LUXPOWER SNA-US 6000 ECO Hybrid Inverter User Manual
- June 12, 2024
- LUXPOWER
Table of Contents
USER MANUAL
ECO Hybrid Inverter
SNA-US 6000 Where sun shined Power always on
Information on this Manual
Validity
This manual is valid for the following devices:SNA-US 6000
Scope
This manual provides the installation, operation and troubleshooting of this
unit, please read this manual carefully before installations and operations.
Target Group
For qualified persons and end users. Qualified persons and end users must have
the following skills:
- Knowledge about this unit operation
- Training in deal with the security issues associated with installations and electrical safety
- Training in the installation and commissioning of electrical devices and installations
- Knowledge of the applicable local standards and directives
Safety Instructions
WARNING: This chapter contains important safety and operating instructions. Read and keep this manual for future reference.
- All the operation and connection need to be operated by qualified persons.
- Before using the unit, read all instructions and cautionary marking on the unit. Any damage caused by inappropriate operation is not warranted by Lux power .
- All the electrical installation must comply with the local electrical safety standards.
- Do not disassemble the unit. Take it to a qualified service center when service or repair is required, incorrect re-assembly may result in a risk of electric shock or fire. Do not open inverter cover or change any components without Luxpower’s authorization, otherwise the warranty commitment for the inverter will be invalid.
- To reduce risk of electric shock, disconnect all wirings before attempting any maintenance or cleaning, turning off the unit will not reduce this risk.
- CAUTION-To reduce risk of injury, charge only deep-cycle lead-acid type rechargeable batteries and lithium batteries, other types of batteries may burst, causing personal injury and damage.
- NEVER charge a frozen battery.
- For optimum operation of this unit, please follow required spec to select appropriate cable size and breaker.
- Please strictly follow installation procedure when you want to disconnect AC or DC terminals, please refer to INSTALLATION section of this manual for the details.
- GROUNDING INSTRUCTIONS -This unit should be connected to a permanent grounded wiring system, be sure to comply with local requirements and regulation to install this inverter.
- NEVER cause AC output and DC input short circuited. Do not connect to the mains when DC input short circuits.
Brief Introduction
1.1 Features of the inverter
SONAR series is a multifunctional, high frequency pure sine wave ECO Hybrid inverter solar inverter, features:
- Applicable for pure off grid inverter/ backup power / self-consumption / on grid situation
- Integrated with 2 MPPT solar charge controllers, MPPT ranges 120V~385V
- Rated power 6KW, power factor 1
- Be able to run with or without battery in ongrid and offgrid mode
- With separated generator input interface, able to control generator remotely
- Solar and utility grid can power loads at the same time
- With integrated advanced parallel function, up to 16pcs max paralleling
- Support CAN/RS485 for Li-ion battery BMS communication
- WIFI/ GPRS remote monitoring , setting and firmware update, support website, free IOS/Android APP
1.2 Interface of the inverter
1.3 Packing List
Before installation, please inspect the unit. Be sure that nothing inside the
package is damaged.
You should have received the following items in the package:
Storing the Inverter
The inverter must be stored appropriately if not installed immediately, refer
to below figure.
CAUTION !
a) The inverter and its components must be stored in its original packaging.
b) The storage temperature should be within -25~60 and humidity within 0~85%.
c) The packing should be upright and maximum stacked layers is 6 .
d) Do not directly exposed the inverter and its packaging to sunshine,
raindrops and keep away from corrosion.
Installation
2.1 Preparation
The system connection is as below:
Please prepare the breakers and cables in advanced before installation.
- Battery connection: For safety operation and regulation compliance, it’s requested to install a separate DC over-current protector or disconnect device between battery and inverter. The recommend battery capacity is 200AH-400AH, the recommended spec of DC breaker is 200A/60V. Recommended battery cable and terminal size:
Model| Maximum Amperage| Battery capacity| Wire Size| Ring Terminal| Torque value|
---|---|---|---|---|---|---
Cable mm2| Dimensions
D (mm)| L (mm)
SNA-US6000| 140A| 200AH| 12AWG| 38| 6.4| 39.2| 8 Nm
26AWG| 28| 6.4| 33.2 - AC connection: Please install a separate AC breaker between inverter and AC input power source, inverter and AC output load. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 63A. Recommended AC input/ AC output /GEN cable size for each inverter.
