4

Cross Head Screw X6

OT Terminal X2

Battery communication cable

RSD Meter X1

3.2 Select Location
Suggestions and Requirements
a) The wall for mounting should be strong enough to bear the weight of inverter . b) To ensure the heat dispassion efficiency and inverter lifespan, do not install the inverter enclosed.

400mm

400mm

400mm

400mm

03

04

3.3 Install the Inverter
The inverter is wall-mounted installed , steps shows below:
Step1. Use the cardboard as the template to mark the position of the 4 holes, then drill 8 mm holes and make sure the depth of the holes is deeper than 50mm.

c) The structure of the wall where inverter mounted should not be flammable, or make sure the inverter is not surrounded by flammable or corrosion materials and is away from the gas.
d) Never install the inverter exposed to directly sunshine, rain and snow. Please refer to below figure and select a well shaded place or install a shell to protect the inverter from directly sunshine, rain and snow etc.

Step2. Install the expansion tubes into the holes and tight them, then use the expansion screws (packaged together with the expansion tubes) to install and fix the wall-mounting bracket on the wall.

75

90

05

Step3. Install the inverter on the wall-mounting bracket and lock the inverter using the security screws.

90

90

06

3.4 Connection
3.4.1 Connection Overview
The system connection diagram is as below( for US version):
L2 L1
L1 L2 L1 L2 L1 L2

UPS Load

Please prepare the breakers before connetion, breakers selection recommendation for both DC and AC

Hybrid

12K

9K/10K/11K

7.6K/8K

DC Breaker selection(6 poles)

600V/40A

600V/40A

600V/40A

DC Breaker selection(2 poles)
AC Breaker selection(2 poles) AC Breaker with RCD
UPS Breaker selection(2 poles)

100V/300A
63A/230Vac Type AC,>0.3A
63A/240Vac

100V/300A
50A/230Vac Type AC,>0.3A
50A/230Vac

100V/300A
40A/230Vac Type AC,>0.3A
40A/230Vac

Connection Terminals and Interfaces Overview

DC Switch

PV INPUT

BAT INPUT

WIFI COM

AC OUTPUT

3.4.2 PV Connection
The PV connection of hybrid inverter is the same to traditional on-grid solar inverter (string inverter).

– Before connection the PV, please use the multi-meter to measure the PV array voltage to verify if PV array is working normally, if not, please fix the PV array to normally working states before connection
– When your PV panel ambient temperature could possibly be lower than 0, then please check the PV array voltage up ceiling and if you are not sure please ask your system or panel provider for further assistance. As when temperature is extremely low the PV panel voltage will increase by a certain percentage.
– Turn off or disconnect the PV switch(DC witch). Then keep this switch always open during the connection

Cable Requirement: Cross-section
4 – 6 mm2

Cable Diameter
2.5-4mm

Minimum Voltage
600V

Assemble the PV connector
a) Strip 6~8mm insulation from the cable end. b) Assemble the cable ends to crimp contacts. c) Secure the pipe fitting to the enclosure using the nut provided with the pipe. d) Route the PV input power cable through the conduit and then fitting of the pipe. e) Connect the PV input power cable to the terminal block. Connect positive pole(+) of connection
cable to positive pole(+) of PV input terminal block, connect negative pole(-) of connection cable to negative pole(-)of PV input terminal block. f) Secure the fitting to the conduit. g) Checks that the cables are connected correctly and securely. Then take appropriate measures to ensure that the pipe conduit and fittings are secured reliably, and seal the cable holes.

07

08

Step 1: Strip 6-8mm insulation from the cable end and Assemble the cable ends to crimp contacts.

Step 2: Route the battery power cable through the conduit and then fitting of the pope.

Please pass the positive lead of PV through the AFCI module, and pass the negative lead of PV through the RSD communication magnetic ring first

Step 3: Secure the pipe fitting to the enclosure using the nut provided with the pipe.
Polarity reverse will damage the inverter! Install a DC isolator between battery and inverter can avoid potential damages caused by electric arc.

