LUXPOWERTEK SNA3000 WPV ECO Hybrid Inverter User Manual

June 16, 2024
LUXPOWERTEK

LUXPOWERTEK SNA3000 WPV ECO Hybrid Inverter

Specifications

Installation
Before installing the ECO Hybrid Inverter, please ensure that you have read and understood all safety precautions mentioned in the user manual. Follow the steps below for installation:

  1. Select a suitable location for the inverter installation. Ensure it is well-ventilated and away from direct sunlight.
  2. Mount the inverter securely on the wall using the provided mounting brackets.
  3. Connect the solar panels to the inverter using the appropriate cables, following the instructions provided in the user manual.
  4. Connect the battery bank to the inverter using the provided cables and ensure proper polarity.
  5. Connect the AC load to the inverter output using the designated terminals.
  6. Check all connections for tightness and ensure there are no loose or exposed wires.
  7. Turn on the inverter using the power switch.

Operation

The ECO Hybrid Inverter is designed to convert solar power into usable AC power. Follow these steps to operate the inverter:

  1. Ensure that the solar panels are receiving sufficient sunlight.
  2. Monitor the inverter’s LCD display for real-time information such as input voltage, output power, and battery status.
  3. In case of power outages, the inverter will automatically switch to battery power and continue supplying electricity to connected loads.
  4. To shut down the inverter, turn off the power switch and disconnect the AC load and solar panels.

Maintenance
To ensure optimal performance and longevity of the ECO Hybrid Inverter, regular maintenance is recommended:

  1. Keep the inverter clean and free from dust accumulation. Use a soft cloth to wipe the exterior surfaces.
  2. Inspect all cables and connections periodically for signs of wear or damage. Replace any damaged cables immediately.
  3. Check the battery bank regularly for proper voltage levels and ensure it is adequately charged.
  4. Refer to the user manual for any specific maintenance requirements or recommendations.

FAQ

  • Q: Can I connect multiple solar panels to the ECO Hybrid Inverter?
    A: Yes, you can connect multiple solar panels to the inverter. Ensure that the total combined power output of the panels does not exceed the maximum supported wattage of the inverter.

  • Q: Can I use the inverter during a power outage?
    A: Yes, the ECO Hybrid Inverter is designed to provide backup power during power outages. It will automatically switch to battery power to supply electricity to connected loads.

  • Q: How can I monitor the performance of the inverter?
    A: You can download the LUX POWER Monitor App from the respective app stores (Android or iOS) to monitor real-time information and performance of the inverter.

USER MANUAL

Where sun shined Power always on

Information on this Manual

Validity
This manual is valid for the following devices:SNA3000 WPV/SNA4000 WPV/SNA5000 WPV/SNA6000 WPV

Scope
This manual provides the installation, operation and troubleshooting of this unit, please read this manual carefully before installations and operations.

Target Group
For qualified persons and end users. Qualified persons and end users must have the following skills:

  • Knowledge about this unit operation
  • Training in deal with the security issues associated with installations and electrical safety
  • Training in the installation and commissioning of electrical devices and installations
  • Knowledge of the applicable local standards and directives

Safety Instructions

WARNING : This chapter contains important safety and operating instructions. Read and keep this manual for future reference.

  • All the operation and connection need to be operated by qualified persons.
  • Before using the unit, read all instructions and cautionary marking on the unit. Any damage caused by inappropriate operation is not warranted by Luxpower .
  • All the electrical installation must comply with the local electrical safety standards.
  • Do not disassemble the unit. Take it to a qualified service center when service or repair is required, incorrect re-assembly may result in a risk of electric shock or fire. Do not open inverter cover or change any components without
  • Luxpower’s authorization, otherwise the warranty commitment for the inverter will be invalid.
  • To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning, turning off the unit will not reduce this risk.
  • CAUTION-To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries and lithium batteries, other types of batteries may burst, causing personal injury and damage.
  • NEVER charge a frozen battery.
  • For optimum operation of this unit, please follow required spec to select appropriate cable size and breaker.
  • Please strictly follow installation procedure when you want to disconnect AC or DC terminals, please refer to INSTALLATION section of this manual for the details.
  • GROUNDING INSTRUCTIONS -This unit should be connected to a permanent grounded wiring system,  be sure to comply with local requirements and regulation to install this inverter.
  • NEVER cause AC output and DC input short circuited. Do not connect to the mains when  DC input short circuits.

