LUXPOWER LXP Series LXP 3K Hybrid Inverter User Manual

June 5, 2024
LUXPOWER

USER MANUAL
LXP HYBRID INVERTER Standard Model:
LXP 3K/3.6K/4K/4.6K/5K/6K Hybrid Parallel Model:
LXP 3K/3.6K/4K/4.6K/5K/6K MG
High Voltage Model:
LXP 4K/5K/6K HB

” Where sun shied Power always-on ,,

Monitor APP Download

|
---|---
https://play.google.com/store/apps/details?id=com.nfcx.luxinvpower| https://itunes.apple.com/cn/app/luxpowerview/id1415841608?mt=8

Safety

1.1 Symbol Explanation

Symbols in This Manual

The general information and safety instruction is highlighted with the following symbols in this manual:

DANGER WARNING CAUTION Notice

Danger indicates a hazardous situation which, if not avoided, will result in death or serious injury. ”| “Warning” indicates a hazardous situation that, if not avoided, could result in death or serious injury.| “ Caution indicates a hazardous situation which, if not avoided, could result in minor or moderate injury.”| “Notice” provides tips that are valuable for the optimal operation of your products.

Symbols on Inverter Label

Following list shows the meaning of all the safety symbols on inverter type label:

Mark

|

RCM Mark

|

Certification

|
Beware of the hot surfaces. The inverter can be hot during operating, avoid contact during operating.
---|---|---|---

Danger of high voltage. Danger to life due to the high voltages in the inverter.

Risk of electric shock.
Observe enclosed documentation
Danger of high voltage. Residual voltage in the inverter needs 5min to discharge, wait 5min before operation.

General Saftey Instructions

The inverter has been designed and tested strictly according to international safety regulations. Read all
safety instructions carefully prior to any work and observe them at all times when working on or with the
inverter. The operator must be qualified personnel and the installation must be capable of relevant
national or international standards or regulations.
Incorrect operation or work may cause:
– injury or death to the operator or a third party; or
– damage to the inverter and other properties belonging to the operator or a third party.

Important Safety Notification.

There are many safety issues that need to be carefully notified before, during, and after the installation, and also in future operation and maintenance, following is important safety notifications to the operator, owner, and user of this product’s inappropriate usage.

DANGER Dangers of High Voltages and Large Current.

  • Beware of high PV voltage. Please turn off the DC switch of PV Panel output before and during the installation to avoid electric shock.
  • Beware of high grid voltage. Please turn off the AC switch of the grid connection before and during the installation to avoid electric shock.
  • Beware of the large current of the battery output. Please turn off the battery module before and during the installation to avoid electric shock.
  • Do not open the inverter when it’s working to avoid electric shock and damage from live voltage and current from the system.
  • Do not operate the inverter when it’s working, only the LCD and buttons can be touched in limited cases by qualified personnel, other parts of the inverter can be touched when the inverter is under a safe state(e.g. fully shut-down).
  • Do not connect or disconnect any connections (PV, battery, grid, communication, etc.) of the inverter when it’s working.
  • Make sure the inverter is well-grounded, an operator should make sure itself is well protected by reasonable and professional insulation measurements (e.g. personal protective equipment (PPE)).
  • Inspect relevant existing wiring on-site of the installation is under good condition before installation, operation or maintenance.
  • Inspect the connections are good between inverter and PV, battery and grid during installation to prevent damage s or injuries caused by bad connections.

WARNING Avoid misoperation and Inappropriate Usage

  • All the work of this product (system design, installation, operation, setting and configuration, maintenance, etc. must be carried out by qualified personnel as required.
  • All connections must be in accordance with local and national regulations and standards.
  • Only when permitted by the utility grid, the inverter and system can interconnect with the utility grid.
  • All the warning tables or nameplates on the inverter must be clearly visible and must not be removed, covered, or pasted.
  • The installation should choose the right position and location as required in this manual with consideration to the safety of users in future operations.
  • Please keep the children away from touching or misoperation the inverter and relevant system.
  • Beware of burning hurt, the inverter and some parts of the system could be hot when working, please do not touch the inverter surface or most of the parts when they are working. During inverter working states, only the LCD and buttons could be touched.

CAUTION

Only qualified personnel can change the inverter settings.
There might be possible damage to the health as a result of the effects of radiation, do not stay closer than 20cm to the inverter for a long time.

NOTICE

Please carefully read this manual before any work is carried out on this inverter, after the installation, please keep this manual carefully stored and easy to access at any time.
The qualified person should have had training in the installation and commissioning of the electrical system as well as dealing with hazards, also they should have the knowledge of the manual and other related documents. As the installer or operator, they are required to be familiar with local regulations and directives.

Brief Introduction

2.1 System Solution

This product and the relevant system are suitable for the following system applications (system diagram):

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Brief

Installation

3.1 Packaging List & Storing
Packaging List
When the packaging is unpacked, the inner components should be the same as described in below packaging list.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Packging

Storing the Inverter
The inverter must be stored appropriately if not installed immediately, refer to the below figure.

CAUTION
a) The inverter and its components must be stored in its original packaging.
b) The storage temperature should be within -25~60 and humidity within 0~85%.
c) The packing should be upright and the maximum number of stacked layers is 6.
d) Do not expose the inverter and its packaging to direct sunshine, and raindrops and keep away from corrosion.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Humidity

3.2 Select Location
The LXP hybrid inverters are designed as IP65 devices with the capability to be installed in both outdoor and indoor conditions. However, selecting an optimal installation location is highly recommended to increase the safety, performance, and lifespan of the inverter. Please note the installation should not be accessible to children for safety considerations.

