OPA 465–960 RKTG-P (ECO) c/w UC8
Air Cooled Packaged Units – Reverse Cycle – R410A
Installation & Maintenance
GENERAL
Temperzone OPA Outdoor Air Cooled Packaged units.
Follow these instructions to ensure the optimum performance, reliability and
durability.
Units must be installed in accordance with all national and regional
regulations and bylaws. National Health and Safety regulations must be
followed to avoid personal injuries.
The appropriate local permits must be acquired and adhered to.
Local regulations on maximum boundary noise need to be considered when
positioning the unit.
INSTALLATION
Refer to diagrams below and in supplied Specifications sheet for minimum clearances. If multiple units are to be placed side-by-side then allow at least 2m between coil faces.
Fresh Air Cowl Option
The fresh air cowl is supplied separately and must be fitted to the unit –
usually before the unit is lifted into place. Screws and pre-drilled holes are
provided. Ensure the top of the cowl is tucked under the roof lip of the air
conditioner and that all joints are sealed with silicone sealant. There must
be at least 300mm clearance beneath the cowl once it is fitted in place.
Mounting
The unit should be fastened to a firm flat horizontal base using the holes
supplied in the mounting channels. When the unit is being installed on a roof
it is recommended that the unit is installed on a substantial structure with
vibration-isolating mounts or pads.
Flexible duct connections are recommended between the supply and return ducts
and the unit.
Unit is shipped with blocks installed under the compressors. Ensure these
blocks are removed from the compressor feet prior to starting the unit (not
required for operation).
Factory filter slides are fitted, access to the filter access door should be
considered when designing return and supply air ductwork. Access to the
filters can still be achieved by removing the return air access door.
Condensate Drain
The condensate drain should be `U’ trapped outside the unit. The trap should have a vertical height of at least 100 mm. The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe. (refer fig. 2)
REFRIGERATION SYSTEM
General
The OPA 465-960 models have two independent refrigeration circuits and two compressors to provide the flexibility and economy of two stage operation, i.e. utilising one or two circuits as conditions vary, plus the advantage of staggered starting, one stage being digital for improved control and system efficiency. Each refrigeration system has been charged with HFC-410A (R410A) refrigerant; refer Specifications document for amount.
Compressors
The compressors are directional scroll type. The compressor lubricant is polyolester oil (POE). Note, this oil absorbs moisture quickly if exposed to open air. On commissioning, the compressors must be checked for correct rotation (refer Start-Up Procedure 5.2.2).
Economiser (Option) – ECO Plus Version
If the outdoor air temperature, or heat content preferably, is below that of the return air the fresh air damper can be opened and the return air damper closed to provide the first stage of cooling. A spill air facility in the building may be necessary for when the return air damper is closed. The fresh air damper should return to minimum setting and the return air damper open before the compressors are allowed to operate to provide further cooling.
Fresh Air (Option)
Air flow through the damper should not exceed 15% of the OPA unit’s nominal
air flow. Excessive amounts of low ambient fresh air will reduce the
performance of a reverse cycle OPA unit especially on heating cycle.
The damper setting is dependant on the return air duct static pressure and the
design air flow for the specific installation. It is recommended an air flow
balance commissioning contractor be utilised. Too much fresh air introduction
may void the OPA unit’s warranty.
WIRING
Electrical Requirements
Electrical work must be done by a qualified electrician.
DANGER LIVE ELECTRICAL CONNECTIONS. REMOVE MAINS POWER BEFORE WORKING ON UNIT.
ONLY QUALIFIED PERSONS WHO ARE COMPETENTLY TRAINED SHOULD PERFORM SERVICE AND
MAINTENANCE TASKS.
The outdoor unit must be wired directly from a distribution board by means of
a circuit breaker and a mains isolator provided – preferably close to the
unit.
Note: DO NOT USE REWIRABLE FUSES.
A 24 hour power supply to the compressor crank case heaters is required,
otherwise the warranty is void.
Control options
OPA ECO units can be controlled using any of the following options:
- TZT-100 wall thermostat
- SAT-3 wall thermostat
- 24V AC and 0-10V signals from an external controller or thermostat
- Remote on/off switch and/or time clock
- Modbus RTU serial communications over RS485 connection
- BACnet-IP serial communications over Ethernet connection (with optional gateway module)
Standard reverse cycle units are suitable for use with thermostats and
controls with manual heating/cooling selection or automatic change-over.