3.4.3 Battery Connection
Cable Requirement:

Model

Cross-section Cable Diameter

5-8K 9-10K

50-60 mm2 60-85 mm2

15-25mm 15-25mm

11-12K

85-100 mm2

15-25mm

Minimum Voltage
600V 600V 600V

3.4.4 Communication Connection
Interface Overview Battery Communication Interface DRM Interface
CT and Meter Communication Interface
Parallel cable communication Interface

09

Temperature Sensor
Serial communication Mains model CAN Matching resistance Dry node
10

Battery Communication Connection
If the battery type is lithium-ion or ternary battery which need communication between the inverter and battery management system (BMS), the communication connection must be installed.
RJ45 Terminal Configuration of Battery Communication

Pin 1 2 3 4 5 6 7 8

Pin
1 2 3 4 5 6 7 8

Function Description
BAT 485 B BAT 485 A BAT CAN L BAT CAN H
NC BAT NTC
GND-S

Make the RJ45 terminal based on above introduction of each Pin definition, you could either make RS485 connector or CAN connector based on the best support connection way of your battery packs. For Lead acid battery temperature sensor, please connect signal to Pin6 and Pin8, the other pins are not connected.(External temperature sensor is needed, the sensor is 15K thermistor for typical, or consult Luxpowertek)

3.4.5 US Model Grid/UPS Connection

Cable Requirement:

Cross-section
8 – 10 mm2

Cable Diameter
5-10mm

Minimum Voltage
600V

a) Strip 8~10mm insulation from the cable end. b) Assemble the cable ends to crimp contacts. c) Secure the pipe fitting to the enclosure using the nut provided with the pipe. d) Secure the fitting to the conduit. e) Checks that the cables are connected correctly and securely, then take appropriate measures
to ensure that the pipe conduit and fittings are secured reliably, and seal the cable holes.

For Li-ion battery 1. If work with lithium battery , please make sure it is compatible with the units. Now inverter is compatible with Pylontech, Dyness, Aoboet, Weco, Murata. Please contact your distributor for updated compatible list. 2. After battery power cable and communication cable connection, users need to choose battery brand by LCD. 3.Please remember to connect Master battery to inverter if you have battery group, and set the Master battery for the battery group.(Please contact battery manufacture for battery group setup). For Lead-acid battery 1. The lead acid battery temperature sensor cable is optional, if required, please request the temperature sensor cable from your supplier. 2. There are three stages for lead acid battery charge . For charge part, please set CV voltage and floating voltage. For discharge part, please set the discharge cut off voltage for on grid and off grid
11

Grid Type Configuration – SW2 By configuring the DIP switch the inverter could comply with different grid system. Sw2 Safety Standard Configuration Switch Overview
Note: The DIP switch is composed of five-digit binary number PINs. Each PIN has two status, when set upward to”ON”, its value turns to”1″, when set downward, its value turns to “0”. Voltage standards Configuration Guidance
12

Grid type

L

N

Voltage

Sw2 Configuration

240V single phase

L1 N L2

240V split phase

L2 N

208V split phase L1

3.4.5.1 240V Single-phase Connection 240V Grid Connection Mains L is connected to terminal L1, mains N is connected to terminal L2, and the machine output N is connected with air switch and mains N; the schematic reference is as shown in the picture below
EPS Connection Connect the power L line of the important load or equipment to the UPS port output L1, the N line to the UPS port output L2, and the PE line to the inverter and other equipment. Schematic reference is as follows.

N L
PE

LN

PE

EPS Connection for Split phase For 240V or 208V loads or equipment, please connect the power supply L1 and L2 to the UPS output L1 and L2 respectively, and the PE wire to the inverter and the equipment used. For 120V loads or equipment, please connect the L line of its power supply to L1 or L2 of the UPS output, and connect the N line of the equipment power supply to the N of the UPS output. Schematic reference is as follows.
N L2 L1
PE

L

N

PE

120V

120V

240V

3.4.6 Work with Gen set
This hybrid inverter can work with generator. Users can connect the generator output to inverter GEN terminal. Please purchase an external control box to remote turn on/off the generator(which support dry contact function). The generator will be automatically started when battery cannot discharge or there is charge request from battery. When battery can discharge and SOC is higher than AC charge SOC setting, generator will be stoped. Battery will get charged when the generator is turned on, and the generator is bypassed to take all loads in UPS terminal.