Brief Introduction

Features of the inverter

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-020

SONAR series is a multifunctional, high frequency pure sine wave ECO Hybrid inverter solar inverter, features:

  • Applicable for pure off grid inverter/ backup power / self-consumption / on grid situation Integrated with 2 MPPT solar charge controllers, MPPT ranges 120V~385V
  • Rated power 6KW, power factor 1
  • Be able to run with or without battery in ongrid and offgrid mode
  • With separated generator input interface, able to control generator remotely
  • Solar and utility grid can power loads at the same time
  • With integrated advanced parallel function, up to 10pcs max paralleling
  • Support CAN/RS485 for Li-ion battery BMS communication
  • WIFI/ GPRS remote monitoring , setting and firmware update, support website, free IOS/Android APP

Interface of the inverter

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-03

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-04

Packing List

Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items in the package:

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-05

Storing the Inverter
The inverter must be stored appropriately if not installed immediately, refer to below figure.

CAUTION

  • The inverter and its components must be stored in its original packaging.
  • The storage temperature should be within -25~60 and humidity within 0~85%.
  • The packing should be upright and the maximum stacked layers is 6.
  • Do not directly expose the inverter and its packaging to sunshine, and raindrops and keep away from corrosion.

 Installation

Preparation
The system connection is as below:

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-002

Please prepare the breakers and cables in advanced before installation.

  1. Battery connection: For safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. The recommend battery capacity is 150AH-200AH, the recommended spec of DC breaker is 150A/60V. Recommended battery cable and terminal size:
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-08

  2. AC connection: Please install a separate AC breaker between inverter and AC input power source, inverter and AC output load. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 32A. Recommended AC input/ AC output /GEN cable size for each inverter.
    Model| Gauge| Cable (mm2)| Torque Value
    ---|---|---|---
    SNA6000WPV| 10AWG| 6| 1.2 Nm

  3. PV Connection: Please install separately a DC circuit breaker between inverter and PV modules. The recommended of DC breaker is 600V/25A. It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below:

Model Gauge Cable (mm2) Torque Value
SNA6000WPV 1x12AWG 4 1.2 Nm
  • Before connecting all wiring, please take off bottom cover by removing 3 screws as shown below.

Mounting the Unit

Notice
Consider the following points before selecting where to install:

  • Mount on a solid surface
  • Do not mount the inverter on flammable construction materials.
  • For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
  • The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
  • The recommended installation position is to be adhered to the wall vertically.

Steps to mounting the unit

  1. Step1. Use the wall-mounting bracket as the template to mark the position of the 4 holes, then drill 8 mm holes and make sure the depth of the holes is deeper than 50mm.
  2. Step2. Install the expansion tubes into the holes and tight them, then use the expansion screws (packaged together with the expansion tubes) to install and fix the wall-mounting bracket on the wall.
  3. Step3. Install the inverter on the wall-mounting bracket and lock the inverter using the security screws.

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-010

Battery Connection
Battery Power Cable Connection
Note: for lead acid battery, the recommended charge current is 0.2C( C to battery capacity)

  1. Please follow below steps to implement battery connection:
  2. Assemble battery ring terminal based on recommended battery cable and terminal size.
  3. Connect all battery packs as units requires. It’s suggested to connect at least 200Ah capacity battery for SNA5000 WPV.
  4. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2 ~3Nm. Make sure polarity of the battery is correctly connected and ring terminals are tightly screwed to the battery terminals.