Model| Gauge| Cable (mm2)| Torque Value
---|---|---|---
SNA-US6000| AC INPUT(GRDI side)| 8AWG| 6| 2.0 Nm
AC OUTPUT(EPS side)| 10AWG| 6| 2.0 Nm
GEN INPUT(GEN side)| 10AWG| 6| 2.0 Nm - PV Connection: Please install separately a DC circuit breaker between inverter and PV modules. The recommended of DC breaker is 600V/25A. It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below:
Model| Gauge| Cable (mm2)
---|---|---
SNA-US6000| 1x10AWG| 4 - Before connecting all wiring, please take off bottom cover by removing 3 screws as shown below.
2.2 Mounting the Unit
Consider the following points before selecting where to install:
Notice:
- Mount on a solid surface
- Do not mount the inverter on flammable construction materials.
- For proper air circulation to dissipate heat, allow a clearance of approx. 20 cm to the side and approx. 50 cm above and below the unit.
- The ambient temperature should be between 0°C and 55°C to ensure optimal operation.
- The recommended installation position is to be adhered to the wall vertically.
Steps to mounting the unit
Step1. Use the wall-mounting bracket as the template to mark the position
of the 4 holes, then drill 8 mm
holes and make sure the depth of the holes is deeper than 50mm.
Step2. Install the expansion tubes into the holes and tight them, then
use the expansion screws (packaged
together with the expansion tubes) to install and fix the wall-mounting
bracket on the wall.
Step3. Install the inverter on the wall-mounting bracket and lock the
inverter using the security screws.
2.3 Battery Connection
2.3.1 Battery Power Cable Connection
Note: for lead acid battery, the recommended charge current is 0.2C( C to
battery capacity)
- Please follow below steps to implement battery connection:
- Assemble battery ring terminal based on recommended battery cable and terminal size.
- Connect all battery packs as units requires. It’s suggested to connect at least 200Ah capacity battery for SNA6000 WPV.
- Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2 ~3Nm. Make sure polarity of the battery is correctly connected and ring terminals are tightly screwed to the battery terminals.
2.3.2 Lithium Battery Connection
If choosing lithium battery for SNA6000 WPV, please make sure the battery BMS
is compatible with Lux power inverter. Please check the compatible list in the
Lux power website.
Please follow below steps to implement lithium battery connection:
- Connect power cable between inverter and battery
- Connect the CAN or RS485 communication cable between inverter and battery. If you do not get the communication cable from inverter manufacturer or battery manufacturer, please make the cable according to the PIN definition
- Lithium battery configuration, in order to communicate with battery BMS, you should set the battery type to “Li-ion” in Program “03” by LCD and choose the right battery brand (for details, please check the LCD setting chapter), users can also choose the battery type and brand by monitor system.
2.4 AC Input/Output Connection
CAUTION!!
- There are two terminal blocks with “IN” and “OUT” markings. Please do NOT mis-connect input and output connectors.
- Be sure to connect AC wires with correct polarity. If L and N wires are connected reversely, it may cause utility short-circuited when these inverters are worked in parallel operation.
Please follow below steps to implement AC input/output connection:
- Before making AC input/output connection, be sure to open DC protector or disconnected first.
- Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3 mm.
- Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screwsBe sure to connect PE protective conductor first.
- Insert AC output wires according to polarities indicated on terminal block and tighten terminal screws. Be sure to connect PE protective conductor first.
- Make sure the wires are securely connected.
L1→LINE (red)
L2→LINE (black)
N→ Neutral (blue)
PE→ Ground(yellow-rgin)
2.5 PV Connection
Please follow below steps to implement PV module connection:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Check correct polarity of connection cable from PV modules and PV input connectors.