240V

3.4.5.2 240V/208V Split phase Connection 240V/208V Split phase Grid Connection
The split-phase system applicable to this series of Hybrid products includes 240V mains power with a phase angle difference of 180 degrees and 208V mains power with a phase angle difference of 120 degrees. For split-phase systems, please connect L1 to the inverter Grid port L1, L2 to the inverter Grid port L2, and N to the inverter port N. Schematic reference is as follows.

13

14

N L2 L1 PE

240V

120V

3.4.7 European Model Wiring Diagram

Grid type

Voltage

Sw2 Configuration

L

N

230V single phase

Single-phase wiring

LN

LN

LN

N

EPS OUTPUT GEN

GRID

L

PE

LN

PE

15

LN

LN

LN

EPS OUTPUT

GEN

GRID

N

L

PE

LN

PE

LN
EPS OUTPUT

LN
GEN

LN
GRID

N L PE

16

3.4.8 Meter and CT Connection
In a completed installed on-grid energy storage system, the CT or Meter should be installed. The CT or Meter should installed in the right position as below picture

RJ45 Terminal Configuration of Meter/CT Communication

Pin 1 2 3 4 5 6 7 8

Pin Function Description

The communication port for communicate with meter or CT clamp is as below:

L1 L2 L1 L2

/

5/6

Reserved

CTN

CTP

UPS Load
L1 L2 L1 L2

3.4.8.1 Connect the Meter The functional interfaces overview of the meter is shown in below figure. Now Luxpower only support EASTRON SDM120 and SDM630- Modbus Modbus model meter.
Step1. Connect the meter in the LN line as below

AC Grid Side

Inverter Side

Step2. Connect the communication cable between inverter and meter, and plug the RJ45 to communication port

UPS Load
17

1

2

Step3. Check the connection. When the meter displays -xxxxW as below figure shows, the hybrid inverter is feeding power to the grid.and when it displays xxxxW, it means the house load is using energy from grid.

18

3.4.8.2 Connect the CT For the CT clamp connection, we need to put the CT clamp in the L cable and the arrow printed on the CT should point to inverter. Now Luxpower support two ratio 1000:1 and 3000:1 CT clamps . For default, the ratio is 1000:1, if you install another CT clamp, please set it in the monitor system or LCD. For the CT clamp cable, users can use the normal net cable to extend the length if the original length is not enough. The longest distance can be 100m.

TO Grid

TO PCS

3.4.8.4 Balancing Resistor Configuration – SW1 By configuring the SW1 balancing resistor configuration switch, you could configure the balancing resistors of parallel CAN communication. This Function is used for multiple inverter paralleling operation. Please turn on the DIP in the first and last inverter in the inverter loop. For more info, please check the parallel connection part.
3.4.8.5 Wireless Communication Module Connection

3.4.8.3 DRMs Connection
DRMs is short for `inverter demand response modes’, and it is a mandatary requirements for inverters in Australia
RJ45 Terminal Configuration of DRM

Pin 1 2 3 4 5 6 7 8

Pin Function Description

1

DRM15

2

DRM26

3

DRM37

4

DRM48

5

RefGen

6

DRM0

7

+12V

8

GND-S

DRM Communication Interface Overview

19

In addition to WIFI, there are 4G and GPRS versions

The Wireless Communication Interface Details

Pin 1 & 2 3 & 4

Function Description

20

4. Operation Guide

4.1 Operation Mode
Users can have different settings to satisfy their demands, the working modes is as below:

Mode
Self usage (Default mode)
Charge priority
Force time
Micro Grid mode(Genset)

Explanation
The priority of the PV energy will be Load >battery> grid, which means the energy generated by PV will be mainly used by local loads, and rest will be stored in the battery, excessive power will be feed back into the grid.
The priority of the PV energy will be battery >Load >grid, which means the energy generated by PV will be used to charge the battery first, and then used by local loads, excessive power will be feed back into the grid.
User can set the charging and discharging time and priority of energy use under Force Time Use mode. This is also used to flexibly make use of your system by customized settings by the users.
When used in pure off grid application, users may connect the Gen set output to grid input , when battery SOC is low. Inverter will use generator to take the load and charge the battery.