Lithium Battery Connection
If choosing lithium battery for SNA5000 WPV, please make sure the battery BMS is compatible with Luxpower inverter. Please check the compatible list in the Luxpower website.

Please follow below steps to implement lithium battery connection

  1. Connect power cable between inverter and battery
  2. Connect the CAN or RS485 communication cable between inverter and battery. If you do not get the communication cable from inverter manufacturer or battery manufacturer, please make the cable according to the PIN definition
  3. Lithium battery configuration, in order to communicate with battery BMS, you should set the battery type to “Li-ion” in Program “03” by LCD and choose the right battery brand (for details, please check the LCD setting chapter), users can also choose the battery type and brand by monitor system.

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-011

2.4 CT
To measure the power imported from and exported to the grid, a pair of Cts must be installed at the service entry point in or near the main service panel. We standardly supply 2 CT for one inverter,”External Grid CT” function is off by default, and if you need inverter to export power to compensate the grid loads, you can set “External Grid CT” function to Enable” state. Please refer to section 4.4 LCD Settings for detected setting info.

CT Port Pin definition
The CT interface for CT connection is a RJ45 port

Pin Description
CT-L1 CT-L2
1/3 B
2/4 A
5 CT1N
6 CT1P
7 B2
8 A2

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-012

Please refer to the connection diagram to determine the correct position of the Grid CT and securely attach it to the L wire at the service entry point in the main service panel. The arrow on the CT should point towards the inverter. (*** Incorrect installation of the CT may result in the display showing incorrect information, and the inverter features may not function properly.) If the CT is installed in the wrong direction, you can change the CT direction on your inverter by selecting “CT Direction Reversed” in the Advanced Tab. There is no need to make any physical changes.

CT Clamp Ratio
The inverter support 3 ratios of CT clamp- 1000:1 , 2000:1 and 3000:1 . The CT ratio of the CTs in the accessory bag is 3000:1. If you are using a 3rd party CT, please ensure the CT ratio is one of them, and select the correct CT ratio setting in the inverter monitor page or on the inverter LCD.

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-014

AC Input/Output Connection

CAUTION

  • There are two terminal blocks with “IN” and “OUT” markings. Please do NOT disconnect input and output connectors.
  • Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.

Please follow below steps to implement AC input/output connection

  1. Before making AC input/output connection, be sure to open DC protector or disconnected first.
  2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
  3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure to connect PE protective conductor first.
  4. Insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor first.
  5. Make sure the wires are securely connected.

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-015

PV Connection
Please follow below steps to implement PV module connection:

  1. Remove insulation sleeve 10 mm for positive and negative conductors.
  2. Check correct polarity of connection cable from PV modules and PV input connectors.
  3. Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
  4. Make sure the wires are securely connected.
  5. Finally, after connecting all wiring, please put bottom cover back by screwing two screws as shown below.

Generator Connection

L→LINE (brown or black)
N→Neutral (blue)

  1. Before making Generator connection, be sure to open DC protector or disconnected first.
  2. Remove insulation sleeve 10mm for 2 conductors.
  3. Insert L and N wires according to polarities indicated on terminal block and tighten the terminal screws All lux units can work with generator.

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-017

  • Users can connect the generator output to ECO Hybrid inverters. GEN input terminal.
  • The generator will be automatically started when battery voltage is lower than the cut-off value or there is charge request from BMS. When voltage is higher than AC charge setting value, it will stop the generator
  • Battery will get charged when the generator is turned on, and the generator is bypassed to AC output to take all loads .

