La Marche FT Series Pure Sine Wave Inverter Installation Guide
- June 5, 2024
- La Marche
Table of Contents
- La Marche FT Series Pure Sine Wave Inverter
- Important Safety Instructions
- Electrical Safety
- Model Scope/General Description
- Installation
- Operation
- Service
- Appendix A: Technical Specifications
- Appendix C: Example Wiring Diagram
- Appendix D: Manufacturer’s Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
La Marche FT Series Pure Sine Wave Inverter
Important Safety Instructions
Before using this equipment, read all manuals and other documents related to this inverter and other equipment connected to this unit. Always have a copy of an inverter’s manual on file nearby, in a safe place; if a replacement copy of a manual is needed, it can be found at www.lamarchemfg.com.
Electrical Safety
WARNING:
Hazardous voltages are present at the input of power systems. The output from
inverters and batteries may be low in voltage but can have a very high current
capacity that may cause severe or even fatal injury. When working with any
live battery or power system, follow these precautions:
- Never work alone on any live power system, someone should always be close enough to come to your aid.
- Remove personal metal items such as rings, bracelets, necklaces, and watches.
- Wear complete eye protection (with side shields) and clothing protection.
- Always wear gloves and use insulated hand tools.
WARNING:
Lethal voltages are present within the power system. Parts inside the unit may
still be energized even when the unit has been disconnected from the DC or AC
input power. Check with a meter before proceeding. Do not touch any parts that
are not insulated.
- A licensed electrician should be used in the installation of any unit.
- Always disconnect the unit from the supply, batteries, and loads before performing maintenance or cleaning.
- If the unit is hot-swappable, simply remove it from the shelf for any maintenance or cleaning.
- Always assume that an electrical connection is live and check the connection relative to the ground.
- Be sure that neither liquids nor any wet material come in contact with any internal components.
- Do not operate this unit outside the input and output ratings listed on the unit nameplate.
- Do not use this unit for any purpose not described in the operation manual.
Mechanical Safety
- This unit or parts of the unit may get very hot during normal operation, use care when working nearby.
- Do not expose equipment to rain or snow. Always install in a clean, dry location.
- Do not operate the equipment if it has received a sharp blow, been dropped, or otherwise damaged in any way.
- Do not disassemble this unit. Incorrect re-assembly may result in a risk of electric shock or fire.
Battery Safety
WARNING:
Follow all of the battery manufacturer’s safety recommendations when working
with or around battery systems. DO NOT smoke or introduce a spark or open
flame in the vicinity of a battery. Some batteries generate explosive gases
during normal battery operation.
- To reduce the risk of arc, connect, and disconnect the battery only when the unit is off.
- If it is necessary to remove the battery connections, always remove the grounded terminal from the battery first.
- Remove personal metal items such as rings, bracelets, necklaces, and watches.
- Always wear rubber gloves, safety glasses, and a rubber-lined vest/apron when working near a battery.
- Have plenty of freshwater and soap nearby in case the battery electrolyte contacts skin, clothing, or ey
- If the battery electrolyte contacts skin or clothing, wash immediately with soap and water.
- If the electrolyte enters the eye, immediately flood the eye with running cold water for at least ten (10) minutes and seek medical attention immediately.
- Do not drop metal on a battery. A spark or short-circuit could occur and could cause an explosion.
Unit Location
- Allow at least 6 inches of free air on all vented surfaces for proper cooling.
- Do not operate this unit in a closed-in area or restrict ventilation in any way.
- Do not set any battery on top of this unit.
- Never allow battery electrolyte to drip on this unit when reading the specific gravity or filling the battery.
- Never place this unit directly above a standard flooded battery. Gases from the battery will corrode and damage equipment.
- A sealed maintenance-free or valve-regulated lead-acid (VRLA) battery may be placed below this equipment.
Check for Damages
Before unpacking the product, note any damage to the shipping container and
take pictures. Unpack the product and inspect the exterior and interior of the
product for damage. If any damage is observed, take pictures and contact the
carrier immediately to file a damage claim. Contact La Marche for a Return
Material Authorization number to have the inverter sent back for evaluation
and repair.
Returns for Service
Save the original shipping container. If the product needs to be returned for
service, it should be packaged in its original shipping container. If the
original container is damaged/unavailable, make sure the product is packed
with at least three inches of shock-absorbing material to prevent shipping
damage. La Marche is not responsible for damage caused by improper packaging
of returned products.
Inspection Checklist
- The enclosure exterior and interior are not marred or dented. No visible damage to the components.
- All hardware and connections are tight.
- All wire terminations are secure.
- All items on the packing list have been included.
Handling
Equipment can be very heavy with uneven distribution of weight. Use adequate
manpower or equipment for handling. Until the equipment is securely mounted,
care must be used to prevent equipment from being accidentally tipped over or
dropped.
Model Scope/General Description
The La Marche FT Series Inverter is a pure sine wave AC output, designed to adopt to various types of loads. This DC to AC Inverter with dual CPU control provides excellent performance with automatic protection. The FT Inverter temporarily provides up to 120% of the output for 30 seconds, providing extra power needed to start motorized equipment. Available in 120 VAC or 230 VAC Output.
Understanding the Model Number
The FT Series model number is coded to describe the features that are
included. Find the model number on the nomenclature nameplate of the
enclosure. Follow the chart below to determine the configuration of the
inverter.
Optional Accessories Included in the Inverter
This inverter may have been outfitted with a number of optional accessories or
option packages. To determine the options included (if any) refer to the cover
page of the manual package. If the manual package that is included with the
inverter is no longer available, contact La Marche and provide the model or
serial number to receive a list of the included accessories.
Equipment Handling
If the FT Series Inverter is to be stored for more than a few days after
delivery, it should be stored within its shipping container. The location
chosen for storage should be within an ambient temperature of -4 to 140°F (-20
to 60°C) with a non-condensing relative humidity of 0 to 95%. Storage should
not exceed 2 years due to the limited shelf life of the filter capacitors when
they are not in service.
Moving the FT Series Inverter
After careful inspection and upon verification that the FT Series is
undamaged, identify the enclosure style and weight of the inverter. Refer to
Table 1 below.
| Output kW| Output Voltage| Dimensions (D x W x H)|
Weight (lbs)| Enclosure Size
---|---|---|---|---|---
FT Series Inverter| 1kW/2kW/3kW| 120VAC,
208VAC,
220VAC
or 230VAC
| 19.2 x 10 x 7”| 28.6/35.2/39.6| 250
4kW/5kW/6kW| 22 x 12 x 8”| 59.5/66.1/74.9| 251
8kW| 25.7 x 13.3 x 10.2”| 103.6| Consult Factory
Installation
When mounting the FT Series Inverter, consider the size and weight of the inverter. The FT Series Inverter is wall mounting system. Refer to Table 1 to verify the weight of the inverter. The location chosen for the inverter should be within an ambient temperature range of -4˚F to 122˚F (-20˚C to 50˚C) with a non-condensing relative humidity no higher than 95%. The inverter should be mounted in an area free of explosive materials and away from any liquids. Avoid using equipment in a location with corrosive gases (e.g. over flooded Lead Acid batteries) and dust. The FT Series utilizes fan-assisted cooling, so clearance of at least 12 inches of free air must be maintained in buttom and on top for proper cooling. The preferred fastener is a machine bolt backed with a flat washer, lock washer, and nut. All hardware should be corrosion- resistant.
Wall-Mounting the FT Series Inverter
To wall-mount the FT, mark and drill the points on the wall per the
mounting dimensions and install (4) bolts in the wall, rated to support the
inverter’s weight plus a safety factor of at least four times. Refer to Table
1 for unit weight specifications. Secure the inverter on bolts, add
appropriate mounting hardware, and tighten securely.
FT Series Inverter Overview
DC Input Connections
Before making any of the DC output connections, make sure you read and
fully understand the DC Connection Procedure on the following page. Select
proper size for the DC wires using the table below. Refer to Appendix A for
the DC input current draws at full load capacity. This is based on an overload
current of 110-115% of the input current listed on the inverter nameplate. If
the distance between the inverter’s DC input and the battery exceeds 10 feet,
use the Power Wiring Guide in Appendix B to minimize the voltage drop across
the wire distance. WARNING: Before beginning any work inside the inverter,
ensure that all incoming AC/DC power is de-energized and/or isolated. Verify
that no voltage is present inside the case by using a voltmeter at all input
and output terminals. Assure the inverter that is being used is the same
number and type of cell as the inverter front nameplate specifications. The FT
inverter DC terminal bolts accept a 5/16” or M8 ring terminal stud size.
NOTE:
It is recommended to use a battery disconnect breaker between inverter and
battery bank; helpful during battery or inverter maintenance. The
breaker/disconnect should be sized with consideration of the full load DC
input current of the inverter. Refer to Appendix A for the DC input current
draws at full load capacity.
Breaker Size/ Fuse Size (Amps)| Minimum AC/DC Wire Size Requirement|
Equipment Grounding Conductor Minimum
---|---|---
25| #10| #12
30| #10| #10
40| #8| #10
50| #8| #10
60| #6| #10
70| #6| #8
80| #4| #8
90| #4| #8
100| #4| #8
125| #2| #6
150| #1| #6
175| #1/0| #6
200| #2/0| #6
250| #4/0| #4
300| 250 MCM| #4
DC Connection Procedure
The battery connections should be done in the following order:
- Assure that the incoming AC mains input power to the inverter is turned off.
- Check polarity of DC input cables and verify with multimeter.
- Connect the positive DC input cable to the positive terminal and the negative DC input cable to the negative terminal. OBSERVE PROPER POLARITY.
AC Output/AC Input Connections
A terminal strip is provided for the AC output/load, as well as for the AC
input line (utility). Before beginning any work inside the inverter, ensure
that all incoming AC/DC power is de-energized and/or isolated. Verify that no
voltage is present inside the inverter by using a voltmeter at all input and
output terminals.Select wire size using the Table 2 on the previous page. Use
the table below to determine the breaker size used in the FT inverter being
installed. Refer to Figures 4 and 5 for connector locations.For the AC output,
connect the AC load phase (hot) to the OUTPUT (L) terminal and the AC load
neutral to the OUTPUT (N) terminal. For the AC input, connect the AC input
phase (hot) to the INPUT (L) terminal and the AC input neutral to the INPUT
(N) terminal. Connect an adequate earth ground lead (use table on previous
page for sizing) to the corresponding grounding terminal. The AC terminals
accept 14 – 6 AWG wire.
NOTE:
Feeder breakers should be sized to match the size of the protection used in
inverter. See the table below for the inverter AC breaker sizes.
FT
Model
| AC Input/Output Voltage
---|---
120VAC| 208VAC| 220VAC| 240VAC
1K| 11A| 6A| 6A| 6A
2K| 21A| 12A| 12A| 11A
3K| 32A| 18A| 17A| 16A
4K| 42A| 24A| 23A| 21A
5K| 52A| 30A| 29A| 26A
6K| 63A| 36A| 34A| 32A
8K| 84A| 48A| 46A| 42A
Alarms
The FT series inverter has an audible buzzer alarm which activates
depending on the status of the inverter. Below are the available alarms/status
indicators:
- Load Powered by Battery: Beeps 4 times every 15 seconds
- High Battery Voltage: Beeps 4 times per second
- Low Battery Voltage: Beeps 2 times per second
- temperature: Beeps 2 quick times per second
Alarm/Status Indicator Descriptions
LOAD POWERED BY BATTERY ALARM
will trigger and the inverter will beep 4 times every 15 seconds if the AC
load is being powered by the battery. This may be an indication that the AC
mains may not be available as a supply or the AC mains may not be within range
to be considered an AC supply. The alarm will clear once the inverter shifts
its source to the AC mains.
LOW BATTERY VOLTAGE ALARM
will trigger and the inverter will beep 2 times per second if the DC voltage
falls below 1.67 volts per cell for longer than 5 seconds. The alarm will
clear once the low battery voltage condition is no longer present.
HIGH BATTERY VOLTAGE ALARM
will trigger and the inverter will beep 4 times per second if the DC voltage
rises above 2.5 volts per cell for longer than 5 seconds. The alarm will clear
once the high battery voltage condition is no longer present.
OVERTEMPERATURE ALARM
will trigger and the inverter will beep 2 quick times per second if the
internal temperature of the inverter rises above 40ºC/104ºF for longer than 5
seconds. The alarm will clear once the temperature alarm condition is no
longer present.
Operation
Checking the Installation
Before attempting to start up the FT Series Inverter, check and verify the
following:
- Verify all connections are correct.
- Assure all terminations and contacts are tightened securely.
- Verify AC feeder breaker and battery breaker (if applicable) matches the inverter’s protection rating.
- Assure the battery/load voltage matches the DC input and AC output voltage on the inverter’s nameplate respectively.
Start-Up Sequence
To power up the FT inverter, simply press the ON/OFF button while the screen
is off. The inverter’s display should turn on and display the output voltage.
Power Down Sequence
To power down the FT inverter, simply press the ON/OFF button while the screen
is on. The inverter’s display should turn off and the output voltage should
decrease. Confirm with multimeter if attempting to service the FT.
Front Panel LCD Display
After the FT Series Inverter has completed startup, the LCD will display
the Input/Output Voltage, Frequency, Grid Mode, Inverter Mode, Battery
Capacity, Load Capacity, Alarm Warning. See below for
reference.
- AC Mains Input Voltage Meter
- AC Output Frequency Meter & Operating Mode Indicator
- AC Output Voltage Meter
- AC Mains Input Status
- AC-DC Operation Status
- DC-AC Operation Status
- Load Usage Percentage Indicator
- Battery Capacity Indicator
- Mute Status
- . Error Indicator
Controls
Button | Function |
---|---|
**** | Mute / Operation Mode Menu |
Press: Enter Operation Mode menu
| Up / Charge Voltage Menu| 1 Second Press: Raise current setting/value
5 second Press: Enter Charge Voltage menu
| Down / Charge Current Menu| 1 Second Press: Lower current
setting/value 5 second Press: Enter Charge Current menu
****| ON/OFF| ON/OFF control
LCD Display Indicators
Operating Mode can be entered by long pressing the Function button for seconds.
Panel key/LCD Setting Detail
Operating Modes
The FT series inverter has 3 operating modes which can accommodate for
various priorities, whether it be prioritizing the AC mains source, inverter
source, or the low energy consumption. Below are the three available priority
modes:
Grid Prority Mode:
In Grid Priority Mode, the inverter starts with the AC mains input supply.
Under normal operation, the FT will supply power to the load and at the same
time, charge the connected battery. When the AC mains input is abnormal, the
inverter will transfer the connected load to the battery.
Energy-Saving Mode:
In Energy-Saving Mode, the FT will turn on and will detect for load. When
the load is greater than 5% of the rated output, the inverter will begin to
power up the load. When inverter detects no load, the output will be off and
the inverter Awill cycle through a load detection every 10 seconds. The load
detection feature allows for lower battery energy consumption.
Battery Priority Mode:
In Battery Priority Mode, the FT starts with AC mains supply under normal
operation, but not charging connected battery. When the battery is connected
to the external charging device (like solar charging system) after adequate
power charged, inverter will automatically switch to battery mode through
internal relay to supply power to the connected load. If connected battery
voltage is under acceptable range, the inverter will switch to battery mode
rightaway after power up.
Service
All work inside the FT inverter should be performed by qualified personnel. La Marche is not responsible for any damages caused by an unqualified technician. Before working inside the FT, ensure the AC power is off at the main breaker box and the battery has been removed from the inverter’s DC input terminals, either by removing the battery cables or exercising the battery disconnect. Verify that no voltage is present by using a voltmeter at all input and output terminals. Although minimal maintenance is required with La Marche inverters, routine checks and adjustments are recommended to ensure optimum system performance.
- Confirm air vents are open. Remove dust and debris from interior of unit.
- Verify all connections are tight.
- Perform a visual inspection on all internal components.
- Check front panel meters for accuracy and LED operation.
Appendix A: Technical Specifications
Model| 1kW| 2kW| 3kW| 4kW| 5kW| 6kW|
8kW
---|---|---|---|---|---|---|---
Battery| Rated Voltage (VDC)| 12V| 24V| 48V| 12V| 24V| 48V| 24V|
48V| 24V| 48V| 24V| 48V| 96V| 48V| 96V| 48V| 96V
Current Draw @ Full Load (ADC)| 95A| 47A| 24A| 189A| 95A| 47A| 142A|
71A| 189A| 95A| 235A| 118A| 59A| 142A| 71A| 189A| 95A
Charge Current| 30A (default) C0-C6 can be set
Battery Type| U0-U7 can be set
Input| AC Voltage Range| 90-132VAC / 170-275VAC
Frequency| 45-65Hz
Output| Voltage Range| 120VAC, 208VAC, 220VAC, AND 240VAC; ±5%
(Inverter Mode)
Frequency| 50/60Hz; ±1% (Inverter Mode)
Output Current (230VAC Model)| 4.5A| 9.1A| 13.6A| 18.2A| 22.7A| 27.3A|
36.3A
Output Current
(110VAC Model)
| 9.1A| 18.2A| 27.2A| 36.4A| 45.2A| 54.6A| 72.7A
Output Wave| Pure Sine Wave
Switching Time| <10ms (Typical Load)
Efficiency| >85% (80% Resistive Load)
Overload| 110-120% (30 Seconds); >130% (1 Second)
Protection| Battery over/undervoltage, overload, short circuit
protection, over-temperature protection, etc.
Operating Ambient Temperature| -15℃ – +50℃
Storage Ambient Temperature| -20℃ – +60℃
Operating/Storage Ambient| 0-90% (No Condensation)
Dimensions| 19.2 x 10 x 7| 22 x 12 x 8|
Weight (lbs)| 28.6| 35.2| 39.7| 59.5| 66.1| 92.06| 103.6
Appendix B: Power Cabling Guide
Use the following formulas and table to determine proper wire size for minimal
voltage drop. At distances exceeding 10 feet, the DC wire size should be
chosen to keep the voltage difference between the inverter’s DC input
terminals and the battery at less than 1/2 volt when the inverter is fully
loaded.
Size (AWG) | Area CIR.MILS | Size (MCM) | Area CIR.MILS |
---|---|---|---|
18 | 1620 | 250 | 250000 |
16 | 2580 | 300 | 300000 |
14 | 4110 | 350 | 350000 |
12 | 6530 | 400 | 400000 |
10 | 10380 | 500 | 500000 |
8 | 16510 | 600 | 600000 |
6 | 26240 | 700 | 700000 |
4 | 41740 | 750 | 750000 |
3 | 52620 | 800 | 800000 |
2 | 66360 | 900 | 900000 |
1 | 83690 | 1000 | 1000000 |
0 | 105600 | 1250 | 1250000 |
00 | 133100 | 1500 | 1500000 |
000 | 167800 | 1750 | 1750000 |
0000 | 211600 | 2000 | 2000000 |
Appendix C: Example Wiring Diagram
Appendix D: Manufacturer’s Warranty
All La Marche Manufacturing Co. equipment has been thoroughly tested and found
to be in proper operating condition upon shipment from the factory and is
warranted to be free from any defect in workmanship and material that may
develop within one (1) year from date of purchase under normal use.If the
equipment proves defective within a one year period, it shall be replaced
without charge after examination at our factory,providing such defect in our
opinion, is due to faulty material or workmanship and not caused by tampering,
abuse, misapplication, or improper installation.Should the equipment require
major replacement or repair, the equipment must be returned to the La Marche
factory to have the inspections, parts, replacements, and testing performed by
factory personnel. Should it be necessary to return a piece of equipment to
the factory, the customer or Sales representative must first obtain an RMA
(Return Material Authorization) from the factory. If upon inspection at the
factory, the defect was due to faulty material or workmanship, all repairs
will be made at no cost to the customer during the warranty period.
All internal maintenance to be performed by La Marche.La Marche reserves the
right to honor the warranty with a replacement unit.In accepting delivery of
the equipment, the purchaser assumes full responsibility for proper
installation, installation adjustments, and service arrangements. Should minor
adjustments be required, the local La Marche Sales Representative should be
contacted to provide this service.All sales are final. Only standard La Marche
units will be considered for return. A 25% restocking fee is charged when
return is a factory authorized. Special units are not returnable.In no event
shall La Marche Manufacturing Co. have any liability for consequential
damages, or loss, damage, or expense directly or indirectly arising from the
use of the products, or any inability to use them either separately or in
combination with other equipment or materials, or from any other cause. In
addition, any alterations of equipment made by anyone other than La Marche
Manufacturing Co. render this warranty null and void.La Marche Manufacturing
Co. reserves the right to make revisions in the current production of
equipment and assumes no obligation to incorporate these revisions in earlier
models.The failure of La Marche Manufacturing Co. to object to provisions
contained in customers’ purchase orders or other communications shall not be
deemed a waiver of the terms or conditions hereof, nor acceptance of such
provisions.The above warranty is exclusive, supersedes, and is instead of all
other warranties, expressed or implied, including any implied warranty of
merchantability or fitness. No person, agent, or dealer is authorized to give
any warranties on behalf of the Manufacturer, nor to assume for the
Manufacturer any other liability in connection with any of its products unless
made in writing and signed by an official of the manufacturer.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>