Related Settings Application Notes

Effective when charge priority and force time charge/discharge are disable

increase the self consumption rate and reduce the energy bil significantly

Charge Priority and related time, SOC

When the load shedding always happens, users need to charge battery first

Force charge/discharge enable and disable, and related time SOC

This mode suits for situation where the price difference of energy is big under Time of Use (To U)

Micro grid enable /disable

Area where is no grid and there is utility

4.2 LCD settings
4.2.1 Information Searching
Refer to below flow chart which shows the information option interfaces and interconnection. Operator can search target information by following below directions.
a) Enter into Display Menu Interface Touching the screen to light it up when it goes into sleeping mode. We can read the current information of the equipment, including its current status, voltage, power etc.

PV Energy
Today: Total: Discharge Energy
Today: Total: Import
Today: Total: Consumption Today: Total:

21

b) Search History Information Touching the label of the present menu to enter into the equipment’s interface, we can read the real-time information of PV, Battery Grid, UPS etc.

PV Data Battery Data Grid Data UPS Data Other

Vpv1 Vpv2 Vpv3 Epv1_day Epv2_day Epv3_day

Ppv1 Ppv2 Ppv3 Epv1_all Epv2_all Epv3_all

c) Search fault/alarm Information
Touching the warning label under the present menu to enter into the fault information interface, we can read the current and historical fault & warning information.

Fault record Alarm record

Error code 1 2 3 4 5 6 7 8 9 10

Error time

Error state

22

d) Search setting information Touching the setting label under the present menu to enter into the equipment’s setting interface, we can read the equipment’s current setting information.

Application setting PV Input

Charge setting

Vpv Start (V)

Discharge setting Reset and Debug Installer setting Device information

Meter or CT Meter Type UPS Voltage UPS Frequency

Set

Set

Com Addr

Set

Set

CT Ratio

Set

Set

4.2.2 Settings Guidance
All setting items can be input or selected by the way of touching, just like the way of operating a smart phone.
a) Common Setting
Common setting is the regular setting item. We can set the information of time, communication terminal, start voltage of PV, as well as choosing the ratio of CT, type of meter, type of battery, batter brand & capacity etc.
1. Notice that the setting range of the RS485 communication address is from 000 to 255, and it’s set to be 001 by default when manufactured. 2. In order to the correct type of meter, we should confirm if the meter we are going to install is a single phase meter or a three phase meter while setting the meter mode.
3. Setting the CT mode: In order to set a correct CT proportion, we need to inspect the marked proportion on the CT. We don’t need to set the type of CT. 4. Selecting the battery mode: we don’t need to set the battery type and battery capacity. 5. Selecting the lead-acid battery mode: we need to select the lead-acid battery capacity according to its real capacity, and don’t need to choose the battery brand. 6. Selecting the Lithium mode: we need to choose it based on the real brand, and ignore the setting of lead-acid battery capacity.

Application setting PV Input

Charge setting

Vpv Start (V)

Discharge setting Reset and Debug Installer setting Device information

Meter or CT Meter Type UPS Voltage UPS Frequency

Set

Set

Com Addr

Set

Set

CT Ratio

Set

Set

b) Application Setting Enter into Application Setting interface:
1. UPS function can continually power the essential house loads in the case of blackout. We should set the output voltage, Frequency and to enable seamlessly switch function.
2. The anti-backflow function can prevent energy feed into the grid. Since in some countries, users can not feed energy into grid, so they are able to disable energy export function in the LCD, or set power percent which can feed into grid.
3. Setting the max. input power to prevent input power overload.
4. When connect the generator to inverter AC terminal, users need to enable mirco grid function so the inverter will use generator to charge battery and will not export any power by AC terminal. 5. Switching on or off the equipment to turn it into the standby mode from the quitting of normal status.
Noted: In the case of battery being turned off, we have to make it sure that the capacity of the UPS port loads should smaller than the capacity of PV output, and the enable PV grid off function will be normally working.