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-018

  • The system will use AC first if there is both utility input and generator input.
  • The capacity of the generator is recommended It is supported to parallel 2~3 PCS inverter with single phase in single phase parallel system and three phase parallel system to charge battery with Generator! And it is depends on the load performance of the generator too.
Number of the single parallel inverter Capacity
Single inverter >10KW
2 parallel >15KW

Dry Contact Signal control

The Dry port(NO2,COM2) could be used to deliver signal to external device when battery voltage reaches warning level. The GEN port(NO1,COM1) could be used to wake-up the Generator and then the generator can charge the battery.

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-019

Parallel function

SNA series inverter support up to 10 units to composed single phase parallel system or three phase parallel system, for parallel system setup

  1. Step1. Cable connection: the system connection is as below
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-021
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-022

  2. Step2. Please put the CAN communication PIN to on status for the first and the end inverter
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-023

  3. Step3. Setup the monitor for the system, add all datalogs in one station. Users can login to the visit interface of monitor system, Configuration->station->Plant Management->add datalog to add the datalogs.
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-024

  4. Step4. Enable share battery for the system if the system share one battery bank, otherwise disable the shared battery function

  5. Step5. Set the system as a parallel group in the monitor system
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-025

For more detailed guidance for paralleling system, please visit https://www.luxpowertek.com/download/And download the guidance

Power and EPS ON/OFF

  1. LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-026 Power Switch: Control power supply for the unit
  2. EPS Output Switch: Use to control the AC output After connection, please turn on both switch. Users can turn off the EPS output switch to turn off power supply in some emergency case

Working modes

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-027LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-028LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-029LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-030
Working Modes related setting description

Situation| Setting 1| Setting 2| Setting 3| Working modes and Description
---|---|---|---|---
AC abnormal| NA| NA| NA| off grid inverter mode

if P_Solar>=P_load, solar is used to take load and charge battery  if P_Solar<P_load, solar and battery take the load together, system will discharge until battery lower than the Cut Off Voltage/SOC

| | | | Hybrid Mode 1(charge first)
| | | | Solar power will used to charge battery first,
| | In the AC first time| NA| 1.The solar power will be used to charge the battery first. AC will take load. 2.if solar power is higher than power need to charge the battery, the

extra power will used to take load togther with grid

| | | | 3.If there is still more energy after charge battery and take the load,
| | | | it will feed enegry into grid if export to grid function is enabled
|

PV&AC Take Load

| | AC charge accroding to Time| Hybrid Mode 1(charge first)+AC charge battery if solar power is not enough to charge battery
|
| Jointly Enable| Enable AC charge and in the AC charge time|

AC charge accroding to

| Hybrid Mode 1(charge first)+AC charge battery if solar power is not

enough to charge battery and the battery voltage/SOC is lower than AC

AC normal| | | battery voltage or SOC| start charge voltage/SOC, the AC will stop charging when the battery
| | | | Voltage/SOC is higher than AC end charge battery voltage/SOC
| | | | Hybrid Mode 2(load first)
| |

  1. Not in the AC first time and
  2. Disable AC charge or not in the AC charge time

|

NA

| Solar power will used to take load first,

1.if solar power is lower than load, battery will discharge together to take load until battery lower than EOD voltage/SOC

| | | | 2.if solar power is higher than load, the extra power will used to charge
| | | | battery, if there is still more energy, it will feed into grid if enable export
| | In the AC first time| NA| Bypass Mode

AC will take the load and Solar is used to charge battery

| | | | Bypass Mode+AC charge battery
| | | AC charge accroding to Time| Solar is used to charge battery

AC will take load and also charge battery during AC charge time

| | | | if solar power is not enough
| PV&AC Take Load| Enable AC charge and in the AC charge time| |
| Bypass Mode+AC charge battery
| Jointly Disable| | AC charge accroding to SOC/Battery voltage| Solar is used to charge battery

AC will take load and also charge battery when battery SOC/Volage is lower than start SOC/Voltage, and the AC will stop charging when the

| | | | battery Voltage/SOC is higher than AC end charge battery voltage/SOC
| | | NA| off grid inverter mode
| |

  1. Not in the AC first time and
    Disable AC charge or not in the AC charge time

| if P_Solar>=P_load, solar is used to take load and charge battery

if P_Solar<P_load, solar and battery take the load together, system will

| | | | discharge until battery lower than EOD Voltage/SOC

  1. SONAR can work as traditional off grid inverter or as a hybrid inverter. When disable PV&AC Take load Jointly, it will work as a traditional off grid inverter, otherwise it will work as a hybrid
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-031

  2. Working as a traditional off grid inverter. In this situation, inverter either use (solar+battery) to take load or use AC take load. Related settings
    AC First: During the setting time, system will use AC to take load first, use solar power to charge the battery. If the battery is full, solar power may be wasted. When out of the setting time, system will use battery and solar to take load until battery voltage/SOC is lower than cut off voltage/SOC
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-031

  3. Working as a hybrid inverter. Related settings
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-032
    3.1 AC First: During this setting time, system will use AC to take load, use solar power to charge the battery first. If there is extra solar power, extra solar power will take the load. When out of the setting time, system will use solar and battery to take load first until the battery voltage/SOC is lower than On Grid EOD settings, then it will use AC to take the load.
    LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-033

Export to Grid/Export Power percent: Users can also enable export function, it is allowed and set export power percent

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-034AC Charge function Disable: The system will not use AC to charge the battery(except Li ion BMS set force charge flag )

  • According to Time: During the setting time, system will use AC to charge the battery until battery full and battery will not discharge during the setting time.
  • According to Battery Voltage: During the setting time, system will use AC to charge the battery if battery voltage is lower than AC Charge Start Battery Voltage and will stop when Voltage is higher than AC Charge End Battery Voltage. And
  • battery will not discharge during the setting time.
  • According to Battery SOC: During the setting time, system will use AC to charge the battery if battery SOC is lower than AC Charge Start Battery SOC and will stop when Voltage is higher than AC Charge End Battery SOC. And battery will not discharge during the setting time.

LCD display and settings

LED Display

LED Indicator Messages

1

|

Green

| Solid On| Working normal
Flashing| fast: Warning

slow: Firmware update

2| Red| Flashing| Fault condition occurs in the inverter

LCD Display

No. Description Remarks

1

|

Generally Information Display Area

| Display the currently time/date by default(year/month/day/ hour/ minute” switching automatically). When press Up or Down buttons, this area will display the firmware version information, serial number etc. Display the setting selection information when entering settings
2| On-grid solar inverter output power and energy data| This area shows the data of PV voltage, power and the setting of PV input connection information

3

|

Battery information and data

| This area shows the battery type, battery brand(lithium battery), the lead- Acid battery setting of CV voltage, Floating charging voltage, Cut off voltage, Discharge end voltage . And display the voltage, SOC and power in turns of period of 1 seconds

4

|

System working status

/ setting code

| There are three type of working status- normal, warning and fault, in right side of this area, there are code display, it will display different type of code -the system working mode code, warning code, fault code and setting code

5

| UPS/EPS output information and data| When UPS function is enabled, this area will display UPS voltage, frequency, power etc. in turns of periods of 1s

6

| Programming & the percentage of AC output power| When firmware updating in process, it will display relevant information When in grid off, this area will display the Percentage of the maximum AC output power
7| Loads consumption| Display the power consumption by the loads in on grid model

8

|

Grid information and Generator information

| Display the grid(GRIDA) information of voltage, frequency, input or output power, the Generator (GRIDB) information of voltage, frequency, input power ,switch period of 1s

9

|

Working mode settings area

| When make settings on the SNA5000 inverter through the LCD, this area will display the AC Charge, Force Discharge, Charge First option for setting on those working modes. It will not display those information unless in the setting process.