A unit wiring diagram is supplied alongside the electrical board and in the
Specifications document.
Remote on/off
The UC8 has an input for a remote on/off function on terminal On’, signal return is terminal
0V’. When used the remote on/off terminals should connect
to a voltagefree relay contact. When not used the remote on/off terminals
should be shorted (`looped’).
Capacity control
OPA ECO units offer the following capacity control options:
- Automatic control when the unit connects to the TZT-100 or SAT-3 wall thermostat.
- 0-10V control signal via terminal
VC’ on the UC8 circuit board, signal return is terminal
0V’. - Control by a building management system via Modbus RTU or BACnet-IP serial communications.
Unit Controller (UC8)
The temperzone Unit Controller 8 (UC8) is the successor to the UC6 controller.
Each dual compressor OPA unit utilises two UC8 Controllers, one for each
refrigeration system. The UC8 controllers receive requests such as Unit On/Off’,
Start compressors’, Activate HEAT (Reverse Cycle)’ and transfer the requests to the outputs after enforcing safety timers. The Unit Controller provides several system protection functions. These are covered in Appendix I (p.9). For additional information, refer to the UC8 Controller label on the unit or www.temperzone.biz for operation & fault diagnostics information; model search
UC8′. References available:
UC8 Operation Manual : Air-to-Air Units
UC8 Fault & Display Messages (as per unit label)
UC8 Quick Reference and Operation Fault Diagnosis
UC8 Troubleshooting Guide
UC8 Modbus Communications
UC8 BACnet Communications
UC8 Master-Slave Connection
START-UP PROCEDURE
Before starting the compressor
- Before working on the unit remove mains power from the unit by opening the mains isolating switch.
- Remove the shipping blocks from beneath each compressor. Check that each compressor is securely mounted.
- Check the thermostat and/or other controls are correctly wired to the unit.
- Check tightness of electrical connections.
- Check the air filters have been correctly installed, if present.
- Check that all indoor fan motors can freely rotate.
- Apply mains power to the unit by closing the mains isolating switch.
- Check the supply voltage between each phase and neutral.
- Check air diffusers are open.
- Before starting the compressors a four hour delay period is required to allow the crankcase heaters to drive any liquid refrigerant out of the compressor oil. Mains power must be switched on during this four hour delay period.
Commissioning
After the four hour delay period has expired (see step 10 in section 5.1) complete the following procedure. You can use the Commissioning Sheet (supplied with the unit) to help you.
-
Place the UC8 master controller in commissioning mode by holding down the SW3 push button on the circuit board (see Section 4.5) until the display shows:
0′ [release] →
1′ [long press] →t’; [short press] repeat to find
c’, then [long press] to select. This Commissioning mode `c’ reduces the waiting times at start-up and between cycles. for the next half hour, or until the controller is reset by removing power. -
Start compressor number 1 in cooling mode.
Note: Compressors are directional. If a compressor rotates incorrectly it will not pump, be noisy and draw minimal current. If this is the case switch the unit off and check for correct mains phase connections at the main power terminals and recheck. -
Check the outdoor fan motors run smoothly.
Note: Outdoor fans do not necessarily start rotating immediately after the compressor is started. The fans may run-on for a short period after the compressor stops. Outdoor fans stop during outdoor coil de-ice cycles. -
Measure the current draw on each phase to the compressor motor and to each fan motor. Check the readings against the specified values in the wiring diagram or specification sheet.
-
The display and pushbutton on the UC8 can be used to check temperatures and pressures. Short presses on the pushbutton cycles through the available options. Table 1 on page 8 shows, in sequence, what information is available with examples.
Alternatively use a set of pressure gauges suitable for R410A refrigerant. -
Repeat steps 2 to 5 for each compressor.
-
Test operation of the compressors when operating in heating mode.
-
Check for desired supply air flow rate at each outlet.
-
Touch up any outdoor unit paintwork damage to prevent corrosion.
-
Sign the check label.
Commissioning of variable speed (EC) indoor plug fans
A unit equipped with variable speed (EC) indoor plug fans allows adjustment of the fan speeds to obtain the desired indoor supply airflows. Using TZT-100 option If the unit is controlled with a temperzone TZT-100 wall thermostat then adjustments are made as follows:
- Stop all compressors. The UC8 display should show a flashing dot (- • ).