Application setting Power backup

Charge setting

Seamless switch

Discharge setting Reset and Debug Installer setting

Feed-in Grid Feed-in Power(%) Max. Input power(W) Normal / Standby

Device information

Set PV Grid Off
Set Fast zero export
Set Micro-grid

23

24

c) Charge Setting Setting the battery charging parameters:
1. Setting the charging power & current. 2. Setting the AC charging, we have three non-overlapping period of time to be set, and the charging power, cut off soc etc. 3. Setting the equalization voltage, equalization peroid, equalization time etc.

Application setting Charge setting Discharge setting Reset and Debug Installer setting

Charge power(%) Charge current(A)

AC Charge

Time Range 1

:

Time Range 2

:

Time Range 3

:

Device information

Equalization Voltage(V) Equalization peroid(day)

Set Charge last Set

Set

:

AC Charge power(%)

:

AC Charge SOC(%)

:

Set Equalization time(hour)

d) Discharge Settings
Discharge Setting is used to set the relevant parameters of battery discharge, including:
1. Setting the output power, output current, and stop the discharging SOC both in case of having grid and without grid. 2. Setting the force discharging function, we need to set the discharging time periods (three non -overlapping period of time can be set),output power, discharge cut-off SOC etc. 3. Setting the cut-off voltage, start derate voltage, discharge temp low()discharge temp high()etc.

Application setting Charge setting Discharge setting Reset and Debug Installer setting Device information

Discharge power(%) On-grid EOD(%) Discharge start power(W)

Forced diacharge

Time Range 1

:

Time Range 2

:

Time Range 3

:

Cut-off Voltage(V)

Set Discharge current(A)

Set

Off-grid EOD (%)

Set

Set

Set

:

Forced discharge power(%)

:

Forced discharge SOC(%)

:

Set Start derate Voltage (V)

Set

e) Reset and Debug In case of receiving fault notification from the machine, we can restart the inverter to eliminate the report of abnormal event.

Application setting Restart inverter Reset

Charge setting Discharge setting Reset and Debug Installer setting Device information

FAQ: Why do not discharge? Why do not charge? Why is there no output power from AC terminal? Why is there no output from EPS terminal?

f) Device information
We can set the standby time after the inverter has been powered on, and we can check the equipment’s factory default information.

Application setting Charge setting Discharge setting Reset and Debug

Standby time (s) Model Serial number Firmware version

Installer setting

Build version

Device information Time

Set

:

:

Set yyyy-mm-dd hr:mi:se

25

26

Parallel line 3 Parallel line 3

4.3 Monitor System
Users can use wifi donlge/WLAN dongle/4G dongle(Avaiblable from 2021 March for some countries) to monitor the energy storage system, The monitor website is: server.luxpowertek.com The APP is also available in the google play and apple APP store(Scan two code bar to download the APP). Please download the introduction of guidance by website: https://www.luxpowertek.com/download/ Document Reference:
1. Wifi Quick Guidance Quick guidance for setting password for wifi module, the paper is also available in the wifi box 2.Monitor system setup for Distributors and Monitor system setup for endusers Monitor system registration ,wifi password setting, and wifi local monitor and setting 3.Lux_Monitor_UI_Introduction Introduction of monitor interface 4. WebsiteSettingGuidance Introduction of website settings for hybrid inverter

4.4 Parallel system setup guidance
Please note that the parallel model is different from standard model, if users need to connect the UPS together, they need to buy parallel model from distributors. For parallel system setup, Step1. Cable connection :the system connection for single phase paralleling is as below: the system connection for threephase paralleling is as below:

Inverter 1

PV

AC Input

Parallel line 1

CAN 1 CAN 2 AC Output
BAT

DC

Inverter 2

PV

AC Input

CAN 1

Parallel line 2

CAN 2 AC Output BAT

DC

Inverter 3

PV

AC Input

CAN 1 CAN 2 AC Output
BAT DC

L

AC

Grid Bus-Bar(L,N)

N

PE

L

AC

N

PE

UPS Bus-Bar(L,N)

L

AC

N

PE

L

AC

N

PE

AC Input Grid Bus-Bar(L,N)

PE

Grid

L

AC

N

PE

L

AC

N

PE

AC Output Grid Bus-Bar(L,N)
PE

EPS Load

27

Inverter 1

PV

AC Input

Parallel line 1

CAN 1 CAN 2 AC Output
BAT

DC

Inverter 2

PV

AC Input

Parallel line 2

CAN 1 CAN 2

AC Output

BAT

DC

Inverter 3

PV

AC Input

CAN 1 CAN 2

AC Output

BAT

DC

L

AC

N PE

L

AC

N

PE

UPS Bus-Bar(L,N)

L

AC

N

PE

L

AC

N PE

L

AC

N

PE

L

AC

N PE

Phase L1 Grid or Generater
Phase L1 UPS
Phase L2 Grid or Generater
Phase L2 UPS
Phase L3 Grid or Generater
Phase L3 UPS

Please put the CAN communication PIN to on status for the first and the end inverter

Parallel line(n to 1)

The max parallel quantity is 10, so 2<n<10

4

Parallel line1

4

Parallel line2

4 Parallel line(n-1 to n) 4

No.1

11

1 0

3

No.2

00

1 0

3

No.n-1

00

1 0

3

No.n

11

1 0

3

28

Step2. Setup the monitor for the system,add all datalogs in one station. Users can login the visit the monitor system, Configuration->station->Plant Management->add datalog to add the datalogs.
Step3. Setup Master and Slave for Parallel system. There should be only one master in the system. Set one inverter as master and the others as slave
Step4. Enable share battery for the system if the system share one battery bank, otherwise disable the shared battery function Step5. Set the system as a parallel group in the monitor system
Please contact your distributor for more detailed guidance for paralleling system
29

5. Start-up and shut down the inverter
5.1 Start up the inverter
Step1. Turn on the battery breaker , then turn on “UPS Output” switch and check if the inverter works in battery back-up mode.
Step2. Make sure the PV voltage of the strings are higher than 120V ,and check if the inverter works in PV charge or PV charge back-up mode.
Step3. Make sure step1and 2 above work properly before turning the grid power or generator, and check if the inverter can go to bypass mode and on-grid mode normally.
5.2 Shut down the inverter
Danger: Do not disconnect the battery , PV and AC input power under load. If there is emergency issue , and you have to shut down the inverter ,please follow the steps as below, Step1. Cut off AC input breaker of inverter side
Step2. Cut off the breaker of load side Step3. Cut off PV breaker and then cut off the battery ,and waiting for the LCD goes off Step4. Turn off “Power” switch on the inverter if needed.

6. Troubleshooting & Maintenance

6.1 Troubleshooting

6.1.1 Introduction to LED Displays

LED

Display

Description

Suggestion

Green LED
Yellow LED Red LED

Long light Flashing Long light Long light

Working normally

Firmware upgrading

Wait till upgrading complete

Warning, inverter working Need troubleshooting

Fault, inverter stop work

Need troubleshooting

6.1.2 Maintenance
Every segment of the system need to be check monthly/quarterly/yearly according to the detailed requirements of each segment.
Inverter Maintenance a) Check the inverter every 6 months or 1 year to verify if there are damages on cables, accessories, terminals and the inverter itself.
b) Check the inverter every 6 months to verify if the operating parameter is normal and there is no abnormal heating or noise from the inverter.
c) Check the inverter every 6 months to confirm there is nothing covers the inverter heat sink, if there is, shut-down the inverter and clear the heat sink.