Suggestions and Requirements
a) The wall for mounting should be strong enough to bear the weight of the inverter.
b) The ambient temperature is required to be within -25°C ~ 60°C.
c) To ensure the heat dispassion efficiency and inverter lifespan, do not install the inverter enclosed.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - lifespan

d) The structure of the wall where the inverter is mounted should not be flammable, or make sure the inverter is not surrounded by flammable or corrosion materials and is away from the gas.
e) Never install the inverter exposed to direct sunshine, rain, and snow. Please refer to the below figure and select a well-shaded place or install a shell to protect the inverter from direct sunshine, rain, snow, etc.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - rain

3.3 Install the Inverter

The inverter is wall-mounted installed, steps show below:
Step1. Use the wall-mounting bracket as the template to mark the position of the 4 holes, then drill 8 mm holes and make sure the depth of the holes is deeper than 50mm.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - deeper

Step2. Install the expansion tubes into the holes and tighten them, then use the expansion screws (packaged together with the expansion tubes) to install and fix the wall-mounting bracket on the wall.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - packaged

Step3. Install the inverter on the wall-mounting bracket and lock the inverter using the security screws.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - bracket

3.4 Connection
3.4.1 Connection Overview
The system connection diagram is as below:

LUXPOWER LXP Series LXP 3K Hybrid Inverter - UPS 1

Please prepare the breakers before connection, breakers selection recommendation for both DC and AC

Hybrid

| LXP 3K/3.6K/4K (MG)| LSP 4.6K/5K (MG)| LXP 6K (MG)| LXP 4K HB (MG)| LXP 5K HB (MG)|

LXP 6K HB (MG)

---|---|---|---|---|---|---
DC Breaker selection(2 poles)| 100A/100V| 100A/100V| 50A/500V| 50A/500V| 50A/500V| 50A/500V
AC Breaker selection(2 poles)| 40A| 50A| 50A| 50A| 50A| 50A
UPS Breaker selection(2 poles)| 40A| 40A| 50A| 50A| 50A| 50A

Connection Terminals and Interfaces Overview

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Terminal

3.4.2 PV Connection
The PV connection of the LXP hybrid inverter is the same as the traditional on-grid solar inverter (string inverter).

Notice

  • Before connecting the PV, please use the multi-meter to measure the PV array voltage to verify if the PV array is working normally, if not, please fix the PV array to a normal working state before connection
  • When your PV panel ambient temperature could possibly be lower than 0 ℃, then please check the PV array voltage up the ceiling and if you are not sure please ask your system panel provider for further assistance. As when the temperature is extremely low the PV panel voltage will increase by a certain percentage.

Cable Requirement:

Cross-section Cable Diameter Minimum Voltage
3 – 6 mm 2-2.6mm 600V

Step1: Turn off or disconnect the PV switch (DC switch). Then keep this switch always open during the connection.
Step 2: Assemble the PV connector

a) Strip 6~8mm insulation from the cable end.
b) Assemble the cable ends to crimp contacts.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - crimp

c) Lead the cable through the cable gland, then insert it into the corresponding insulator until it snaps into place, then tighten the cable gland.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - cable

When verified the PV connector is tightened, align the 2 half connectors and mate them together by hands until ‘click’ is felt or heard.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - elt

3.4.3 Battery Connection
This part in this manual only describes the battery connection on the inverter side, should you need more detailed information regarding the battery connection on the battery side please refer to the manual of the battery you are using.

Step 1: Assemble the terminal.battery connection.

NOTICE
For the first time power on, please turn on the batte ry after the LCD show “Run without Bat”, otherwise it may shorten the lifetime of the inverter.
For lead-acid batteries temperature sensor, please refer to Page29 “Cable Connection” figure.

Battery Communication Connection

If the battery type is lithium-ion or ternary battery which needs communication between the inverter and battery management system (BMS), the communication connection must be installed.

RJ45 Terminal Configuration of Battery Communication

Pin Function Description
1 BAT 485 B
2 BAT 485 A
3 BAT CAN L
4 BAT CAN H
5 NC
6 BAT NTC
7 BAT Wake UP
8 GND-S

Make the RJ45 terminal based on the above introduction of each Pin definition, you could either make an RS485 connector or CAN connector based on the best support connection way of your battery packs. For the Lead-acid battery temperature sensor, please connect the signal to Pin6 and Pin8, the other pins are not connected.(External temperature sensor is needed, the sensor is a 15KΩ thermistor for typical, or consult Luxpowertek)

NOTICE

For Li-ion battery

  1. If works with a lithium battery, please make sure it is compatible with the Lux units. Now Lux Power inverter is compatible with Pylontech, Dryness, Aoboet, Weco, Murata, and Merit 48V batteries.
  2. After the battery power cable and communication cable connection, users need to choose the battery brand by LCD
  3. The battery communication cable inside the Luxpower carton box is used for the Pylontech battery, if you are using a Pylontech battery, you can use the cable directly. Please note there is a label ‘BAT’ (need to plug into battery side) attached with the cable, do not plug the battery side terminal to the inverter side
  4. If you install more than 8pcs Pylontech batteries, you need a hub for the battery.
  5. Please remember to connect the Master battery to the inverter if you have a battery group, and set the Master battery for the battery group.(Please contact battery manufacturer for battery group setup).

For Lead-acid battery

  1. The lead-acid battery temperature sensor cable is optional, if required, please request the temperature sensor cable from your supplier.
  2. There are three stages for lead-acid battery charge. For the charge part, please set CV voltage e andfloating voltage. For the discharge part, please set the discharge cut off voltage for on-grid and off-grid

The connection between inverter and battery

LUXPOWER LXP Series LXP 3K Hybrid Inverter - battery

3.4.4 Grid Connection
Cable Requirements:

Cross-section Diameter
4 – 6 mm2 2 mm – 2.6 mm

Step 1: Assemble the AC connector.

AC Connector Structure Overview| a) Lead the AC cable through the cable gland, seal ring, and threaded sleeve, fully insert the conductors to corresponding terminals on the connection terminal and tighten the screws.
---|---
|
b) Refer to the below figure and confirm the AC cables are correctly connected. The difference between the AC connector and UPS connector is that the AC connector has a “Grid” mark on it and UPS does not| c) Assemble the GRID connector and make sure that the rib of the terminal block and the groove on the housing engage perfectly until a ‘click’ is heard or felt.
|

Step 2: Install the AC connector
a) Align the GRID connector and AC terminal and mate them together by hand until a ‘click’ is heard or felt.
b) An AC breaker (AC switch) should be installed between the inverter and the grid, confirm the AC breaker is working normally before connecting the AC cable from the inverter to the AC breaker. Turn off the AC breaker and keep it open.
c) Connect the PE conductor to the grounding electrode, and connect N and L conductors to AC breakers.
d) Connect the AC breakers to the AC grid.
e) You must install a separate single-phase circuit-breaker or other load disconnection unit for each inverter in order to ensure that the inverter can be safely disconnected under load.

NOTICE
The inverter has the function of detecting residual current and protecting the inverter against the residual current. If your inverter has to equip an AC breaker that has the function of detecting residual current, you must choose an AC breaker with a rating residual current of more than 300mA.

3.4.5 UPS/Back-up Connection

Cable requirements

Cross-section Diameter
4 – 6 mm2 2 mm – 2.6 mm

Step 1: Assemble and install the UPS connector process is the same as AC connectors which show in Chapter 5.4 Grid Connection (Step 1 and Step 2). Finish the UPS connector assembling and installation first of all.

Step2: UPS warning
There are 2 different UPS wiring modes in accordance with different local or national rules, standards or regulations. Please choose the suitable wiring mode according to the local requirements.
Mode A: Neutral line of alternative supply must not be isolated or switched. The connection diagram of UPS Connection Mode A is shown in the below figure.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - UPS

NOTICE
Backup loads neutral and grid neutral are connected internally inside the inverter, so the installer does not need to connect them outside. The power of the backup load should be lower than 5kW.

Mode B: Neutral lines of alternative supply can be isolated or switched.
The connection diagram of UPS Connection Mode B is shown below figure.

3.4.7.2 Safety Standard Configuration – SW2

By configuring the DIP switch the inverter could comply with different safety requirements of various areas.

Sw2 Safety Standard Configuration Switch Overview
Note: The DIP switch is composed of five-digit binary number PINs. Each PIN has two statuses when set upward to“ON”, its value turns to“1” when set downward, its value turns to “0”.
Safety Standard Configuration Guidance

3.4.7.3Blancing Resistor Configuration

By configuring the SW1 balancing resistor configuration switch, you could configure the balancing resistors of parallel CAN communication. This Function is used for multiple inverters paralleling operations.
Please turn on the DIP in the first and last inverter in the inverter loop. For more info, please check the parallel connection part.

3.4.7.4 Wireless Communication Module Connection

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Module
Connection

3.4.8 Grounding
The second protective earth (PE) terminal is equipped at the side of the inverter. Be sure to connect this PE terminal to the PE bar for reliable grounding.
Cable Requirements
3-6mm² copper cable or 10-16mm² aluminum cable.

NOTICE
Install the Protective Shell
When you finish all of the above chapters of connections, please don’t forget to install the protective shell back to the inverter. This step can be carried out either after finished grounding or c Tommi SSI one of the systems.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - shell

Operation Guide

4.1 Operation Mode
Users can have different settings to satisfy their demands, the working modes are as below:

Operation
mode

| Explanation| Related Settings|

Application Notes

---|---|---|---
Self-usage
(Default mode)| The priority of the PV energy will be Load > battery > grid, which means the energy generated by PV will be mainly used by local loads, and the rest will be stored in the battery, and excessive power will be feedback into the grid.| Effective when charge priority and force-time charge/discharge are disable| increase the self-consumption rate and reduce the energy bill significantly
Charge priority| The priority of the PV energy will be battery >Load >grid, which means the energy generated by PV will be used to charge the battery first, and then used by local loads, excessive power will be feedback into the grid.| Charge Priority and related time, SOC| When the load shedding always happens, users need to charge the battery first
Force time| Users can set the charging and discharging time and priority of energy use under Force Time Use mode. This is also used to flexibly make use of your system by customized settings by the users.| Force charge/discharge enable and disable, and related time SOC| This mode suits situations where the price difference of energy is big under Time of Use (To U)
Micro Grid
mode(Genset)| When used in the pure off-grid application, users may connect the Gen-set the output to grid input, when battery SOC is low. The inverter will use the generator to take the load and charge the battery.| Microgrid enable /disable| The area where is no grid and there is a utility
Off-grid mode| The inverter will switch to off-grid mode
automatically when there is no grid.| UPS enables| The area where is no grid

4.2 LCD operation and settings
4.2.1 LCD Menu Structure Overview

4.2.2 Status and Parameter show in LCD

a. Standby
The inverter is waiting for sufficient DC voltage from the PV or battery. It occurs when the sunlight is not sufficient to make the inverter work and battery SOC is low.
b. Fault
A fault occurred with the inverter or system. The inverter will stop working unless the fault or error is fixed.
For detailed information and troubleshooting please refer to Chapter 8. Troubleshooting & Maintenance.
C. Flash
When upgrading the firmware of the inverter, the inverter will work at flash status.

There are 2 ways to upgrade the firmware of the inverter:
– Remote upgrading based on the remotely connected server through the wireless communication module.
– Locally upgrading through RS485 communication connection.

d) PV Grid On
The inverter is working normally on-grid, and all the power generated by PV will export or feed in via the AC grid connection to your general loads and the grid.
e) PV Charge
The inverter is working normally, the power generated by PV is within a range that all the PV power is used to charge the battery, while there is no excessive power rested to output from neither the AC Grid connection nor UPS connection.
f) PV Charge + Grid On
The inverter is working normally on-grid, the power generated by PV is sufficient and within a range in which PV power is used to charge the battery and there is still excessive PV power rested to export or feed in via the AC grid connection. Under this inverter working status, your general loads will either consume the power from PV or use power from the grid or at the same time from the two sources, the detailed situation is based on the PV power output range and your general load’s power demands differences.
g) Battery Grid On
The inverter is working on the grid with no PV power input, and there is sufficient energy stored in the battery, the inverter is discharging the battery and exporting the power via AC grid connection to your system.
h) PV+Battery Grid On
The inverter is working normally on-grid with limited PV power input and the battery energy is sufficient, at this inverter working status the limited PV power is used together with the battery discharging power to export or feed in via the AC grid connection.
I) AC Charge
The inverter is working normally on-grid with no PV input power, and is using the AC power from the grid to charge the battery as configured previously (the function should be enabled firstly as Chapter Inverter Settings – h) AC Charge Settings described).
j) PV+AC Charge
The inverter is working normally on-grid with limited PV input power, and the batter SOC is not sufficient, if at this time the inverter is configured to charge the battery with both PV power and AC grid power, then the inverter will run in this status.
k) Battery Grid Off
The inverter is working normally off-grid with no PV input power, and the battery SOC is sufficient. When the inverter works at this status, the battery is discharging to output power via the UPS connection.
l) PV Battery Grid Off
The inverter is working normally off-grid with limited PV input power, and the battery SOC is sufficient.
When the inverter works at this status, the battery is discharging together with the PV power to output via the UPS connection.
m) PV Charge Grid Off
The inverter is working normally off-grid with sufficient PV input power, and the battery SOC is insufficient. Wen inverter works at this status, the inverter is charging the battery using PV power and there is excessive power rested to output via the UPS connection.

Parameter Explanation of LCD Displays

Parameters of Power:

Ppv: PV input power Pac: active power of AC output
Sac: apparent power of AC output Po: active power of UPS
So: The apparent power of UPS Pc: Charging power
Pd: discharging power PhotoGrid: active power of exporting / feed-

in to grid

Parameters of Voltage and Frequency etc.

Vb: battery voltage Vo: UPS voltage
Vbus: voltage of DC bus Vg: grid voltage
F: frequency SOC: state of charge

Parameters of Energy:

Einvday: energy output via AC output today| Einvall: total energy output via AC output
---|---
Ecday: charged energy  today| Ecall: total charged energy
Edday: discharged energy today| Edall: total discharged energy
Eoday: UPS output energy today| Eoall: total UPS output energy
Epv1day: energy generated today of PV array 1| Epv2day: energy generated today of PV array 2
Epv1all: total energy generated of PV array 1| Epv2all: total energy generated of PV array 2
Erecday: AC charge energy of today| Erecall: total AC charge energy
EtoUday: energy consumed by loads today| EtoUall: total energy consumed by loads
EtoGday: feed-in energy today| EtoGall: total feed-in energy

4.2.3 LCD Settings
4.2.3.1 Information Searching
Refer to the below flow chart which shows the information option interfaces and interconnection.
The operator can search for target information by following the below directions.

a. Enter into Display Manu Interface
Touch the Return button to enter the Display Menu interface, search and select corresponding information options using the Up and Down button, relevant information will be immediately displayed on the LCD screen after touching Enter button to confirm the selection.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - LCD

B. Search History Information

In the Display Menu interface, select the History menu and touch Enter button to enter the History menu interface and use the Up and Down button to select the relevant display menu, and touch Enter button to view detailed historical information.

C. Search Product Information

In the Display Menu interface, select Product Info. menu and touch Enter button to enter the Product Info. the menu interfaces to view detailed product information.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Search
Product

d. Search Measured information

In the Display Menu interface, select Measured Info. menu and touch Enter button to enter in the Measured Info. the menu interfaces to view detailed running information of the system, such as PV, battery, grid, and UPS data.

4.2.3.2 Settings Guidance

a) Enter Into Setting Interface
Touch the Return button to enter into the Display Menu interface, search and select the Setting menu using the UP and Down button, and then touch Enter button to confirm and enter into the inverter setting interface.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - touch
Enter

b) Language Setting

LUXPOWER LXP Series LXP 3K Hybrid Inverter - language
setting

c) Communication Address setting

Notice that the setting range of the RS485 communication address is from 000 to 255, and it’s set to be 001 by default when manufactured.
Operating Guidance: by touching Enter button to select the numerical digits of the COM address – hundreds, tens, and units, and use the UP and Down button to set the number of selected numerical digits.

d) Battery Setting

In the Setting interface, search and select the Set Battery menu and touch Enter button to confirm and enter into the battery setting interface. Set the battery parameters and configuration follow the direction in the below flow chart. Notice that the LXP Hybrid series energy storage inverter supports Lithium-ion and Lead-Acid type batteries. Operating Guidance: by touching Enter button to select the options and use the Up and Down button to set the parameter or number of selected options.

e) Time Setting

In the Setting interface, search and select the Set Time menu then enter into the time setting interface. Follow the direction in the below flow chart to set the time parameters.
Operating Guidance: by touching Enter button to select the numerical digits of the time – year, month, date, hour, and minute, and use the Up and Down button to set the number of selected numerical digits.

f) PV Input Setting

Operating Guidance: by touching the Up and Down buttons to select the parameter of the PV input. Notice that the PV input parameters must be set in accordance to actually the configuration of the PV system. The parameter is set to Two PV separate by default.

g) UPS Setting

h)AC Charging setting

In the Setting interface, search and select the Set AC Charge menu and enter into the AC charge setting interface. Follow the directions in below flow charge to enable or disable the AC charge function, if enabled then configure relevant parameters.

I) Feed-in grill setting

Since in some countries, users can not feed energy into the grid, so they are able to disable the energy export function in the LCD or set the power percent which can feed into the grid.

J) EOD Setting
Users are able to set the end of discharge (stop discharging) battery le vel when there is a grid. This setting is important for some areas that always have load sheddings.

K) CT or Metar setting

Since the inverter supports the connection of both CT clamp and meter, users can select if the system is connecting a meter or a CT clamp and the n chooses the CT clamp ratio when connecting a CT clamp.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Meter
setting

I) Micro-Grid Setting
When connecting the generator to the inverter AC terminal, users need to enable the microgrid function so the inverter will use the generator to charge the battery and will not export any power by the AC terminal.

m) Chose master or slave for a parallel system
For a parallel system, users need to set one inverter to master and others to slave. If the system is a single-phase, then users need to choose 1 phase master, if the system is three-phase, then users need to choose a 3 phase master.

n) Parasys phase setting
For a parallel system, the inverter is able to detect the phase auto if there is three-phase grid input. If the application is a pure off-grid three- phase application, users need to set the phase output for each inverter. For the master, it is considered the phase.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Phase
setting

4.3 Monitor System
Users can use wifi dongle/WLAN dongle/4G dongle(Available from 2021 March for some countries) to monitor the energy storage system, The monitor website is: server.luxpowertek.com
The APP is also available in the google play and apple APP stores (Scan two code bars to download the APP).
Please download the introduction of guidance by the website: https://www.luxpowertek.com/download/

Document Reference:

  1. Quick guidance for setting a password for wifi module the paper is also available in the wifi box
  2. Wifi Quick Guidance, and Monitor system setup for Distributors Monitor system setup for end users Monitor system registration wifi password setting and wifi local monitor and setting,
  3. Lux_Monitor_UI_Introduction. Introduction of monitor interface
  4. WebsiteSettingGuidance. Introduction of website settings for hybrid inverter

4.4 Work with Gen-set
All lux units can work with a generator.
Users can connect the generator output to the inverter Grid terminal. If you have both grid and generator as AC input, we need an external ATS to switch between grid and generator.
Please purchase an external control box to remote turn on/off the generator(which supports the dry contact function).
The generator will be automatically started when battery voltage is lower than the cut-off value or there is a charge request from BMS. When voltage is higher than the AC charge setting value, it will stop the generator
You should enable the ‘Micro-grid’ function via the APP or Web page while you connect the generator to the
Lux unit. The battery will get charged when the generator is turned on, and the generator is bypassed to take all loads in AC and UPS terminal.

LUXPOWER LXP Series LXP 3K Hybrid Inverter - Generator

4.5 Parallel system setup guidance
Please note that the parallel model is different from the standard model, if users need to connect the UPS together, they need to buy a parallel model from distributors.
For parallel system setup,
Step1. Cable connection: the system connection for single-phase paralleling is as below: the system connection for three-phase paralleling is as below:

Please put the CAN communication PIN on status for the first and the end inverter

Step2. Setup the monitor for the system, and add all catalogs in one station. Users can log in the visit the monitor system, Configuration->station->Plant Management-> add datalog to add the data logs.

Step3. Setup Master and Slave for Parallel system. There should be only one master in the system. Set one inverter as master and the others as slave

Step4. Enable share battery for the system if the system share one battery bank, otherwise disable the shared battery function.
Step5. Set the system as a parallel group in the monitor system.

For more detailed guidance for the paralleling system, please visit And download the guidance https://www.luxpowertek.com/download/

Startup and shut down the inverter

5.1 start up the inverter

Step1. Turn on the battery breaker, then turn on the “EPS Output” switch and check if the inverter works in battery back-up mode.
Step2. Make sure the PV voltage of the strings is higher than 120V, and check if the inverter works in PV charge or PV back-up mode.
Step3. Make sure step1and 2 above work properly before turning the grid power or generator, and check if the inverter can go to bypass mode and on- grid mode normally.

5.2 Shut down the inverter

Danger: Do not disconnect the battery, PV, and AC input power under load.
If there is an emergency issue, and you have to shut down the inverter, please follow the steps as below,
Step1. Cut off AC input breaker of inverter side
Step2. Cut off the breaker of the load side
Step3. Cut off the PV breaker and then cut off the battery, and wait for the LCD to go off.
Step4. Turn off the “Power” switch on the inverter if needed.

Troubleshooting & Maintenance

6.1 Troubleshooting

When faults and errors occurred, please deal with these problems following the below procedures and requirements.
6.1.1 Introduction to LED Displays

LED| Display| Description|

Suggestion

---|---|---|---
Green LED| Long light | Working normally|
Flashing| Firmware upgrading| Wait till upgrading complete
Yellow LED| Long light| Warning, inverter working| Need troubleshooting
Red LED| Long light| Fault, inverter stop work| Need troubleshooting

6.1.2 Maintenance
Every segment of the system needs to be checked monthly/quarterly/yearly according to the detailed requirements of each segment.

Inverter Maintenance
a) Check the inverter every 6 months or 1 year to verify if there are damages to cables, accessories, terminals, and the inverter itself.
b) Check the inverter every 6 months to verify if the operating parameter is normal and if there is no abnormal heating or noise from the inverter.
c) Check the inverter every 6 months to confirm there is nothing that covers the inverter heat sink, if there is, shut down the inverter and clear the heat sink.

Battery Maintenance
As per different types of batteries, the original manufacturer’s requirements on maintenance, when you carried out these works on batteries, please make sure to fully shut down the inverter for safety considerations.

6.1.3 Troubleshooting Based On LCD Displays
Once there are any warnings or faults occurred, the LED and LCD will display information to remind the operator, and the LCD will display a relevant error code and a short description.

Code

| Description| LCD Display|

Troubleshooting

---|---|---|---
£000| Internal communication fault 1| E000| Restart the inverter, if the error still exists, please contact us
E001| Model fault 1| E001| Check the parallel CAN cables between inverters, and balance resistor is in the right place
£008| Parallel CAN fault| E008| Reset the model, check if the safety of the standard switch is in the right place
E009| Master loss| E009| 1. Check the parallel CAN cables between master to slaves. and the balance resistor is in the right place
2. Check if the parallel system lacks a master inverter, and reconfigure a master.
E010| Multiple masters| E010| 1. Check if the parallel system has two masters at less.
2. Only allow one master, to reconfigure the others into slaves.
E011| Parallel AC inconsistent| E011| Check the AC connection between parallel inverters
E012| UPS short circuit| E012| 1. Check UPS 1_, N connection
2. Disconnect the UPS connector, if the error still exists, contact us.
E013| UPS power reversed| E013| Restart the inverter, if the error still exists, contact us.
E015| Parallel phase abnormal| E015| Check the AC connection between the triphase parallel system
E016| Relay fault| E016| Restart the inverter, if the error still exists, please contact us.
E017| Internal communication
fault 2| E017| Restart the inverter, if the error still exists, please contact us
E018| Internal communication
fault 3| E018| Restart the inverter, if the error still exists, please contact us
E019| Bus voltage high| E019| Wait for the inverter automatically restart complete, if this error repeats several times, please contact us
E020| UPS connection fault| E020| Check UPS and AC connections
E021| PV voltage high| E021| Check PV input connection and If PV voltage is in range
E022| Overcurrent| E022| Restart the inverter, if the error still exists, please contact us
E023| Neutral fault| E023| Check neutral connection
E024| Both PV short circuit| E024| Disconnect both PV connections, if the error still exists, contact us
E025| Temperature over range| E025| Check NTC Connection
E026| Internal fault| E026| Restart the inverter, if the error still exists, please contact us
E027| Sampling inconsistent between main and slave CPU| E027| Restart the inverter, if the error still exists, please contact us
E031| Internal communication fault 4| E031| Restart the inverter, if the error still exists, please contact us
W000| Communication failure with the battery| Bat Com Fault| Check if the communication cable is right and have chosen the right battery brand, if the warning still exists, contact us
W003| Communication failure with meter| Meter Com Fault| Fix the communication cable, if the warning still exists, contact us
W004| Battery failure| Battery failure| Restart the battery, if the warning still exists, please contact us and the battery manufacture
W005| Auto Test failure| Auto Test failure| Restart the inverter, if the warning still exists, please contact us
W016| No AC connection| No AC Connection| Check AC connection
W017| AC voltage out of range| AC V Outrange| Check AC grid voltage
W018| AC frequency out of range| AC F Outrange| Check AC grid frequency
W020| PV isolation low| PV Isolation low| Restart the inverter, if the error still exist, please contact us
W021| Leakage current high| Leakage I high| Restart the inverter, if the error still exists, please contact us
W022| DC injection high| DC Injection high| Restart the inverter, if the error still exists, please contact us
W023| PV short circuit| PV short| Check and fix PV input connection
W025| Battery voltage high| Bat Volt High| Check and fix battery connection
W026| Battery voltage low| Bat Volt Low| Check and fix battery connection
W027| Battery open circuit| Bat open| Check and fix battery connection
W028| UPS overload| UPS Over Load| Check and adjust UPS load
W030| Meter connection reversed| Meter Reversed| Check and fix meter connection
Solar Input| 3K Hybrid| 3.6K Hybrid| 4K Hybrid| 4.6K/5K Hybrid| 6K/Hybrid
---|---|---|---|---|---
Max. DC Input Power| 6600W| 7000W| 7000W| 8000W| 8000W
Nominal DC Input Voltage| 360Vd.c| 360V.d.c| 360V.d.c| 360V.d.c| 360V.d.c
DC Input Voltage Range| 100 – 550V.d.c| 100 – 550V.d.c| 100 – 550V.d.c| 100 – 550V.d.c| 100 – 550V.d.c
MPPT Voltage Range| 120 – 500V.d.c| 120 – 500V.d.c| 120 – 500V.d.c| 120 – 500V.d.c| 120 – 500V.d.c
Start-up Voltage| I 40V.d.c| 140V.d.c| 140V.d.c| 140V.d.c| 140V.d.c
MPPT Number| 2| 2| 2| 2| 2
Max. DC Input Current| 12.5A/I 2.5A| 12.5A/I2.5A| 12.5A/I2.5A| 12.5A/I2.5A| 12.5A/12.5A
Max. Short-circuit Current| 13.7A/I 3.7A| 13.7A/1 3.7A| 13.7A/1 3.7A| 13.7A/ 13.7A| 13.7A/ 13.7A
Max. Input Power per MPPT| 3600W/3600W| 4000W/4000W| 4000W/4000W| 4000W/4000W| 4000W/4000W
Max. Feedback Current to Array| 0/0 A| 0/0 A| 0/0 A| 0/0 A| 0/0 A

Battery Output

Compatible Battery Type| Lithium-ion/Lead-Acid| Lithium-ion/Lead- Acid| Lithium-ion/Lead-Acid| Lithium-ion/Lead-Acid| Lithium-ion /Lead-Acid
---|---|---|---|---|---
Nominal Battery Voltage| 48V.d.c| 48V.d.c| 48V.d.c| 48V.d.c| 48V.d.c
Battery Voltage Range| 40 – 60V.d.c| 40 – 60V.d.c| 40 – 60V.d.c| 40 – 60V.d.c| 40 – 60V.d.c
Max. Charge/Discharge Current| 66A/66A| 80A/80A| 80A/80A| 80A/80A| 80A/80A
Max. Charge/Discharge Power| 3600W/3600W| 3600W/3600W| 3600W/3600W| 3600W/3600W| 4000W/4000W
Charging Curve| 3 stages| 3 stages| 3 stages| 3 stages| 3 stages
Max. Charge Voltage| 59V| 59V| 59V| 59V| 59V
DOD(Lithium-ion/Lead-Acid)| 8096/50%| 80%/50%| 80%/50%| 80%/50%| 80%/S0%
Capacity of Battery| 2-20kWh| 2-20kWh| 2-20kWh| 2-20kWh| 2-20kWh

Ac Output

Nominal AC Output Power| 3000W| 3600W| 4000W| 4600W/5000W| 6000W
---|---|---|---|---|---
Max. AC Output Power| 3000VA| 3600VA| 4000VA| 4600VA/5000VA| 6000VA
Max. AC Output Current| I 5A| 16A| 20A| 25A| 26A
Nominal AC Voltage| 230V.a.c| 230V.a.c| 230V.a.c| 230V.a.c| 230V.a.c
AC Voltage Range| 180 – 270V.a.c| 180 – 270V.a.c| 180 – 270V.a.c| 180 – 270V.a.c| 180 – 270V.a.c
Nominal AC Frequency| 50Hz /60Hz| 50Hz /60Hz| 50Hz / 60Hz| 50Hz /60Hz| 50Hz / 60Hz
AC Frequency Range| 45 – 55Hz /55 – 65Hz| 45 – 55Hz /55 – 65Hz| 45 – 55Hz / 55 – 65Hz| 45 – 55Hz / 55 – 65Hz| 45 – 55Hz/55 – 65Hz
| Adjustable 0.8 overexcited to| Adjustable 0.8 overexcited to| Adjustable 0.8 overexcited to| Adjustable 0.8 overexcited to| Adjustable 0.8 overexcited to
Power Factor| 0.8 under excited| 0.8 under excited| 0.8 under excited| 0.8 under excited| 0.8 under excited
THDI| <3%| <3%| <3%| <3%| <3%
Inrush Current| 10A/1 Ous| I OA/1 Ous| 10A/1 Ous| I OA/I Ous| I 0A/10us
Max. Output Fault Current| 50A/20us| 50A/20us| 50A/20us| 50A/20us| 50A/20us
Max. Output Over-Current Protect| 15A| 20A| 20A| 25A| 26A

UPS Output – with Battery

UPS Max. Output Power without Solar| 3600W| 3600W| 3600W| 3600W| 4000W
---|---|---|---|---|---
UPS Max. Output Power with Solar| 5000W| 5000W| 5000W| 5000W| 6000W
UPS Nominal Output Voltage| 230V.a.c| 230V.a.c| 230V.a.c| 230V.a.c| 230V.a.c
UPS Nominal Output Frequency| 50Hz / 60Hz| 50Hz / 60Hz| 50Hz / 60Hz| 50Hz / 60Hz| 50Hz / 60Hz
UPS Nominal Output Current| I 3A| I 3A| I 3A| I 3A| I 7.4A
Peak Power| 4500W, the 30s| 4500W, the 30s| 4500W, the 30s| 4500W, the 30s| 4500W, the 30s
THDV| <5%| <5%| <5%| <5%| <5%
Switching Time| <0.0k| <0.0 Is| <0.0k| <0.01| <0.0 k

Efficiency

Europe Efficiency 97.5% 97.5% 97.5% 97.5% 97.5%
Max. Efficiency 97.9% 97.9% 97.9% 97.9% 97.9%
Battery Charge/Discharge Efficiency 94.5% 94.5% 94.5% 94.5% 94.5%

Protection

Reverse Polarity Protection Yes Yes Yes Yes Yes
Over CurrentNoltage Protection Yes Yes Yes Yes Yes
Anti-islanding Protection Yes Yes Yes Yes Yes
AC Short-circuit Protection Yes Yes Yes Yes Yes
Leakage Current Protection Yes Yes Yes Yes Yes
Ground Fault Monitoring Yes Yes Yes Yes Yes
Grid Monitoring Yes Yes Yes Yes Yes
Ingress Protect Degree IP65 / NEMA4X IP65 /NEMA4X IP65 / NEMA4X I P65
/NEMA4X IP65 / NEMA4X
DC Switch Yes Yes Yes Yes Yes

General Data

Dimensions (W/H/D)| 451/469(551)/184| 451/469(551)/184| 451/469(551)/184| 451/469(551)/184| 451/469(551)/184
---|---|---|---|---|---
Weight| 20 kg| 20 kg| 20 kg| 20 kg| 20 kg
Topology| Transformerless (scar), HF (Battery)| | Transformerless (solar), HF (Battery) Tr-formless (solar), HF (Battery)| |
Cooling Concept| Natural Convection| Natural Convection| Natural Convection| Natural Convection| Natural Convection
Relatively Humidity| 0- 100%| 0-100%| 0-100%| 0- 100%| 0-100%
Operating Temperature Range| -25 – 60 °C| -25 – 60 °C| -25 – 60 °C| -25 – 60 °C| -25 – 60 °C
Altitude| <2000m| <2000m| <2000m| <2000m| <2000m
Noise Emission| <25dB| <25dB| <25dB| <25dB| <25dB
Standby Consumption| <5W| <5W| <5W| <5W| <5W
Display& Communication Interface,| LCD, LED, RS4| 35, Wi-Fi, CAN| LCD, LED, RS485,| Wi-Fi, CAN| CD, LED, RS485, Wi-Fi, CAN
Solar Input| LXP4K HB| LXP5K HB| LXP6K HB
---|---|---|---
Max. DC Input Power| 7000W| 8000W| 8000W
Nominal DC Input Voltage| 360V.d.c| 360V.d.c| 360V.d.c
DC Input Voltage Range| 100 – 550V.d.c| 100 – 550V.d.c| 100 – 550V.d.c
MPPT Voltage Range| 120 – 500V.d.c| 120 – 500V.d.c| 120 – 500V.d.c
Start-up Voltage| 140V.d.c| 140V.d.c| 140V.d.c
MPPT Number| 2| 2| 2
Max. DC Input Current| 12.5A/I2.5A| 12.5A/I2.5A| 12.5A/I2.5A

Battery Input/Output

Compatible Battery Type| Lithium-ion/Lead-Acid| Lithium-ion/Lead-Acid| Lithium-ion/Lead-Acid
---|---|---|---
Nominal Battery Voltage| 250V.d.c| 250V.d.c| 250V.d.c
Battery Voltage Range| 90 – 450V.d.c| 90 – 450V.d.c| 90 – 450V.d.c
Max. Charge/Discharge Current| 20A/20A| 20A/20A| 25A/25A
Max. Charge/Discharge Power| 4000W/4000W| 5000W/5000W| 6000W/6000W
Charging Curve| 3-stages| 3-stages| 3-stages

AC Input/Output

Nominal AC Output Power 4000W 5000W 6000W
Nominal AC Output Current 17.5A 2I.7A 26A
Max. AC Output Current 22A 27A 30A
Nominal AC Voltage 230V 230V 230V
Optional AC Voltage Range I 80-270Vac I 80-270Vac I 80— 270Vac
Nominal AC Frequency SOHC/60Hz 50Hz/60Hz 50Hz/60Hz
AC Frequency Range 45-55Hz/55-65Hz 45-55Hz/55-65Hz 45-55Hz/55-65Hz
Power Factor > 0.99@rated power 0.8lagging-0.8 leading Adjustable
THDI <3% <3% <3%

UPS Output – with Battery

UPS Nominal Power 4000W 5000W 6000W
UPS Nominal Voltage 230Vac 230Vac 230Vac
UPS Nominal Frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz
UPS Nominal Current 17.5A 2I.7A 26A
Peak Power 5000W, the 30s 6200W, the 30s 6900W, the 30s
THDV <3%@R-load <3%@R-load <3%@R-load
Switching Time Typical 0.0 Is Typical 0.01 s Typical 0.0 I s

Efficiency

Europe Efficiency 97.% 96.% 96.%
Max. Efficiency 98.% 98.% 98.%
Max. Charge/Discharge Efficiency 97%/ 96.6% 97%/ 96.6% 97%/ 96.6%

Protection

Reverse Polarity Protection Yes Yes Yes
Over Voltage, Over Current Yes Yes Yes
Anti-islanding Protection Yes Yes Yes
AC Short-circuit Protection Yes Yes Yes
Leakage Current Protection Yes Yes Yes
Ground Fault Monitoring Yes Yes Yes
Grid Monitoring Yes Yes Yes
Ingress Protect Degree IP65 / NEMA4X IP65 / NEMA4X IP65 / NEMA4X
DC Switch Integrated Integrated Integrated

General Data

Dimensions (W/H/D) 455 /476(565)/181 455 /476(565) / 181 455 /476(565) /181
Weight 20 kg 20 kg 20 kg
Topology Transformerless Transformerless Transformerless
Cooling Concept Natural Convection Natural Convection Natural Convection
Relatively Humidity 0-100% 0- I 00% 0-100%
Operating Temperature Range -25 – 60 °C -25 – 60 °C -25 – 60 °C
Altitude <2000m <2000m <2000m
Noise Emission <25dB <25dB <25dB
Standby Consumption < I OW < IOW < IOW
Display/Communication Interface LCD/ LED/R5485/ Wi-Fi/ CAN LCD/ LED/RS485
/Wi-Fi/ CAN LCD/ LED/RS485/ Wi-Fi/ CAN

Certification & Approvals
CEI 0-21 IEC62109-1-2, IEC62040, EN6 1 000-6-1, EN6 1 000-6-2, EN6I000-6-3