- Hold down the SW3 push button on the circuit board until the display shows:
0′ [release]
1′ [long press]t’; [short press] repeat to find
H’, then [long press] to select. The indoor fan will start and run at High speed. The display shows the fan control voltage for the High speed setting, factory default value is 8.0V. - Each following button press increases the control voltage in steps of 0.5V. The maximum is 10V. Pressing the button when the maximum of 10V is reached causes the control voltage to step down to the minimum of 3V, where-after subsequent presses once again raise the control voltage in steps of 0.5V.
- When the desired High speed control voltage is displayed, [long press] to select and save. The controller then exits the menu and the fan stops.
- From the flashing dot (- • ), hold down the SW3 push button on the circuit board until the display shows:
0′ [release]
1′ [long press]t’; [short press] repeat to find
L’, then [long press] to select. The indoor fan will start and run at the Low speed setting. The factory default value is 5.0V - Repeat steps 3 and 4 to adjust the fan Low speed setting. The minimum control voltage for Low speed is 1V and the maximum control voltage for Low speed is 8V. (Note: A
low’ control voltage of less than 2V is not recommended.) If
low’ is set higher thanhigh’, the
high’ is made equal to `low’.
Using SAT-3 option
If the unit is controlled with a temperzone SAT-3 wall thermostat then
adjustments are made as follows:
- Activate fan setup mode: Hold down and `4′ button together for 3 seconds.
- When fan setup mode is active symbol flashes on and off.
- Press to adjust the fan `low’ control voltage up or down.
- When the desired
low’ voltage is set then press and repeat step 3 to set the fan
high” voltage. - When adjustment is complete press fan setup mode.
Using Alternative Thermostats
Follow same procedure as for TZT-100. to exit
Note:
If fan speed selections are different from the factory default values then the
procedure above must be carried out for each UC8 controller in the unit. It is
allowed to make the control voltages for low and high fan speed equal. This
makes the indoor fan act as a fixed speed fan. It is allowed to control the
indoor fan speed by an external source, independent of the UC8 controller. It
is then the responsibility of the system designer and installer to ensure
proper and safe operation of the indoor fan, and the system as a whole, under
all operating conditions. Setting the indoor fan speed too low can bring risk
of frost forming on the indoor coil with potential nuisance frost protection
trips on cooling, possibly even unit lockout, and/or HP trips on heating.
Setting the indoor fan speed too high can bring a risk of blowing moisture off
the fins of the indoor coil and into the supply air duct. Water could then
start leaking from the supply air vents and diffusers and corrosion of ducting
may occur. Setting the indoor fan speed too high can also bring a risk of
`over-condensing’ (when the unit is heating) which in turn could cause the
unit to perform more outdoor coil de-ice cycles than necessary.
OPERATION
Safety timers
The UC8 receives control signals and transfers the signals to the outputs after enforcing safety timers and other protection functions. If the compressor is held off, or held on, by a safety timer then the display shows message `H-O-L-d’.
Normal durations of safety timers are:
- Minimum off time 3 minutes
- Minimum run time 1.5 minutes
- Min. cycle time 6 minutes (up to 10 compressor starts per hour)
- Min. mode change-over time 10 minutes (cooling to heating or vice-versa)
Variable Capacity
OPA 465960 units are equipped with two compressors where the first compressor is variable capacity (ie digital scroll type); the second either fixed or variable capacity depending on the model (refer 7.1). DIP switch 14 on the UC8 circuit board can be used to select one of two operating modes:
DIP switch 14 | Capacity control mode |
---|---|
OFF | Standard capacity control |
ON | Close capacity control |
Compressor operating capacities and 0-10V control voltages are:
Compressor type | Minimum | Nominal |
---|---|---|
Close control | Standard control | |
Fixed duty | 100% | |
Digital scroll | 16% (1.6V) | 40% (4V) |
Note:
At any time, when operating conditions dictate, safety functions can
restrict unit operating capacity. Unless the application requires close
control it is recommended to operate OPA ECO units in standard capacity
control mode. When a capacity signal is presented that is lower than the
minimum capacity (for example 0V on input `VC’) then the compressor operates
on minimum duty. If a unit operates on low capacity for extended periods then
the unit may periodically perform oil flush cycles. Under such operating
conditions compressor lubricating oil may slowly settle in parts of the
refrigeration system other than the compressor; oil flush cycles help to
return the lubricating oil to the compressor. During an oil flush cycle
compressor capacity is increased to a certain minimum. The duration of an oil
flush cycle is 1 minute.
CONTROLS
General
The control details shown in this document relate to the operation of a unit
with:
OPA 465-705: a single digital compressor (Stage 1: variable capacity
controlled) and a fixed speed compressor (Stage 2: on/off controlled):
OPA 855,960: a single digital compressor (Stage 1: variable capacity
controlled) and a second digital compressor (Stage 2: on/off controlled). The
second digital is fitted for extra protection under difficult conditions.
Refer to temperzone Engineering if the desire is to have variable capacity
control on both digital compressors.
TZT-100 and SAT-3 wall thermostat
When the unit is controlled with a TZT-100 or SAT-3 a wall thermostat then it is necessary to configure the UC8 controllers in the unit as a master and a slave. Follow these steps:
- On the master UC8: DIP switch 11 OFF switch 12 OFF
- On the slave UC8: DIP switch 11 ON switch 12 OFF
- The thermostat connects to the master UC8 as shown below.
- The Master-Slave communications cable (factory supplied and connected) must stay connected between individual UC8’s (refer wiring schematic sheet 1, grid reference 5-E to 8-E).
To connect the thermostat to the unit it is recommended to use shielded
twisted pair type cable, suitable for RS485 communications. Signals A and B
should form one twisted pair.
Note: The cable shield should connect to terminal `0V’ on the UC8
controller only. Do not connect at both ends. Connect the thermostat as
follows:
Note: Capacity Staging. A TZT-100 or SAT-3 must be configured for two- stage operation.
TZT-100 has its own DIP switches that must be set as follows:
DIP switch 2 | ON | Equipment type = Heat Pump |
---|---|---|
DIP switch 3 | ON | Equipment stages = Two |
DIP switch 4 | ON | Reverse cycle valve on = Heating |
Communications format for TZT-100 and SAT-3.
Communications format must be set as per recommended Modbus RTU:
• Baud rate (bd or br)
• Data bits
• Parity
• Stop bits (Pa)
• TZT-100 address (Ad)
• SAT-3 address (Ad)| 19200
8
Even
1
7
8
---|---
TZT-100: The procedure to check and adjust these settings is:
- Press and hold the O/RIDE button until the display shows the PIN
- Use the UP & DOWN buttons to select PIN code 88:21, then press O/RIDE in installer mode.
- Use the O/RIDE and PROG buttons to cycle through the various installer settings.
If necessary, refer TZT-100 User Manual for more detail.
SAT-3: The procedure to check and adjust these settings is:
- Press and hold the MODE and 6 button until the display shows the ‘i’ symbol.
- Use the UP & DOWN buttons to cycle through the various installer settings.
- Press MODE button to save any new setting.
If necessary, refer SAT-3 Installation Set-up Guide for more detail.
Control using switched and 0-10V signals
An external controller that provides 24V AC switched signals or has a set of voltage-free relay contacts should be connected as per the diagram below. UC8 input ‘VC’ will accept a 0-10V capacity control signal. If no capacity control signal is available then link UC8 terminals ‘VC’ and ‘12’. It is necessary to configure the UC8 controllers in the unit as master and slave; refer Section 7.2 and follow steps 1, 2 & 4.
Control via Modbus RTU communications
OPA ECO units can be fully monitored and controlled via Modbus RTU serial communications. The following is typical for most installations:
- Set DIP switches 11 and 12 OFF on all UC8 controllers.
- Connect BMS terminal A / TX+ to terminal A1 on all UC8 controllers.
- Connect BMS terminal B / TX- to terminal B1 on all UC8 controllers.
It is recommended to ‘daisy-chain’ the A&B connections using shielded twisted pair type cable, suitable for RS485 communications. Signals A and B should form one twisted pair. The cable shield should connect to terminal ‘0V’ on the UC8 controller. The Master/Slave communications cable connected between the UC8 controllers must be removed. DIP switch 11 must be set to OFF on both UC8 controllers.
- To avoid collisions of messages on the RS485 serial communications cable it is necessary to ensure each connected UC8 controller has a unique Modbus device address. Refer to section 7.6 for the procedure.
Example:
For detailed information about monitoring and control via Modbus RTU refer to document “UC8 Modbus communications”, available free on the temperzone internet website.
Setting the UC8 Modbus device address
To view or change the Modbus device address of a UC8 follow these steps:
- Power up the unit but leave the compressors off.
- Hold down the SW3 pushbutton on the UC8 circuit board until the display shows: ‘0’ [release] → ‘1’ → short press to ‘2,’ [long press] → A, [long press]
- The display will show the current Modbus device address. The factory default address is ‘44’. [Short press] the button to select higher numbers, for example press once to change the address to 45, press twice for address 46 and so forth. [Long press] to save the chosen address. After address 99 the number returns back to 1.
- The controller returns to the default state (●).
Economiser Option
The Economiser package that is factory fitted consists of two opposed blade
dampers, one for the fresh air and the other for the return air and complete
with individual damper motors controllable from a 0 10V dc signal. The
package also includes a fresh air cowl (weatherhood) assembly that is usually
supplied as a separate item for fitting on site. It is important that the
installation instructions for the fitting of the fresh air cowl are followed
otherwise it is possible some water ingress from rain could occur. The top
flange of the cowl must be tucked under the top panel lip. The damper control
will be factory wired such that the return air damper will close
proportionally as the fresh air damper opens proportionally and vice versa.
The fresh air damper’s adjustable stop can be set such that it does not close
100%; many installations may require a minimum fresh air introduction of 10
15% and the stop may be set on site to facilitate this. Set the economiser
Fresh Air Damper motor stop’ to the equivalent negative static pressure as with F/A damper closed. This is to ensure the air flow volume remains constant and does not dramatically increase when introducing fresh air. Failure to set the correct
stop’ position could result in rain/moisture entrainment in the
incoming fresh air resulting in water deposited inside the unit.
As previously mentioned a 0 10V dc control signal is required to drive the
dampers open and closed. This could be from a BMS or a temperature/humidity
controller.
It is recommended that control is by Enthalpy (or by a combination of dry and
wet bulb temperatures) so that free cooling is used without adding any heat
load to the building. Control by dry bulb temperature alone is not recommended
as often, even though the outdoor dry bulb temperature may be lower than that
of the space, the total heat content of the air can be higher thereby adding
heat load in the form of moisture content to the space.
If dry bulb temperature is used as the control method the temperature must be
set several degrees lower than the space temperature to reduce the possibility
of extra heat load being introduced.
Air Quality (CO2) sensors can be used to proportionally control the fresh and
return air dampers (via the control system). In all situations the UC8 Unit
Controller will allow the compressors to operate with the economiser fresh air
damper open providing the refrigeration system is not compromised.
The compressor(s) could be stopped from operating by normal protection devices
such as low suction temperature/ pressure or indoor coil frost protection and
too many trips of either fault could lead to a lock out of the compressor(s)
operation. Should this occur then a review of the control settings may be
necessary.
MAINTENANCE
WARNING HAZARDOUS VOLTAGE. ENSURE ALL POWER SUPPLIES ARE ISOLATED BEFORE PERFORMING MAINTENANCE. FAILURE TO ISOLATE POWER CAN LEAD TO SERIOUS INJURY.
Monthly
- Check air filters, if fitted, and vacuum or wash clean as necessary.
- Check condensate drain for free drainage.
- Check compressor compartment for oil stains indicating refrigerant leaks.
- Check system operating pressures via the UC8 (refer Section 5.2.5).
Six Monthly
- Check the tightness of electrical connections.
- Check for signs of corrosion on electrical connections in high salt atmospheres; replace where necessary.
- Check the tightness of all fans, motor mountings
- Check system operating pressures via the UC8 (refer Section 5.2.5).
- Check and/or replace indoor air filters 6. Check condensate drain for free drainage.
Yearly
- Check all refrigerant piping for chafing and vibration.
- Check the operation of electric heaters, if fitted
- Check air supply at all diffusers
- Check for excessive noise and vibration and correct as necessary.
- Check for insulation and duct damage and repair as necessary.
- Check system operating pressures via the UC8 (refer Section 5.2.5).
- Remove lint and dust accumulation from outdoor coil fins with soft brush or low pressure water spray.
- Touch up any paintwork damage to prevent corrosion.
TROUBLESHOOTING
Room temperature varies significantly from its setting
- Unit may have been incorrectly sized for the building.
- Drafts from wrongly placed supply air diffusers or from the back of the wall plaque could be affecting the temperature sensor built into the wall plaque.
- Poor air circulation in the room can cause incorrect temperature readings.
Air conditioner does not seem to deliver the heating when most needed
- Heating capacity at design conditions may be incorrect. As the outside temperature falls, heat losses through the walls, floor and ceiling increase.
- Check the unit’s brochure for information on the minimum/ maximum operating temperatures.
When heating, units have de-icing cycles built in to remove ice on the
outdoor coil.
- This usually means reversing the cycle for a few minutes during which time there is no heating and in fact a little cooling can occur.
In a new building, why does it take some days before the air
conditioning heat hump unit seems to work properly
- Many new buildings, especially a commercial buildings, have a large amount of concrete and other structural materials that are generally cold and full of moisture. This is most evident in the winter when trying to heat the building from scratch.
Unit is leaking water
- Check the drain trap/vent/slope.
- Water carry-over: Reduce the maximum fan speed.
Air conditioner runs excessively the temperature remains too hot in
summer or too cold in winter.
- Windows or doors may be opened to non conditioned areas.
- Keep doors to unconditioned areas closed.
- Leaves, papers or other items blocking air flow over the outdoor unit coil.
- Location of wall controller or remote temperature sensor is incorrect.
- Check for leaks in supply or return air ductwork.
Outdoor unit displays an error code:
Refer to UC8 Controller label on the unit for operation & fault diagnostics information or visit www.temperzone.biz; model search `UC8′.
WARRANTY
Please refer to the separate warranty document supplied with the unit, or visit www.temperzone.biz for details.
Australia:
warranty@temperzone.com.au
spares@temperzone.com.au
Telephone: 1800 21 1800| New Zealand:
customerservices@temperzone.co.nz
Telephone: 0800 TZWARRANTY (899 2777)
---|---
Table 1, Information available on the UC8 display.
Item | Unit | Abbreviation | Examples |
---|---|---|---|
Compressor suction line pressure | kPa | SLP | Suction line pressure 1034 kPa |
Evaporating temperature | °C | Et | Evaporating temperature 12°C |
Compressor suction line temperature | °C | Sit | Suction line temperature 18°C |
Compressor suction side superheat | K | SSH | Suction side superheat 6K |
Compressor discharge line pressure | kPa | dIP | Discharge line pressure 2447 |
kPa
Condensing temperature| °C| Ct| Condensing temperature 42 °C
Compressor discharge line temperature| °C| chi| Discharge line temperature
70°C
Compressor discharge side superheat| K| dSH| Discharge side superheat 28K
De-ice sensor temperature
(located on fins of the outdoor coil)| °C| ICEt| De-ice sensor temperature
39°C
Capacity| %| CAP| Capacity 100%
Expansion valve 1 opening| %| EE1| Expansion valve 1 75% open
Expansion valve 2 opening| %| EE2| Expansion valve 2 75% open
APPENDIX I
PROTECTION FUNCTIONS
The UC8 implements system protection functions such as indoor coil frost,
extreme high and low pressures, rapid on-off cycling of the compressors, loss
of refrigerant and more. The following applies to all protection functions
except where otherwise indicated: Unit operating capacity may automatically be
reduced before a protection function is activated. Such a reduction may be
sufficient to prevent an actual trip from occurring. When a compressor is
stopped by a protection function it is held off for a period of 3 minutes,
after which it is allowed to restart (provided the cause of the trip has
cleared). When a protection function is active and when a unit is locked out
the alarm relay output “FLT” is active. More detailed information about
protection functions and troubleshooting refer to document “UC8
troubleshooting information”, available for free download from the
temperzone internet website.
-
High pressure protection (HP)
Some OPA ECO units may be fitted with high pressure switches. These switches connect to UC8 inputs IN#1. When a high pressure switch activates (the electrical circuit opens) then the compressor is stopped. Most OPA ECO units are fitted with high pressure transducers connected to UC8 input HPT. A compressor is switched off when the discharge line pressure reading exceeds 4238 kPa. The display shows the letters ‘HP’ when protection is active. -
Low pressure protection (LP)
Some OPA ECO units may be fitted with low pressure switches. These switches connect to UC8 inputs IN#2. When a low pressure switch activates (the electrical circuit opens) then the compressor is stopped. Most OPA ECO units are fitted with low pressure transducers connected to UC8 input LPT. A compressor is switched off when the suction line pressure reading falls below 228 kPa. The display shows the letters ‘LP’ when
protection is active. -
Indoor coil frost protection
When the unit is cooling the evaporating temperature in the indoor coil should remain above -8°C. If this temperature falls below -8°C then ice (frost) likely will form on the indoor coil. If the low temperature persists for longer than 6 minutes then the protection function activates.
When indoor coil frost protection is activated the compressor is stopped for 6 minutes, after which it is allowed to restart. -
High discharge line temperature protection
The controller monitors the compressor discharge line temperature via a sensor connected to input ‘DL’ (red wires). The compressor is stopped when:
• The temperature rises above 110°C for longer than 30 minutes.
• The temperature rises above 120°C (immediate action). The display shows the message ‘Hi-t’ when protection is active. -
High discharge superheat protection
Discharge superheat is defined as the difference between the compressor discharge gas temperature and the condensing temperature. When this temperature differential becomes very high it is an indication that the compressor is being starved of refrigerant gas. Common reasons for this could be a lack of refrigerant (under-charged or loss-of-charge) or a problem with the expansion device (for example a stuck accurator or loose wiring to an EEV). The protection is activated when discharge superheat exceeds 45K for longer than 30 minutes. The display shows the message ‘Hi-dSH’ when protection is active. -
Low discharge superheat protection
Discharge superheat is defined as the difference between the compressor discharge gas temperature and the condensing temperature. When this temperature differential stays very low it can be an indication that the compressor is being flooded with liquid refrigerant. Common reasons for this could be an excess of refrigerant (over-charged) or a problem with the expansion device (for example a stuck accurator or loose wiring to an EEV). The protection is activated when discharge superheat remains below the threshold for longer than 15 minutes. The threshold varies linearly from 0K at standard mode minimum capacity (40%) to 10K at nominal capacity (100%). This protection function is disabled when a compressor operates at less than standard mode minimum capacity (< 40%). The threshold for a variable speed compressor operated in boost mode (capacity above 100%) is fixed at 10K. The display shows the message ‘LO-dSH’ when protection is active. -
High evaporation temperature / high suction line temperature protection
When the unit has a low pressure transducer connected to the compressor suction line then the controller calculates the evaporating temperature from the suction line pressure reading. If the unit does not have a low pressure transducer then the controller finds the evaporating temperature via a coil temperature sensor (input IC when the unit is cooling, input OC when theunit is heating, yellow wires). Additionally the controller monitors the compressor suction line temperature via a sensor connected to input ‘SL’ (white wires). The protection function stops the compressor when:
• The evaporating temperature remains above 27.5°C for longer than 15 minutes.
• The suction line temperature remains above 30°C for longer than 15 minutes. The display shows the message ‘Hi-SL’ when protection is active. -
Other alarms
The controller performs many other protection functions. For example:
• Signals from sensors and transducers must remain inside normal operating range.
• Modbus RTU communications with connected devices (e.g. TZT-100 or SAT-3 thermostat, a Carel Power+ inverter) must continue uninterrupted.
• Modbus RTU communications with a controller such as a BMS that is controlling the unit must continue uninterrupted.
Refer to document ‘UC8 Troubleshooting Guide’ for details. -
Lock-out
Each protection function has a trip counter. A trip counter is reset to 0 whenever the compressor run request is removed. Any trip that has occurred more than 12 hours ago is removed from the trip count. For some protection functions, when the trip counter reaches value 3 (i.e. three consecutive trips occur) then the unit is “locked out”. When a unit is locked out the compressor is not allowed to start. Lock-out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician. The display shows the code of the fault that caused the lock-out condition. A unit that is locked out can be unlocked using any one of the following methods:
• Remove mains power from the unit for at least 3 seconds, then restore power.
• Issue an ‘unlock’ command via Modbus RTU serial communications.
• Reset the controller via Modbus RTU serial communications.
APPENDIX II
AIR HANDLING PERFORMANCE
Note: Airflows are for a dry coil. Reduce airflow by 10% in wet coil
conditions. In a free blow or low resistance application, beware of exceeding
indoor fan motor’s full load amp limit (refer Specifications document). As
filters are optional, the fan air flows given are for units installed without
filters.
OPA 465-P
| **OPA 550-P
---|---
OPA 705-P
| OPA 855-P
**
OPA 960-P
INSTALLER TO COMPLETE
Commissioning Check List
Site Name/address: ………………………………………………………………………………………………………………………………………………………
Installing Company ………………………………………………………………………………………… Date:
………………………………………………….
Serviceman: ………………………………………………………………………………………………… Tel: ………………………………………………………..
Model …………………………………………………………… Serial No………………………………. Site Ref.
……………………………………………….
Unit mounted level? | Y / | N | Supply voltage checked? | Y | / | N | ||
---|---|---|---|---|---|---|---|---|
Temperzone recommended drain trap fitted? | Y / | N | External electrical | |||||
isolator fitted? | Y | / | N | |||||
Water drain tested okay? (panels on, fan running) | Y / | N | Compressor | |||||
overload settings | A | |||||||
Does unit have adequate safe access? | Y / | N | Indoor Plug fan set voltage | |||||
V | ||||||||
All electrical terminals are tight? | Y / | N | Are temperature controller’s | |||||
parameters set? | Y | / | N | |||||
Return air filters fitted? | Y / | N | Checked for excessive noise & vibration | |||||
of unit? | Y | / | N | |||||
Removed compressor shipping blocks? | Y / | N | Has client had controls demo? | |||||
Y | / | N | ||||||
Refrigeration leak checked? | Y / | N | Certificate Of Compliance issued? | Y | ||||
/ | N | |||||||
Is air flow set and balanced? | Y / | N | ||||||
Thermostat type: | BMS | / | SAT-3 / TZT-100 / Other? (name): |
Mark UC8 dip switch positions with an ‘X’
| SW1
---|---
1| 2| 3| 4| 5| 6| 7| 8
On| | | | | | | |
Off| | | | | | | |
| SW2
---|---
| 9 (1)| 10 (2)| 11 (3)| 12 (4)| 13 (5)| 14 (6)| 15 (7)| 16 (8)
On| | | | | | | |
Off| | | | | | | |
Record the following UC8 monitored conditions using push button SW3 (repeat
to scroll through list).
IMPORTANT: Digital compressors must be operating at 100% for at least 10
minutes when taking these readings.
Cool Cycle:
| System 1| System 2
---|---|---
Low Pressure:| SLP| kPa| kPa
Evap temperature:| Et| °C| °C
Suction Line temperature:| SLt| °C| °C
Suction Superheat:| SSH| K| K
Discharge Line Pressure:| dLP| kPa| kPa
Condensing temperature:| Ct| °C| °C
Discharge Line temperature:| dLt| °C| °C
Discharge Superheat:| dSH| K| K
De-ice Sensor temperature:| ICEt| °C| °C
Required Capacity:| CAP| %| %
Expansion Valve 1:| EE1| %| %
Expansion Valve 2:| EE2| %| %
Outdoor Ambient temperature:| °C
---|---
Indoor Return air temperature:| °C
Indoor Supply air temperature:| °C
Indoor fan amps :| A
Fresh Air introduced :| %
Compressor 1 amps :| A
Compressor 2 amps :| A
Heat Cycle:
Low Pressure: | SLP | kPa | kPa |
---|---|---|---|
Evaporating temperature: | Et | °C | °C |
Suction Line temperature: | SLt | °C | °C |
Suction Superheat: | SSH | K | K |
Discharge Line Pressure: | dLP | kPa | kPa |
Condensing temperature: | Ct | °C | °C |
Discharge Line temperature: | dLt | °C | °C |
Discharge Superheat: | dSH | K | K |
De-ice Sensor temperature: | ICEt | °C | °C |
Required Capacity: | CAP | % | % |
Expansion Valve 1: | EE1 | % | % |
Expansion Valve 2: | EE2 | % | % |
Outdoor Ambient temperature: | °C | ||
--- | --- | ||
Indoor Return air temperature: | °C | ||
Indoor Supply air temperature: | °C | ||
Indoor fan amps : | A | ||
Fresh Air introduced : | % | ||
Compressor 1 amps : | A | ||
Compressor 2 amps : | A |
NOTE: This document to be kept with the unit. Failure to provide this completed page on request by Temperzone may effect unit warranty.
© temperzone limited 2022