Inverter Status Display

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-037LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-038LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-039LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-040LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-041LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-042LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-043LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-044LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-045

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-046LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-047LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-048LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-049LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-050LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-051LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-052LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-053LUXPOWERTEK-SNA3000
-WPV-ECO-Hybrid-Inverter-054

Monitor System for ECO Hybrid inverter

  • Users can use wifi dongle / WLAN dongle / 4G dongle (Avaiblable from 2021 March for some countries) to monitor the energy storage system, The monitor website is: server.luxpowertek.com
  • The APP is also available in the google play and apple APP store(Scan two code bar to download the APP).
  • Please download the introduction of guidance by website: https://www.luxpowertek.com/download/Document Reference:
  1. Wifi Quick Guidance
    Quick guidance for setting password for wifi module, the paper is also available in the wifi box

  2. Monitor system setup for Distributors and Monitor system setup for endusers, Monitor system registration, wifi password setting, and wifi local monitor and setting

  3. Lux_Monitor_UI_Introduction
    Introduction of monitor interface

  4. WebsiteSettingGuidance
    Introduction of website settings for offgrid inverter

LUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-055

Specifications

Table 1 Line Mode Specifications

INVERTER MODEL| SNA6000WPV/SNA5000WPV/ SNA4000WPV/SNA3000WPV
Input Voltage Waveform| Sinusoidal (utility or generator)
Nominal Input Voltage| 230Vac
Low Loss Voltage| 170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage| 180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage| 280Vac±7V
High Loss Return Voltage| 270Vac±7V
Max AC Input Voltage| 280Vac
Nominal Input Frequency| 50Hz / 60Hz (Auto detection)
Output Short Circuit Protection| Software protect when GridOff discharge Circuit Breaker protect when GridOn Bypass
Transfer Time| <20ms @ Single        <30ms @ Parallel
Output power derating: When AC input voltage drops to 170V, the output power will be derated.| Output Power Rated Power 20% Power
Charge power derating:

When AC input voltage drops to 170V depending on models, the charge power will be derated.

| Output Power

Rated Power

50% Power

Input Voltage

90V        170V             280V

Output power derating: When AC input voltage drops to 200V, the output power will be derated.| Max inv curren: 26.5A; Max inv Power: 6kW;
Table 2 Inverter Mode Specifications
Rated Output Power| 6KVA/6KW| 5KVA/5KW| 4KVA/4KW| 3KVA/3KW
Output Voltage Waveform| Pure Sine Wave
Output Voltage Regulation| 208Vac/220Vac/230Vac/240Vac±5%
Output Frequency| 50Hz / 60Hz
Peak Efficiency| 93%
Overload Protection| 5s@≥150% load; 10s@110%~150% load
Surge Capacity| 2* rated power within 5 seconds
Battery Voltage Range| 46.4V-60V(Li)       38.4V-60V(Lead_Acid)
---|---
High DC Cut-off Voltage| 59VDC(Li)            60VDC(Lead_Acid)
High DC Recovery Voltage| 57.4VDC(Li)          58VDC(Lead_Acid)

Low DC Warning Voltage

| load < 20%| 44.0Vdc(Settable)
20% ≤ load < 50%| Warning Voltage @load < 20% -1.2V
load ≥ 50%| Warning Voltage @load < 20% -3.6V
Low DC Warning Return Voltage       Low DC Warning Voltage@Different load +2V
Low DC Cut-off Voltage| load < 20%| 42.0Vdc(Settable)
20% ≤ load < 50%| Cut-off Voltage @load < 20% -1.2V
load ≥ 50%| Cut-off Voltage @load < 20% -3.6V
Low DC Cut-off Return Voltage| Cut-off Voltage@load<20%≥45V| Low DC Cut-off Voltage @load<20%+3V
Cut-off Voltage@load<20%<45V| 48V
Low DC Warning SOC| 20% SOC ( Settable )
Low DC Warning Return SOC| Low DC Warning SOC +10%
Low DC Cut-off SOC| 15% SOC (Grid on) ( settable) 15% SOC (Grid off ) ( settable)
Low DC Cut-off Return SOC| Low DC Cut-off SOC +10%
Charge Cut-off Voltage| 58.4Vdc
No Load Power Consumption| <60W
Table 3 Charge Mode Specifications
Utility Charging Mode|
Lead_Acid Battery Charging Algorithm| 3-Step
Max. AC Charging Current| 60Amp(@VI/P=230Vac)
Bulk Charging Voltage| Flooded Battery| 58.4Vdc
AGM / Gel Battery           56.4Vdc
Floating Charging Voltage                                     54Vdc
Battery Voltage, per cell Charging Current 2.43Vdc(2.35Vdc)  Voltage

2.25VdcLUXPOWERTEK-SNA3000-WPV-ECO-Hybrid-Inverter-057100% Charging Curve 50% T0  T1

T1=10*T0,  minimun  10mina,  maxmum 8hour Current

Bulk  Absorption Maintenance  Time (Constant Current)    (Constant Voltage) (Floating)


MPPT Solar Charging Mode|
Start-up Voltage| 100Vdc±10Vdc
PV Array MPPT Voltage Range| 120Vdc~385Vdc
Max. PV Array Open Circuit Voltage| 480Vdc
Table 4 General Specifications

INVERTER MODEL

| SNA6000WPV/SNA5000WPV SNA4000WPV/SNA3000WPV
Safety Certification| CE
Operating Temperature Range| 0°C to 50°C
Storage temperature| -15°C~ 60°C
Humidity| 5% to 95% Relative Humidity (Non-condensing)
Altitude| <2000m
Dimension(DWH)| 505330135mm
Net Weight| 14.5Kg

Trouble Shooting & Error List

The failures mainly divided into 5 categories, for each category, the behavior is different:

Code Description Trouble shooting
E000 Internal communication fault1 Restart inverter, if the error still

exist, contact us (DSP&M3)
E002| Bat On Mos Fail| Restart inverter, if the error still exist, contact us
E003| CT Fail| Restart inverter, if the error still exist, contact us
E008| CAN communication error in Parallel System| Check CAN cable connection is connected to the right COM port
E009| No master in parallel system| Check parallel setting for master/Slave part, there should be one master in the system
E012| UPS output short circuit| Check if the load is short circuit, try to turn off the load and restart inverter
E013| UPS reserve current| Restart inverter, if the error still exist, contact us
E015| Phase Error in three phase parallel system| Check if the AC connection is right for three phase system, there should one at least one inverter in each phase
E016| Relay fault| Restart inverter, if the error still exist, contact us
E017| Internal communication fault2| Restart inverter, if the error still exist, contact us (DSP&M8)
E018| Internal communication fault3| Restart inverter, if the error still exist, contact us (DSP&M3)
E019| Bus voltage high| Check if PV input voltage is higher than 480V
E020| EPS connection fault| Check if EPS and AC connection is in wrong terminal
E021| PV voltage high| Check PV input connection and if PV input voltage is higher than 480V
E022| Over current internal| Restart inverter, if the error still exist, contact us
E024| PV short| Check PV connection

E025

|

Temperature over range

| The internal temperature of inverter is too high,

turn off the inverter for 10minutes, restart the inverter, if the error still exist, contact us

E026| Internal Fault| Restart inverter, if the error still exist, contact us (Bus sample)

E028

| Sync signal lost in parallel system| Check CAN cable connection is connected to the right COM port

E029

| Sync triger signal lost in parallel system| Check CAN cable connection is connected to the right COM port
E031| Internal communication fault4| Restart inverter, if the error still exist, contact us (DSP&M8)
Code| Description| Trouble shooting
---|---|---

W000

|

Communication failure with battery

| Check if you have choose the right battery brand and communication cable is right, if the warning still exist, contact us
W003| Communication failure with meter| Check communication cable, if the warning still exist, contact us

W004

|

Battery failure

| Inverter get battery fault info from battery BMS, restart battery, if the warning  still  exist, contact us or battery manufacture
W008| Software mismatch| Please contact Luxpower for firmware update
W009| Fan Stuck| Check if the fan is OK
W012| Bat On Mos| Restart inverter, if the error still exist, contact us
W013| Over temperature| The temperature is a little bit high inside inverter
W015|

Bat Reverse

| Check the battery connection with inverter is right, if the warning still exist, contact us
W018| AC Frequency out of range| Check AC frequency is in range
W019| AC inconsistent in parallel system2| Reconnect the AC input or Restart inverter, if the error still exist, contact us
W025| Battery voltage high| Check if battery voltage is in normal range

W026

| Battery voltage low| Check if battery voltage is in normal range, need to charge the battery if battery voltage is low

W027

| Battery open| Check if there is output from the battery and battery connection with inverter is OK
W028| EPS Over load| Check if EPS load is too high
W029| EPS voltage high| Restart inverter, if the error still exist, contact us
W031| EPS DCV high| Restart inverter, if the error still exist, contact us
INPUT (PV DC) SNA 3000W                    SNA 4000W                     SNA 5000W SNA 6000W

Max. PV array power(W)| 6000 (3000/3000)| 8000 (4000/4000)| 8000 (4000/4000)| 8000 (4000/4000)
Rated PV input voltage(V)| 320
Number of independent MPPT inputs| 2
PV input voltage range(V)| 100~480
MPPT voltage range(V)| 120~385
Start-up voltage(V)| 100
Max. PV input current per MPPT(A)| 17/17
Max. PV short-circuit current input per MPPT(A)| 25/25
Battery
Compatible battery type| Lithium-ion/Lead-Acid
Rated battery voltage(V)| 48
Battery voltage range(V)| 38.4~60
Max. charging/discharging current(A)| 70| 90| 110| 140
Max. charging/discharging power(W)| 3000| 4000| 5000| 6000
Recomand capacity of battery per inverter| >100AH| >200AH| >200AH| >200AH
Force wake up battery from PV function| YES
Force wake up battery from Grid function| YES
Grid
Rated AC voltage(V)| 230
Rated AC frequency(Hz)| 50/60
Rated AC output current(A)| 13.5| 17.5| 22| 26.5
Rated AC output power(W)| 3000| 4000| 5000| 6000
Max. AC intput current(A)| 26| 35| 35| 39.5
Max. AC intput power(W)| 6000| 8000| 8000| 9000
PF| 0.99
THDI| <5%
Rated AC current of BYPASS relays(A)| 40
UPS
Rated output power(W)| 3000| 4000| 5000| 6000
|
Rated output voltage(V)| 230
Rated output current(A)| 13.5| 17.5| 22| 26.5
Rated output frequency(Hz)| 50/60
Surge power, duration| 2Pn, <2S
Switching time| <15ms@Single/ <30ms@Parallel
Wave form| Sine wave
THDV| 3%
Efficiency
Max. MPPT efficiency| 0.99
Max. efficiency| 0.93
EU efficiency| /
Max. charging efficiency| 0.93
Max. discharging efficiency| 0.93
Protection
Over current/voltage protection| YES
AC Short-circuit current protection| YES
Grid monitoring| YES
AC Surge protection Type III| YES
Battery reverse polarity protection| YES
General
Dimensions(WHD)| 303505135mm/11.919.95.3inch
Weight| 14.5kg/32lbs
Ingress protection rating| IP20
Operating environment temperature range| 0~50°C
Storage temperature range| -15~60°C
Relative humidity| 5%~95%
Display & Communication interface| LCD+LED, RS485/Wi-Fi/CAN
Warranty| 2years
Cooling method| FAN

www.luxpowertek.com
info@luxpowertek.com
LUX POWER TECHNOLOGY CO., LTD

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals