AKO-576032 Semiconductor Gas Detectors Instructions
- June 5, 2024
- AKO
Table of Contents
5764H002 Ed.02
Instructions AKO-576410 AKO-576032
General warnings
-Using the unit without observing the manufacturer’s instructions may alter the appliance’s safety requirements.
– Detectors should be installed in a place protected from vibrations, water,
and corrosive gases, where the ambient temperature does not exceed the value
indicated in the technical data.
– Detectors supervise a point and not an area. If the gas leak does not
reach the sensor, or the level of concentration at that point does not reach
the alarm values, no alarm will be activated. If perimeter supervision is
required, several sensors should be installed around that area.
Working conditions:
-Keep the detector work environment free of chemical agents (such as solvent, paints, alcohol, acetone, silicone, etc.), and free of engine fumes or gases from fermentation (bread, pizza) or ripening (breathing) of fruits.
-The detector should generally be installed in an area of potential concentration/accumulation of gas, in low positions (due to the greater relative density, in relation to air, of the gases subject to detection).
-The AKO-576410 / 576032 refrigerant gas detector may only be used in locations that have not been classified with risk of explosion.
-Reference regulations: EN 378
-Applicable local regulations: Compliance must be ensured
Installation
Carefully perforate the rear entry so as not to damage the electronic board.
This option involves changing from IP68 to IP40.
Option A
Fixed by an adhesive
Opción B
Fixed by screwsConnect following the diagrams
With cable entry using cable gland
If the cable entry at the back has not been drilled, this option provides the IP68 rating.
Technical specifications
Power supply ……………………………………………………………………………………………………………………………………………12-30 Vdc
Consumption…………………………………………………………………………………………………………… Typical: 75 mA,
Maximum:150 mA
Alarm relay ………………………………………………………………………………………………………………………..SPDT 30 Vdc, 2A,
cos j =1
Working ambient temperature……………………………………………………………………………………………………………………-25 to
50 ºC
Storage ambient temperature…………………………………………………………………………………………………………………….-25 to
60 ºC
Range of moisture permitted………………………………………………………………………………………0 – 95 % RH
(Without condensation)
Protection degree With cable entry using cable gland
……………………………………………………………………………………………….IP68
With cable entry from the back …………………………………………………………………………………………………….IP40
Dimensions …………………………………………………………………………………………………………..107 mm (W) x 85 mm (H) x
39 mm (D)
Complies with the EN 14624 standard.
Description
Refrigerant gas detector, which can be used in the independent operation or
connected to alarm stations AKOCam, AKOAlarm, and AKOGas.
Independent detector: The detector makes a certain warning sound in the
event of an Alarm, Pre-Alarm, or sensor error and the red indicator lights up
(See operation section).
Detector connected to the alarm station: The detector notifies the
station of its status (Alarm, Pre-Alarm, or sensor error) and the station
notifies the alarm through sound and indicators (for further information
consult the station’s manual). Alarm delay
|
---|---
Without delay| 180 s
Alarm levels
|
---|---
A levels| B levels
** Always disconnect the power supply to do the wiring.
The wiring between the detector/transmitter and the station should NEVER
be installed in a conduit together with power, control, or supply cables.
Cables for wiring the relay contacts should have an adequate section depending
on the unit to be connected.
Certain international standards maintain that the power supply of the alarm
should originate from a different circuit to that used by the refrigeration
and ventilation system.
Please ensure that you comply with current local regulations.**
|
GASES DETECTED
---|---
AKO-576410|
R-410A
AKO-576032|
R-32
|
A LEVELS
|
**B LEVELS ***
PRE-ALARM| ALARM| PRE-ALARM| ALARM
AKO-576410| 500 ppm| 1000 ppm| 1500 ppm| 3000 ppm
AKO-576032| 500 ppm| 1000 ppm| 1000 ppm| 2000 ppm
*Factory configuration
Wiring
Connection to the alarm station
Independent operation
Operation
Mute push-button
In the event of an Alarm or Pre-Alarm in process, any push-button press
silences the Alarm/Pre-Alarm tone.
Any push-button press deletes saved alarms.
Medium press (between 3 and 9 sec.): It activates or deactivates the SET-HOLD
mode. Should there be a sensor error, reset the detector.
Long press (> 9 sec.): It activates or deactivates the MAINTENANCE mode.
Should there be a sensor error, reset the detector.
Indicators
| Red| Green| Blue
---|---|---|---
OFF| No alarms| Detector turned off| A levels active
ON| Alarm / Pre-Alarm activated| Standard operation| B levels active
Flashing| Alarm / Pre-Alarm saved| Standard operation, acoustic alarm
disabled| MAINTENANCE mode activated
Flash| Detector error| The detector in the initialization process| SET HOLD
mode activated
*Flashing: 0.5 s ON / 0.5 s ON / Flash: 0.1 s ON / 0.8 s OFF
Audible alarm
Pre-Alarm | Alarm | Sensor error |
---|---|---|
Intermittent sound | Bi-tonal sound | 3 tones every 2 minutes |
Alarm relay
Pre-Alarm | Alarm | Sensor error |
---|---|---|
Configuration
In this mode, the acoustic alarm can be activated/deactivated or the detector
can be returned to factory settings.
To activate it:
- – Disconnect the power supply, reconnect it and press the “CONFIGURATION” push-button 5 times within 2 minutes; the detector will emit a confirmation beep and the blue indicator will show the status of the acoustic alarm: ON: Acoustic alarm enabled / Flashing: Acoustic alarm disabled.
- – Press the Mute push button to enable/disable the acoustic alarm.
- – Press the “CONFIGURATION” push-button for 5 seconds to save the changes and exit the configuration mode; the detector will make 5 short beeps.
**** Optionally, you can return the detector to its factory settings. To do so, press the “CONFIGURATION” push button 5 times before step 3.
Pre-alarm jumper
Allows for Pre-alarm detection to be enabled/disabled. Before using this
option, ensure that regulations allow for two alarm levels.
SET-HOLD mode
Prevents false alarms when charging or cleaning the chambers. While this mode
is activated, pre-alarms will not signal and alarms will signal as pre-alarms
when faced with all effects (sound, relay activation, and signaling). This
mode will remain active for a maximum of 5 hours, then will deactivate
automatically.
Maintenance mode
Disables gas pre-alarms and alarms for 1 hour for maintenance tasks. While
this mode is activated, no gas pre-alarm or alarm will sound.