Honeywell E410689 Touchpoint Plus Controller User Guide
- June 5, 2024
- Honeywell
Table of Contents
Honeywell E410689 Touchpoint Plus Controller
Information
Read this entire guide before installing the Touchpoint Plus, as it contains information that is essential for your safety and for the correct operation of the Touchpoint Plus.
Safety
Incorrect setup, maintenance, operation or modification of the Touchpoint
Plus gas detection system or its installation may constitute a serious hazard
to the health and safety of personnel and their environment. It is therefore
imperative that the contents of this chapter are thoroughly understood by
everyone who has access to the gas and fire detection system or its associated
equipment.
Conditions of Use
This Touchpoint Plus equipment should only be operated under the following circumstances:
- By properly trained personnel.
- Under approved conditions.
- With due authorization.
- Using approved maintenance and servicing procedures.
Packaging list
Check that your package was undamaged, and that you have received the following:
- Touchpoint Plus
- Allen Key
- Quick start guide (this document)
Go to www.honeywellanalytics.com to download the Technical Handbook, which contains full install instructions.
General Introduction
The Touchpoint Plus is an entry level (or upgrade) touch-screen digital
controller for light industrial and commercial gas detection installations. It
has eight inputs, with eight inputs available through an expansion unit.
It can handle a wide range of milliamp, millivolt, and catalytic sensors and
analog inputs, and it can control various outputs such as audible and visible
signals and solenoid valves.
The cabinets are constructed from high–impact plastic, is rated IP65, and have
fully-sealed, easy opening access. They are supplied with a wall mount bracket
or can be directly mounted to any solid vertical surface or rack. Cable entry
is via entry glands on the lower side.
Figure: 1 shows the basic layout of the Touchpoint Plus Controller:
Installation
Mount the Unit Directly to the Wall
Fixings Required
Screw x 4; corrosion resistant, sized according to the fixing surface:
- Screw Head dia. < 14 mm (12.1 mm recommended)
- Screw Body dia. < 7.5 mm (6.15 mm recommended)
- Screw Length > 76.2 mm (3 in) (If using concrete anchor, > 55 mm + anchor depth)
- Flat Washer x 4; corrosion-resistant, 19.05 mm max. OD, to fit the screws above.
Mount the Unit Using the Optional Wall Bracket
Refer to the wall mount bracket instructions (part number: TPPLOWMB).
Wiring and Connections
Power Connection
The Touchpoint Plus systems are factory set to operate at a switchable voltage of 110/220 VAC, on a single phase, 50 to 60 Hz supply. They can also be wired to DC 18 — 32 V. Every Unit has a typical peak power consumption of less than 105W, and must be directly connected to supplies via a Main Isolator Switch that leaves protective earth (ground) permanently connected. The circuit should incorporate a Residual Current Device or Residual Current Circuit Breaker (RCD or RCCB). Touchpoint Plus systems are not certified for connection to domestic power supplies.
Expansion Power Module
TPPL has the option to add an expansion unit that has the same power
equipment and modules as the base unit except that it has no Motherboard or
GUI. See Figure 5 for wiring details.
AC Power Supply
To confirm or alter the pre-set operating voltage, open the system front
cover, locate the SMPS RS–150–24 transformer and, if required, change the
voltage selector inserting a screwdriver at the point shown by the Voltage
Selector label below:
Note: Mains Earth (Ground) must only be connected to the Protective Earth
(Ground) rail, and not to the SMPS.
Regional power cable wires are coloured in accordance with the following code:
Wire | Europe | Canada | USA | Asia |
---|
Protective Earth
(Ground)
| Green + Yellow|
Green
|
Green
|
Green
Isolated Earth (Ground)| —| Green| Green + Yellow| —
Neutral| Blue| White| White| Black
Live| Brown| Red or Black| Blue, Red, or Black| Red, Yellow, or Blue
Before making any electrical connections or changes ensure:
- The mains supply isolator switch and backup battery switch are in the Off position.
- The system is set up to operate at the correct voltage.
Refer to the User Manual for further information on system electrical
specifications and power requirements.
Note 1: Input voltage of less than 24 VDC will fail to charge the backup
battery, and the battery will discharge over time.
Note 2: Remote sensors may need their own power supplies if they exceed
15W power consumption.
DC Power Supply
It is possible to power the Touchpoint Plus controller directly from a DC
24V supply without using AC supplies at all. However, batteries alone will not
suffice as they must not drop below 22 volts.
Note: The system must still be connected to Protective Earth (Ground)
when using an external DC supply.
Field Device Cables
Field Device cabling (sensors, lights, solenoids, etc.) should be
appropriate to the zone classification, and in accordance with the device
manufacturer’s recommendations. Refer to local and national regulations where
appropriate, and to the device user manual. All sensor field cables must be
screened and earthed (grounded) in order to:
- Ensure correct operation of the system
- Avoid spurious signals
- Meet European Standards for RFI and EMC.
Ensure that the maximum loop resistance is not exceeded, as specified by the device manufacturer. Take account of voltage drops due to line resistance to ensure that the correct voltage level is present at the field device, as specified by the device manufacturer. The I/O modules will accept wire sizes to a maximum of 2.5 mm².
Main Module Connections
The Main Module controls the Touchpoint Plus and its ancillary components.
Terminal | Label | Channel | Remarks |
---|---|---|---|
1 | +DC |
Power
| +18 – 32 V
2| –DC| -V Return
3| —| Earth / Ground
4| NC|
System State Relay 1
| Fig. 12
5| COM| Fig. 12
6| NO| Fig. 12
7| NC|
System State Relay 2
| Fig. 12
8| COM| Fig. 12
9| NO| Fig. 12
10| NC|
System Failure Relay 3
| Fig. 12
11| COM| Fig. 12
12| NO| Fig. 12
13| +24 VDC|
Visual Output
| Fig. 7
14| VIS| Fig. 7
15| Unused| —
16| A1|
External Alarms
| Fig. 7
17| A2| Fig. 7
18| F| Fig. 7
19| +24 VDC|
External Alarm Power
| Fig. 7
20| +24 VDC| Fig. 7
21| +24 VDC| Fig. 7
22| 3.3 V|
Remote COM/Reset/Inhibit
| Fig. 13
23| R1| Fig. 13
24| R2| Fig. 13
25| CAN_H|
CAN
| Expansion Unit Connection
26| CAN_L| Expansion Unit
Connection
4mA Input Module Connections
This is an optional module for providing up to eight mA loop inputs. (see
Technical Handbook, Ch.5.2.10)
Terminal | Label | Input | Field Device |
---|---|---|---|
1 | +Ve |
mA input 1
| + 24 VDC
2| –Ve| 0 VDC
3| Sig| | 4 – 20 mA signal
---|---|---|---
4| +Ve|
mA input 2
| + 24 VDC
5| –Ve| 0 VDC
6| Sig| 4 – 20 mA signal
7| +Ve|
mA input 3
| + 24 VDC
8| –Ve| 0 VDC
9| Sig| 4 – 20 mA signal
10| +Ve|
mA input 4
| + 24 VDC
11| –Ve| 0 VDC
12| Sig| 4 – 20 mA signal
13| +Ve|
mA input 5
| + 24 VDC
14| –Ve| 0 VDC
15| Sig| 4 – 20 mA signal
16| +Ve|
mA input 6
| + 24 VDC
17| –Ve| 0 VDC
18| Sig| 4 – 20 mA signal
19| +Ve|
mA input 7
| + 24 VDC
20| –Ve| 0 VDC
21| Sig| 4 – 20 mA signal
22| +Ve|
mA input 8
| + 24 VDC
23| –Ve| 0 VDC
24| Sig| 4 – 20 mA signal
mV Input Module Connections
This is an optional module for mV CAT sensor inputs. (see Technical
Handbook, Ch.5.2.11)
Terminal | Label | Input | Field Device |
---|---|---|---|
1 | S |
mV input 1
| Sensitive (+)
2| 01| Signal
3| NS| Sensitive (–)
4| S|
mV input 2
| Sensitive (+)
5| 01| Signal
6| NS| Sensitive (–)
7| S|
mV input 3
| Sensitive (+)
8| 01| Signal
9| NS| Sensitive (–)
10| S|
mV input 4
| Sensitive (+)
11| 01| Signal
12| NS| Sensitive (–)
13| S|
mV input 5
| Sensitive (+)
14| 01| Signal
15| NS| Sensitive (–)
16| S|
mV input 6
| Sensitive (+)
17| 01| Signal
18| NS| Sensitive (–)
19| S|
mV input 7
| Sensitive (+)
20| 01| Signal
21| NS| Sensitive (–)
22| S|
mV input 8
| Sensitive (+)
23| 01| Signal
24| NS| Sensitive (–)
Dual Input Module
This is an optional module for providing 2 or 4 x mA Loop + 2 or 4 x mV CAT
inputs.
Terminal | Label | Input | Field Device |
---|---|---|---|
1, 7, 4, 10 | +Ve |
mA Inputs 1 – 4
| + 24 VDC
2, 5, 8, 11| –Ve| 0 VDC
3, 6, 9, 12| Sig| 4 – 20 mA signal
13, 16, 19, 22| S| mV Inputs 1 – 4| Sensitive (+)
14, 17, 20, 23| 01| | Signal
---|---|---|---
15, 18, 21, 24| NS| Sensitive (–)
Modbus RTU Option
This is an option that uses Modbus RTU (RS-485) control protocols. Full
details are given in the Touchpoint Plus Modbus Installation Guide.
Relay Output Module Connections
This is an optional module providing 12 relay outputs. (see Technical
Handbook, Ch.5.2.14)
Terminal | Label | Output |
---|---|---|
1 | NC |
Relay 1
2| COM
3| NO
4| NC|
Relay 2
5| COM
6| NO
7| NC|
Relay 3
8| COM
9| NO
10| NC|
Relay 4
11| COM
12| NO
13| NC|
Relay 5
14| COM
15| NO
16| NC|
Relay 6
17| COM
18| NO
19| NC|
Relay 7
20| COM
21| NO
22| NC|
Relay 8
23| COM
24| NO
25| NC|
Relay 9
26| COM
27| NO
28| NC|
Relay 10
29| COM
30| NO
31| NC|
Relay 11
32| COM
33| NO
34| NC|
Relay 12
35| COM
36| NO
Table 6. Relay Output Module Connections
mA Output Module
This is an optional module for providing isolation mA loop output (see
Technical Handbook, Ch.5.2.13).
Terminal | Label | Output |
---|---|---|
1 | I+ |
mA Out 1
2| I–
3| I+|
mA Out 2
4| I–
5| I+|
mA Out 3
6| I–
7| I+|
mA Out 4
8| I–
Table 7. mA Output Module Connections
Field Device Circuit Diagrams
Backup Battery Option
The optional backup battery is shipped in sleep mode. You must read the manual before connecting it to the system. Figure 15. Backup Battery Connection
Technical Specifications
General Specifications
Capacity| Up to 8 inputs Base Unit, + 8 inputs with Expansion Unit
Type of Inputs| 2 or 3 wires, mA, mV
Size (Wall Units only)| 426 mm x 300 mm x 156 mm
Weight| 9 Kg (20 lbs) Base Unit, 8.5 Kg (18.7 lb) Expansion Unit
User Interface
Display| 7 inch Colour LCD Touch Screen GUI
Visual Indicators
| 3 LED Master Indicators and 16 LED inputs, Green for Normal, Yellow for
Fault/ Inhibit, and Red for Alarm
---|---
Audible Alarm| 70 dB @ 1 metre (40 ins)
Button| One alarm mute and reset membrane button
Languages
| Selectable English, Chinese (Simplified), Dutch, French, German, Italian,
Portuguese, Russian, Spanish
Power Supply
Power AC| AC 110/220 V, 50 — 60 Hz
(Manual Voltage Selection via SMPS)
Power DC| DC 18 — 32 V (24 VDC Nominal). DC 24 – 32 V
advised
Power Consumption| 105 W max (including field devices), 210 W max with
Expansion Unit
Environmental
Operating Temperature| –10 to +55 °C (+14 to +131 °F) continuous operation
Storage Temperature| Instrument –25 to +60 °C (–13 to +140 °F)
Humidity Range| 5 – 95 %RH non-condensing
Ingress Protection| IP65 (wall mounted), NEMA 4X indoors only
I/O Capacities
mV Input
| Pellistor type Catalytic gas sensors (HA models). 2, 4, or 8 channels with
Base Unit or 10, 12, or 16 channels with Expansion Unit
4 – 20 mA Input| 2 or 3 wire, SOURCE. 2, 4, or 8 channel module
4 – 20 mA Output| 4 or 8 repeated 0 – 22 mA outputs, 12 or 16 with
expansion unit. (4 – 20 mA = 0 – 100 %FSD)
Relay Output| Configurable time delay On/Off option. 1.7 A @ 250 VAC, 1.7 A @
30 VDC, 12 relays per module
Certifications
Electrical Safety| Compliant with CE, EN 50270:2015, UL/ IEC/EN 61010-1, UL
508
Performance
| EN 60079-29-1, EN 50104, EN 45544-1/2/3 and EN 50271
IEC/EN61508:2010 and SIL2 certification
CSA 22.2 no.152
Marine| MED (Item No.: 3.54)
Hazardous Approval
| ISA 12.12.01–2013 (Class 1, Div 2, Groups A,B,C,D & T4)
CSA C22.2 No. 213–M1987
Others
Backup Batteries| 22.2 V Lithium Ion, 2600 mAh.
Circa 30 mins Buffer time when fully charged.
Data Logging
| Configuration backups and event / TWA logging onto SD Card. Can be transferred to PC or Printer (.bin and
.csv)
Communication| Modbus RTU & TCP, Web Monitoring
Default Password
The default access password for all levels is “TPPL”, but it is the User’s
responsibility to immediately change the passwords as to avoid unauthorized
access. Full instructions are contained in the Technical Handbook, and
Honeywell will not accept any liability caused by failing to follow these
instructions.
Find out
more:www.honeywellanalytics.com
Please note: While every effort has been made to ensure accuracy in this
publication, no responsibility can be accepted for errors or omissions. Data
may change, as well as legislation and you are strongly advised to obtain
copies of the most recently issued regulations, standards and guidelines. This
publication is not intended to form the basis of a contract.
Part No. 3011M5000_EN
H_MAN0985 Iss.4.0_02/2019 HAA190006 © 2019 Honeywell Analytics