30

Battery Maintenance As per different types battery, from the original manufacturer’s requirements on maintenance, when you carried out these works on batteries, please make sure to fully shut-down the inverter for safety consideration.

6.1.3 Troubleshooting Based On LCD Displays
Once there are any warning or fault occurred, the LED and LCD will displays information to remind the operator, the LCD will display relevant error code and short description.

Code
E000 E001 E002

Description
Battery communication fault 1
Battery over temperature
Low battery

LCD Display Troubleshooting

E000 E001 E002

Restart inverter, if the error still exist, please contact us

E003 E004
E005 E006 E007

Meter communication fault Battery cannot be charged
and discharged Auto test fault
RSVD LCD communication fault

E008

Parallel CAN fault

E009

The fan does not turn

E010

Multiple master

E011

Parallel AC inconsistent

E012

UPS short circuit

E013

UPS power reversed

E014

BUS short circuit

E015 E016

Parallel phase abnormal Relay fault

E017

Internal communication fault 2

31

E003 E004 E005 E006 E007 E008
E009
E010
E011
E012 E013 E014 E015 E016 E017

Restart inverter, if the error still exist, please contact us
Check the parallel CAN cables between inverters, and balance resistor is in the right place Restart inverter, if the error still exist, please contact us 1.Check if the parallel system have two masters at less. 2.Only allow one master, reconfigure the others to slaves.
Check the AC connection between parallel inverters 1.Check UPS L,N connection 2.Disconnect the UPS connector, if the error still exist, contact us. Restart the inverter, if the error still exist, contact us.
Contact us
Check parallel connection and setting
Restart the inverter, if the error still exist, please contact us.

E018 E019

Internal communication fault 3
Bus voltage high

E018 E019

E020 E021 E023 E024 E025 E026 E027
E028 E029 E031

UPS connection fault
PV voltage high
Neutral fault
Both PV short circuit
Temperature over range
Internal fault Sampling inconsistent
between main and slave CPU Sync signal lost in parallel system Sync trigger signal lost in parallel system Internal communication
fault 4

UPS CN Fault PV voltage high
Neutral fault E024
NTC Open E026 E027
E028 E029 E031

W000

Communication failure with battery

Bat Com Fault

W001 W002
W003

AFCI communication fault AFCI High
Communication failure with meter

W001 W002
Meter Com Fault

W004

Battery failure

Battery failure

W005 W007 W008 W009 W010 W011

Auto Test failure LCD communication Fault
Software mismatch Fan Stuck
Same para address Slave overflow

Auto Test failure W007 W008 W009 W010 W011

Restart the inverter, if the error still exist, please contact us. Wait for the inverter automatically restart complete, if this error repeats for several times, please contact us
Check UPS and AC connections Check PV input connection and If PV voltageis in range Check neutral connection Disconnect both PV connection, if the error still exist, contact us Check NTC Connection
Restart inverter, if the error still exist, please contact us
Check CAN cable connection
Restart inverter, if the error still exist, please contact us Check if communication cable is right and have choose the right battery brand, if the warning still exist, contact us Check PV input connection and restart inverter, if the error still exist, please contact us Fix communication cable, if the warning still exist, contact us Restart battery, if the warning still exist, please contact us and battery manufactyre Restart inverter, if the warning still exist, please contact us
Restart inverter, if the error still exist, contact us
Check parallel number
32

W012 W013 W015 W016 W017 W018 W019 W020
W021
W022
W023 W025 W026 W027 W028 W029 W030 W031

Same para address Overtemprature Battery Reverse No AC Connection
AC voltage out of range AC frequency out of range
AC inconsistent in parallel system2 PV Isolation low
Leakage I high
DC injection high
PV short circuit Battery voltage high Battery voltage low
Battery open UPS Over load UPS voltage high
Meter Reversed UPS DCV high

W012 W013 W015

Restart inverter, if the error still exist, contact us
Check battery power connect

