hager JN202SPD Surge Protection Kit JN 250A Type II User Manual
- June 5, 2024
- hager
Table of Contents
JN202SPD Surge Protection Kit JN 250A Type II
JN202SPD User instructions
Surge Protection Kit JN 250A Type II
Protection Devices Surge Protection Kit
Parts list:
- 16mm sq neutral cable
- 16mm sq L1/L2/L3 cable
- 3 x M8 Bolts for L1/L2/L3 cable connection to incomer with washers
- 2 x M4 Screws
- 1 x SPD Bracket
- 1 x M8 Bolt for Earth Link with washers
- 1 x Copper Earth Link
- 1 x Type II SPD
Fix the din rail bracket to chassis with
2 M4 screws.
‘Always install the chosen Incomer
first’.
Clip the Surge protection device to the
dinrail with the neutral lead to the left
and connect to the neutral assembly as
above, Torque to 13Nm.
Connect the L1/L2/L3 cable lugs to the
Incomer using the M8 Bolts provided
making sure to use the flat washer and
shake proof washer, torque to 13Nm
Feed the L1/L2/L3 cable through the
hole in the chassis and terminate into
the the Surge protection device at
3.6Nm.
Fit the copper earth link to the
chassis with the M8 bolt provided
making sure to use the flat washer
and shake proof washer, torque to
13Nm then screw the earth earth
connection on the Surge protection
device to 3.6Nm.
The device may only be connected and installed by an electrically skilled
person. National standards and safety regulations must be observed.
The device must be checked for external damage prior to installation. If any
damage or other defects are detected in this check, the device must not be
installed. Its use is only permitted within the limits shown and stated in the
installation instructions. Opening or otherwise tampering with the device
invalidates the warranty.