- Connect positive pole (+) of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection cable to negative pole (-) of PV input connector.
- Make sure the wires are securely connected.
- Finally, after connecting all wiring, please put bottom cover back by screwing two screws as shown below.
2.6 Generator Connection
L1→LINE (red) L2→LINE (black) N→ Neutral (blue)
- Before making Generator connection, be sure to open DC protector or disconnected first.
- Remove insulation sleeve 10mm for 2 conductors.
- Insert L1/L2 and N wires according to polarities indicated on terminal block and tighten the terminal screws
All lux units can work with generator.
- Users can connect the generator output to ECO Hybrid inverters. GEN input terminal.
- The generator will be automatically started when battery voltage is lower than the cut-off value or there is charge request from BMS. When voltage is higher than AC charge setting value, it will stop the generator
- Battery will get charged when the generator is turned on, and the generator is bypassed to AC output to take all loads.
- The system will use AC first if there is both utility input and generator input.
The capacity of the generator is recommendedNumber of the single parallel inverter| Capacity
---|---
Single inverter| >10KW
2 parallel| >15KW
It is supported to parallel 2~3 PCS inverter with single phase in single phase
parallel system and three phase parallel system to charge battery with
Generator! And it is depends on the load performance of the generator too.
2.7 Dry Contact Signal control
The Dry port(NO2,COM2) could be used to deliver signal to external device when
battery voltage reaches warning level. The GEN port(NO1,COM1,) could be used
to wake-up the Generator and then the generator can charge the battery.
Unit Status| Condition| |
---|---|---|---
NO2 & COM2| NO1 & COM1
Power Off| Inverter is off and no output is powered.| Open| Open
Power On| Without Grid| Battery voltage < Low DC warning voltage| Close| Close
Battery voltage > Setting value or battery charging reaches floating stage|
Open| Open
With Grid| Battery voltage < Low DC warning voltage| Close| Open
Battery voltage > Setting value or battery charging reaches floating stage|
Open| Open
Notice: NO—Normal open
Dry Port Relay Maximum Specification: 250VAC 5A
Gen Port Relay Maximum Specification: 250VAC 5A
2.8 Parallel function
SNA series inverter support up to 16 units to composed single phase parallel
system or three phase parallel system, for parallel system setup
Step1. Cable connection: the system connection is as below:
Step2. Please put the CAN communication PIN to on status for the first and the end inverter
Step3. Setup the monitor for the system, add all data logs in one station. Users can login to the visit interface of monitor system, Configuration->station->Plant Management->add data log to add the data logs.
Step4. Enable share battery for the system if the system share one
battery bank, otherwise disable the shared battery function
Step5. Set the system as a parallel group in the monitor system
For more detailed guidance for paralleling system, please visit
https://www.luxpowertek.com/download/
And download the guidance
2.9 Power and EPS ON/OFF
- Power Switch: Control power supply for the unit
- EPS Output Switch: Use to control the AC output
After connection, please turn on both switch. Users can turn off the EPS
output switch to turn off power supply in some emergency case
2.10 Rapid Shutdown system Installation (RSD Transmitter)
Working modes
3.1 ECO Hybrid inverter modes introduction:
Bypass Mode | AC is used to take the load | |
---|---|---|
PV Charge Bypass | PV charge the battery while the AC power the load | |
BAT Grid off | Battery is used to take the load | |
PV+BAT Grid off | PV+ Battery power the load together | |
PV Charge | 1. When the EPS key off, the inverter charge the battery only |
2. When the battery is power off, the PV can wake up the battery
automatically
PV Charge+ Grid off| | PV charge the battery and power the load
AC Charge| | 1. AC charge the battery from AC Input or GEN Input
2. When the battery is power off, the AC can wake up the battery
automatically
---|---|---
PV+AC charge| | PV+AC charge the battery
AC is from AC Input or GEN Input
PV Grid off| | NOTE: The output power depends on the PV energy input, if
the PV energy is unstable, witch will influence the output power
When setting without battery, the PV can power the load .
3.2 Working Modes related setting description
Situation| Setting 1| Setting 2| Work ing modes and
Description
---|---|---|---
AC abnormal| NA| NA| off grid inverter mode
if P Solar >=P load, solar is used to take load and charge battery if P_
Solar <P load, solar and battery take the load together, system will
discharge until battery lower than the Cut Off Voltage/SOC
AC normal| In the AC first time| NA| Bypass Mode
AC will take the bad and Solar is used to c ha me battery
Enable AC charge and in the AC charge time| AC charge according to Time|
Bypass Mode AC charge battery Solar is used to c ha rge battery
AC will take load a11:1 a ko charge battery during AC c ha ige time if solar
power is not enough
AC charge according to SOC/Battery voltage| Bypass Mode
AC charge battery
Solar is used to c ha rge battery
AC will take load and also charge battery w he n battery SOCNobge is lowe r t
han start SOCNoltage. and the AC will stop charging who nth* battery
Voltage/SOC is higher than AC end c ha rge battery village/SOC
1. Not in the AC first time and
2. Disable AC charge or not in the AC charge time| NA| off grid inverter mode
if P Solar>=P_ load, solar is used to take load and charge battery if
PSolar<P load, solar and battery take the load together, system will
discharge until battery lower than EOD Voltage/SOC
- SONAP can working as a traditional off grid inverter. In this situation, inverter either use (solar+ battery) to take load or use AC take load. Related settingsAC First: During the setting time, system will use AC to take load first, use solar power to charge the battery.
If the battery is full, solar power may be wasted. When out of the setting time, system will use battery and solar to take load until battery voltage/SOC is lower than cut off voltage/SOC2. AC Charge function Disable: The system will not use AC to charge the battery(except Li ion BMS set force charge flag )
According to Time: During the setting time, system will use AC to charge the battery until battery full and battery will not discharge during the setting time.
According to Battery Voltage: During the setting time, system will use AC to charge the battery if battery voltage is lower than AC Charge Start Battery Voltage and will stop when Voltage is higher than AC Charge End Battery Voltage. And battery will not discharge during the setting time.
According to Battery SOC: During the setting time, system will use AC to charge the battery if battery SOC is lower than AC Charge Start Battery SOC and will stop when Voltage is higher than AC Charge End Battery SOC. And battery will not discharge during the setting time.
LCD display and settings
4.1 LED Display
LED Indicator | Messages |
---|---|
1 | Green |
Flashing | fast: Warning |
slow: Firmware update
2| Red| Flashing| Fault condition occurs in the inverter
4.2 LCD Display
No. | Description | Remarks |
---|---|---|
1 | Generally Information Display Area | Display the currently time/date by |
default(year/month/day/ hour/minute” switching automatically). When press Up
or Down buttons, this area will display the firmware version information,
serial number etc. Display the setting selection information when entering
settings
2| On-grid solar inverter output power and energy data| This area shows the
data of PV voltage, power and the setting of PV input connection information
3| Battery information and data| This area shows the battery type, battery
brand(lithium battery), the lead-Acid battery setting of CV voltage, Floating
charging voltage, Cut off voltage, Discharge end voltage . And display the
voltage, SOC and power in turns of period of 1 seconds
4| System working status / setting code| There are three type of working
status- normal, warning and fault, in right side of this area, there are code
display, it will display different type of code -the system working mode code,
warning code, fault code and setting code
5| UPS/EPS output information and data| When UPS function is enabled, this
area will display UPS voltage, frequency, power etc. in turns of periods of 1s
6| Programming & the percentage of AC output power| When firmware updating in
process, it will display relevant information When in grid off, this area will
display the Percentage of the maximum AC output power
7| Loads consumption| Display the power consumption by the loads in on grid
model
8| Grid information and Generator information| Display the grid(GRIDA)
information of voltage, frequency, input or output power, the Generator
(GRIDB) information of voltage, frequency, input power ,switch period of 1s
9| Working mode settings area| When make settings on the SNA5000 inverter
through the LCD, this area will display the AC Charge, Charge First option for
setting on those working modes. It will not display those information unless
in the setting process.
4.3 Inverter Status Display
Normal status, running status 40 | Warning Status, warning 29 |
---|---|
Fault status, fault 21 | Flash status: download percent is 33% |
When display ‘GRIDA’, it means the Grid information is about AC utility, The
percent display on the right down corner means the load percentage| When
display ‘GRIDS’, it means the AC information is about Genset input
There are four buttons on the LCD. Step for settings by the display:
Step1: After touch Enter button for about 2 seconds, the unit will enter
setting mode. The setting icon and index will flashing.
Step2: Touch UP or Down button to select setting index from 1 to 19.
Step3: Then touch Enter button to set this item.
Step4: Touch UP or Down button to change the settings.
Step5: Touch Enter to confirm the setting or Return the setting list is
as below
Index| Description| Setting Option
1| Date& time|
2| PV input mode|
---|---|---
3| Battery| Run with No Battery:
Step1: Choose battery type first, when no flashing, select Enter to
choose Run with No battery
For Lead Acid:
Step1: Choose battery type first, when Lead-Acid flashing, select Enter
to choose Lead-acid battery Step2:Then choose battery capacity
For Lithium battery
Step1: Choose battery type first, when Li-ion flashing, select Enter to
choose Li-ion battery Step2:Choose battery brand
0-> Standard Battery
2->Pylon Battery
6->Lux power protocol Battery
8->Dynes Battery
4| UPS Output voltage and frequency|
5| Buzzer enable|
---|---|---
6| Ic: Maximum charge current (utility charge current + solar charge current)|
7| Con Char:
CV voltage setting (Only in Lead-acid battery type)|
8| Flo Char:
Floating charging voltage setting (Only in Lead-acid battery type)|
---|---|---
9| Id: Maximum discharge current|
10| TEOd:
Discharge control type: VOLT/SOC|
11| Cut OFF:
Cut off Voltage or SOC, depend on TEOd|
---|---|---
12| Eod:
Discharge end voltage or sac with grid, depend on TEOd
13| Acing: AC voltage range setting|
14| AC charge setting (The setting process must enable the AC charging
function, confirm the full battery SOC value, and set the confirmation time
period 1, 2, 3 to truly complete the AC charging function setting)|
AC Charge function: Setting range:
1. DIS: AC charge disable; 2.TIM: According to time;
3. VOL: According to battery voltage; 4.SOC: According to battery soc; (Touch
“Enter” button to set ac charge parameter )
---|---|---
AC charge control:
Setting range:
Vol:
1.Start Voltage: 35.4~52V;
2.End Voltage: 48~59V;
SOC:
1.Start Soc: 1~90%;
2.End Soc: 20~100%;
Setting AC Charge time of 1 start:
Range:00:00~23:59
Default:00:00~00:00
Setting AC Charge time of 1 endRange:00:00~23:59
Default:00:00~00:00
Similar to set time2 and times
15| Utility source (AC Input) to take Load time setting|
17| Battery Wakeup Enable/disable (Not for No Battery type)|
18| Max Generator Input Power|
---|---|---
19| PV Off Grid enable/disable|
20| Power Save Function enable/disable|
21| Parallel setting|
---|---|---
22| Error/Alarm Record|
23| CT Offset|
---|---|---
24| Fan speed setting|
25| Generator charge setting|
---|---|---
26| N-PE Connect Function enable/disable|
27| PV Isolation Protection enable/disable|
---|---|---
28| Rapid Shutdown Function enable/disable|
29| AFCI Protection enable/disable|
Monitor System for ECO Hybrid inverter
Users can use wifi dongle / WLAN dongle / 4G dongle (Available from 2021 March
for some countries) to monitor the energy storage system, The monitor website
is: server.luxpowertek.com
The APP is also available in the google play and apple APP store(Scan two code
bar to download the APP).
Please download the introduction of guidance by website:
https://www.luxpowertek.com/download/
Document Reference:
-
Wifi Quick Guidance
Quick guidance for setting password for wifi module, the paper is also available in the wifi box
2.Monitor system setup for Distributors and Monitor system setup for end- users, Monitor system registration, wifi password setting, and wifi local monitor and setting -
Lux Monitor UI_ Introduction
Introduction of monitor interface -
Website Setting Guidance
Introduction of website settings for offered inverter
Specifications
Table 1 Line Mode Specifications
INVERTER MODEL| SNA-US 6000
Input Voltage Waveform| Sinusoidal (utility or generator)
Nominal Input Voltage| 110Vac(P-N),220Vac(P-P)/ 120Vac(P-N),240Vac(P-P)
Ac Start-up Voltage| 45Vac(P-N),90Vac(P-P)
Acceptable Input Voltage Range| 65Vac(P-N)~140Vac(P-N),
130Vac(P-P)~280Vac(P-P)
Low Loss Voltage| 170Vac±7V (UPS); 90Vac±7V (Appliances)
Low Loss Return Voltage| 180Vac±7V (UPS); 100Vac±7V (Appliances)
High Loss Voltage| 280Vac±7V
Max AC Input Current| 45A Per Phase
Max AC Input Voltage| 140Vac(P-N)/280Vac(P-P)
Nominal Input Frequency| 50Hz / 60Hz (Auto detection)
Output Short Circuit Protection| Software protect when GridOff discharge
Circuit Breaker protect when GridOn Bypass
Transfer Time| <20ms @ Single
<30ms @ Parallel
Output power derating:
When AC input voltage drops to 170V, the output power will be derated.| Output
Power Rated Power 20% Power
Charge power derating:
When AC input voltage drops to 170V depending on models, the charge power will
be derated.|
Output power derating:
When AC input voltage drops to 200V, the output power will be derated.| Max
inv current: 30A;
Max inv Power: 3kW(P-N),6KW(P-P);
Table 2 Inverter Mode Specifications
Rated Output Power| 6KVA/6KW
Output Voltage Waveform| Pure Sine Wave
Output Voltage Regulation| 100Vac/110Vac/120Vac±5%(P-N)
200Vac/220Vac/240Vac±5%(P-P)
Output Frequency| 50Hz / 60Hz
---|---
Peak Efficiency| 93%
**** Overload Protection| 5s@≥150% load(P-N,P-P);
10s@110%~150% load(P-N,P-P)
Surge Capacity| 2 rated power within 5 seconds
Battery Voltage Range| 46.4V-60V(Li) 38.4V-60V(Lead Acid)
High DC Cut-off Voltage| 59VDC(Li) 60VDC(Lead Acid)
High DC Recovery Voltage| 57.4VDC(Li) 58VDC(Lead_ Acid)
Low DC Warning Voltage| load < 20%| 44.0Vdc(Settable)
20% ≤ load < 50%| Warning Voltage @load < 20% -1.2V
load ≥ 50%| Warning Voltage @load < 20% -3.6V
Low DC Warning Return Voltage
Low DC Warning Voltage Different load +2V
Low DC Cut-off Voltage| load < 20%| 42.0Vdc(Settable)
20% ≤ load < 50%| Cut-off Voltage @load < 20% -1.2V
load ≥ 50%| Cut-off Voltage @load < 20% -3.6V
Low DC Cut-off Return Voltage| Cut-off Voltage load<20%≥45V| Low DC Cut-off
Voltage @load<20%+3V
Cut-off Voltage load<20%<45V| 48V
Low DC Warning SOC| 20% SOC ( Settable )
Low DC Warning Return SOC| Low DC Warning SOC +10%
Low DC Cut-off SOC| 15% SOC (Grid on) ( settable) 15% SOC (Grid off ) (
settable)
Low DC Cut-off Return SOC| Low DC Cut-off SOC +10%
Charge Cut-off Voltage| 58.4Vdc
No Load Power Consumption| <60W
Table 3 Charge Mode Specifications
Utility Charging Mode|
Lead_Acid Battery Charging Algorithm| 3-Step
Max. AC Charging Current| 60Amp(@VI/P=230Vac)
Bulk Charging Voltage| Flooded Battery| 58.4Vdc
---|---|---
AGM / Gel Battery| 56.4Vdc
Floating Charging Voltage| 54Vdc
MPPT Solar Charging Mode|
Max. PV Array Power| 4000W2
Start-up Voltage| 100Vdc±10Vdc
PV Array MPPT Voltage Range| 120Vdc~385Vdc
Max. PV Array Open Circuit Voltage| 480Vdc
Max. PV Charging Current| 140A
Max. Charging Current
(AC Charger Plus Solar Charger)| 140A
Table 4 General Specifications
INVERTER MODEL| SNA-US 6000
Safety Certification| CE
Operating Temperature Range| 0°C to 50°C
Storage temperature| -15°C~ 60°C
Humidity| 5% to 95% Relative Humidity (Non-condensing)
Altitude| <6561ft
Dimension(DWH)| 2.131.470.49ft
Net Weight| 24Kg
Trouble Shooting & Error List
The failures mainly divided into 5 categories, for each category, the behavior is different:
Code | Description | Trouble shooting |
---|---|---|
E000 | Internal communication fault1 | Restart inverter, if the error still |
exist, contact us (DSP&M3)
E002| Bat On MOs Fail| Restart inverter, if the error still exist, contact us
E003| CT Fail| Restart inverter, if the error still exist, contact us
E008| CAN communication error in Parallel System| Check CAN cable connection
is connected to the right COM port
E009| No master in parallel system| Check parallel setting for master/Slave
part, there should be one master in the system
E012| UPS output short circuit| Check if the load is short circuit, try to
turn off the load and restart inverter
E013| UPS reserve current| Restart inverter, if the error still exist, contact
us
E015| Phase Error in three phase parallel system| Check if the AC connection
is right for three phase system, there should one at least one inverter in
each phase
E016| Relay fault| Restart inverter, if the error still exist, contact us
E017| Internal communication fault2| Restart inverter, if the error still
exist, contact us (DSP&M8)
E018| Internal communication fault3| Restart inverter, if the error still
exist, contact us (DSP&M3)
E019| Bus voltage high| Check if PV input voltage is higher than 480V
E020| EPS connection fault| Check if EPS and AC connection is in wrong
terminal
E021| PV voltage high| Check PV input connection and if PV input voltage is
higher than 480V
E022| Over current internal| Restart inverter, if the error still exist,
contact us
E024| PV short| Check PV connection
E025| Temperature over range| The internal temperature of inverter is too
high, turn off the inverter for 10minutes, restart the inverter, if the error
still exist, contact us
E026| Internal Fault| Restart inverter, if the error still exist, contact us
(Bus sample)
E028| Sync signal lost in parallel system| Check CAN cable connection is
connected to the right COM port
E029| Sync triger signal lost in parallel system| Check CAN cable connection
is connected to the right COM port
E031| Internal communication fault4| Restart inverter, if the error still
exist, contact us (DSP&M8)
Code| Description| Trouble shooting
---|---|---
W000| Communication failure with battery| Check if you have choose the right
battery brand and communication cable is right, if the warning still exist,
contact us
W001| AFCI Com failure| Restart inverter, if the error persists, contact your
supplier.
W002| AFCI Hight| Check each PV string for correct open circuit voltage and
short circuit current. If the PV strings are in good condition, please clear
the fault on inverter LCD.
W003| Communication failure with meter| Check communication cable, if the
warning still exist, contact us
W004| Battery failure| Inverter get battery fault info from battery BMS,
restart battery, if the warning still exist, contact us or battery
manufacture
W006| RSD Active| Check if the RSD switch is pressed.
W008| Software mismatch| Please contact Lux power for firmware update
W009| Fan Stuck| Check if the fan is OK
W012| Bat On Mos| Restart inverter, if the error still exist, contact us
W013| Over temperature| The temperature is a little bit high inside inverter
W015| Bat Reverse| Check the battery connection with inverter is right, if the
warning still exist, contact us
W018| AC Frequency out of range| Check AC frequency is in range
W019| AC inconsistent in parallel system2| Reconnect the AC input or Restart
inverter, if the error still exist, contact us
W020| PV Isolation low| Restart inverter, if the error still exist, contact us
W025| Battery voltage high| Check if battery voltage is in normal range
W026| Battery voltage low| Check if battery voltage is in normal range, need
to charge the battery if battery voltage is low
W027| Battery open| Check if there is output from the battery and battery
connection with inverter is OK
W028| EPS Over load| Check if EPS load is too high
W029| EPS voltage high| Restart inverter, if the error still exist, contact us
W031| EPS DCV high| Restart inverter, if the error still exist, contact us
INPUT(PV DC)| SNA US 6000
---|---
Max. PV array power(W)| 8000(4000/4000)
Rated PV input voltage(V)| 320
Number of independent MPPT inputs| 2
PV input voltage range(V)| 100~480
MPPT voltage range(V)| 120~385
Start-up voltage(V)| 100
Max. PV input current per MPPT(A)| 17/17
Max. PV short-circuit current per MPPT(A)| 25/25
Battery
Compatible battery type| Lithium-ion/Lead-Acid
Rated battery voltage(V)| 48
Battery voltage range(V)| 38.4~60
Max. charging/discharging current(A)| 140
Max. charging/discharging power(W)| 6000
Recommend capacity of battery per inverter| >200AH
Force wake up battery from PV function| YES
Force wake up battery from Grid function| YES
Grid
Rated AC voltage(V)| 110(P-N)/220(P-P); 120(P-N)/240(P-P)
Rated AC frequency(Hz)| 50/60
Max. AC input current(A)| 41@220V; 37.5@240V
Max. AC input power(W)| 9000
PF| 0.99
THDI| <5%
Rated AC current of BYPASS relays(A)| 60
GEN
Rated GEN voltage(V)| 110(P-N)/220(P-P); 120(P-N)/240(P-P)
Rated GEN frequency(Hz)| 50/60
Rated GEN input current(A)| 33.5@220V; 30.5@240V
Rated GEN input power(W)| 7370
Rated GEN current of BYPASS relays(A)| 60
UPS
Rated output power(W)| 3000(P-N), 6000(P-N)
Max. Half Wave load(W)| 2300(P-N)
Rated output voltage(V)| 110/220; 120/240
Rated output current(A)| 28@220V; 25@240V
Rated output frequency(Hz)| 50/60
Surge power, duration| 2Pn, <25
Switching time| <15ms@ Single/ <30ms@Parallel
Wave form| Sine wave
THDV| 3%
Efficiency
Max. MPPT efficiency| 0.99
Max. efficiency| 0.93
Max. charging efficiency| 0.93
Max. dischargingefficiency| 0.93
Protection
Over current/voltage protection| YES
Grid monitoring| YES
AC Surge protection Type III| YES
AC SWITCH(Current/Voltage)| 63A/230VAC
UPS SWITCH(Current/Voltage)| 63A/230VAC
Battery SWITCH(Current/Voltage)| 200A/80VDC
GEN SWITCH(Current/Voltage)| 63A/230VAC
General
Dimensions(WHD)| 650450150mm/25.618.15.9in
Weight| 24kg
Ingress protection rating| Ip20
Operating environment temperature range| 0~50℃
Storage temperature range| -15~60℃
Display&Communication interface| LCD+LED, RS485/Wi-Fi/CAN
Warranty| 2years
Cooling method| FAN
Topology| Transformer-less
Noise emission(typical)| <50dB
Standards & Certification