No AC Connection AC V Outrange AC F Outrange W019 PV Isolation low Leakage I high
DC Injection high PV short

Check AC Connection
Check AC voltage
Check AC frequency
Check parallel connection or contact us
Restart inverter, if the error still exist, contact us
Reset model, check if safety standard switch is at the right place Check the parallel CAN cables between inverters, and balance resistor is in the right place
Check and fix PV input connection

Bat Volt High Bat Volt Low Battery open

Check and fix battery connection

UPS Over load W029 W030 W031

Check and adjust UPS load
Restart inverter, if the error still exist, contact us
Check meter connection
Restart inverter, if the error still exist, contact us

7. Fan replace
Please check and clean the fan regularly. The recommended period is 6 months. Please replace the fan by following up the below diagram if there is troublesome with the fans. Turn off the system and wait for more than 5 minutes before disassembling the machine. 1. Open the wiring cover 2. Unplug the fan cable

33

34

3. Loosen the screws and remove them
4. Remove the fan fixing
5. Loosen the waterproof connector 6. Remove the fan and replace it 7. After the fan is installed, follow the steps just now to push back and assemble it back 35

PV Input data

LXP5K

Max. usable input current(A) Max. short circuit input current(A) Start input voltage(V) Startup voltage(V) Full power MPPT voltage range(V) DC nominal voltage(V) MPPT tracker DC voltage range(V) MPP operating voltage range(V) Max. power(W) Number of MPPT Inputs per MPPT

15/15/15 17/17/17 150-550
8000

AC Grid output data

Nominal Output Current(A) Max. Output Current(A) Rated voltage(V) Operating voltage range(V) Nominal power output(W) Max. apparent AC power(VA) Operating frequency(Hz) Operating frequency range(Hz)

21 24
5000 5500

Phase shift Reactive power adjust range

THDI Output inrush curent(A)

UPS AC output data
Nominal output current(A) Nominal output voltage(V) Rated output power(VA) Operating frequency(Hz) Peak power(VA)

21
5000 60

THDV Switching Time

Efficiency

Europe Efficiency

Max. Efficiency @ PV to grid Max. Efficiency @ battery to grid MPPT Efficiency

Battery data

Type

Max. charge current(A)

110

Max. discharge current(A)

110

Nominal voltage(V)

Voltage range(V)

General Data

Integrated disconnect

Reverse polarity protection

DC switch rating for each MPPT Output over-voltage protection varistor

Output over current protection

Ground fault monitoring

Grid monitoring

Pole sensitive leakage current Monitoring unit

AFCI

RSD Dimensions(mm)

Weight(kg)

Degree of protection

Cooling concept Topology

Natural convection

Relative humidity

Altitude(m)

Noise emission(dB)

Internal consumption(W)

Display

Communication interface Standard warranty

LXP7.6K/8K
170-480 10000 31.6/33.3
37 8000 8900
33.3 8000
160/167 160/167

LXP9K
190-480 14000

LXP10K
25/15/15 34/17/17
100 140 210-480 360 100-600 60-480 16000
3 2/1/1

LXP11K
210-480 16000

37.5 41
9000 9900

41.6
46 240 180-270
10000 11000 50/60 45-55/55-65 0.99@full load -0.8~+0.8 leading Adjustable <3% TBD

44 48
11000 11500

33.7

41.6

240

9000

10000

50/60

1.1xPn, 5min/1.25xPn, 1min/1.5xPn, 1s/2xPn, 0.1s

<3%

<20

44 11000

96% 97.5% 94% 99.9%

Lead-acid battery/Lithium battery

190

210

230

190

210

230

48

40-60

DC switch Yes Yes
Yes Yes Yes Yes Yes OPT OPT 580490240mm(22.819.39.4inch) 44kg(96.8 Ibs) NEMA4X / IP 65 FAN
Transformer-less 0-100% <2000m <50dB <15W
Touch color screen Rs485/ Wi-Fi/ CAN
5years

LXP12K
230-480 18000
50 50 12000 13200
50 12000
250 250

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals