DAIKIN FAQ100BVV Air Condition Instruction Manual

June 5, 2024
Daikin

DAIKIN FAQ100BVV Air Condition

Thank you for purchasing this Daikin air conditioner. Carefully read this operation manual before using the air conditioner. It will tell you how to use the unit properly and help you if any trouble occurs. After reading the manual, file it away for future reference. Operation: see the remote controller operation man-ual for details on the names and functions of switches and displays on the remote controller.

Disposal requirements

Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted house-hold waste. Do not try to dismantle the system yourself: the dismantling of the air condi-tioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualified installer in accordance with relevant local and national legislation.Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more infor-mation. Batteries must be removed from the remote controller and disposed of sep-arately in accordance with relevant local and national legislation.

WHAT TO DO BEFORE THE OPERATION

This operation manual is for the following systems with standard control. Before initiating operation, contact your Daikin dealer for the operation that corresponds to your system.

NOTE

  • Read the operation manual that came with the remote controller you are using. If your installation has a customized control system, ask your Daikin dealer for the operation that corre-sponds to your system.
  • Heat pump type This system provides cooling, heating, automatic, program dry, and fan operation modes.
  • Cooling only type  This system provides cooling, program dry, and fan operation modes.

PRECAUTIONS FOR GROUP CONTROL SYSTEM OR TWO REMOTE CONTROLLER CONTROL SYSTEM
This system provides two other control systems beside individual control (one remote controller con-trols one indoor unit) system. Confirm the following if your unit is of the following control system type.

  • Group control system One remote controller controls up to 16 indoor units. All indoor units are equally set.
  •  Two remote controller control system Two remote controllers control one indoor unit (In case of group control system, one group of indoor units) The unit is individually operated.
  • Contact your Daikin dealer in case of changing the combination or setting of group control and two remote controller control systems.

Names and functions of parts

a Indoor unit
b Outdoor unit
c Remote controller
d Inlet air
e Discharged air
f Air outlet
g Air flow flap (at air outlet)
h Refrigerant piping, connection electric wire
i Drain pipe
j Air inlet

The built-in air filter removes dust and dirt.

k

| Ground wire

Wire to ground from the outdoor unit to pre- vent electrical shocks.

SAFETY CONSIDERATIONS

  • We recommend that you read this instruction man-ual carefully before use to gain full advantage of the function of the air conditioner, and to avoid malfunc-tion due to mishandling.
  • This air conditioner comes under the term “appli-ances not accesible to the general public”.
  • The precautions described below are WARN-ING and CAUTION. These are very important precautions concerning safety. Be sure to observe all of them without fail.
  • These are the matters with possi- bilities leading to serious conse-quences such as death or serious injury due to erroneous handling.
  • These are the matters with possi- bilities leading to injury or material damage due to erroneous han-dling including probabilities lead-ing to serious consequences in some cases.
  • After reading, keep this manual at a place where any user can read at any time. Further-more, make certain that this operation manual is handed to a new user when he takes over the operation.

WARNING

  • Avoid exposure of your body directly to the cold air for a long time, or avoid excessive exposure of your body to the cold air. Otherwise, your physical condition may be dete-riorated and/or your health may be ruined.
  • When the air conditioner is in abnormal con-ditions (smell of something burning, etc), unplug the power cord from the outlet, and contact the dealer where you purchased the air conditioner.
  • Continued operation under such circumstances may result in a failure, electric shock, and fire.
  • Ask your dealer for installation of the air con-ditioner.
  • Incomplete installation performed by yourself may result in a water leakage, electric shock, and fire. Ask your dealer for improvement, repair, and maintenance.
  • Incomplete improvement, repair, and maintenance may result in a water leakage, electric shock, and fire. Do not insert your finger, a stick, etc., into the air inlet, outlet, and fan blades.
  • A fan in high-speed running may result in injury. For refrigerant leakage, consult your dealer. When the air conditioner is to be installed in a small room, it is necessary to take proper mea-sures so that the amount of any leaked refriger-ant does not exceed the limiting concentration even when it leaks. If the refrigerant leaks exceeding the level of limiting concentration, an oxygen deficiency accident may happen.
  • For installation of separately sold compo-nent parts, ask a specialist.
  • Be sure to use the separately sold component parts designated by our company.
  • Incomplete installation performed by yourself may result in a water leakage, electric shock, and fire.
  • Ask your dealer to move and reinstall the air conditioner.
  • Incomplete installation may result in a water leakage, electric shock, and fire.
  • Do not use any fuse with improper capacity. The use of a piece of wire and whatnot may result in a failure and fire.
  • The refrigerant in thae air conditioner is safe and normally does not leak. If the refrigerant leaks inside the room, the contact with a fire of a burner, a heater or a cooker may result in a harmful gas.
  • Do not use the air conditioner until when a ser-vice person confirms to finish repairing the por-tion where the refrigerant leaks.
  • Be sure to establish an earth.
  • Do not earth the unit to a utility pipe, arrester, or telephone earth.
  • Incomplete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the air conditioner. Be sure to install an earth leakage breaker. Failure
  • to install an earth leakage breaker may result in electric shocks, or fire.
  • Consult the dealer if the air conditioner sub-merges owing to a natural disaster, such as a flood or typhoon.
  • Do not operate the air conditioner in that case, or otherwise a malfunction, electric shock, or fire may result.

CAUTION

  • Do not use the air conditioner for other purposes. Do not use the air conditioner for a special appli-cation such as the storage of foods, animals and plants, precision machines, and art objects as otherwise the deterioration of quality may result.
  • Do not remove the air outlet of the outdoor unit. The fan may get exposed and result in injury.
  • When the air conditioner is used in combina-tion with burners or heaters, perform suffi-cient ventilation.
  • Insufficient ventilation may result in an oxygen deficiency accident.
  • Check and make sure that foundation blocks are not damaged after a long use.
  • If they are left in a damaged condition, the unit may fall and result in injury.
  • Neither place a flammable spray bottle near the air conditioner nor perform spraying. Doing so may result in a fire.
  • To clean the air conditioner, stop operation, and unplug the power cord from the outlet. Otherwise, an electric shock and injury may result. Do not operate the air conditioner with a wet hand.
  • An electric shock may result.
  • Do not place items that might be damaged by water under the indoor unit.
  • Water may condensate and drip if the humidity reaches 80% or if the drain exit gets clogged.
  • Do not place a burner or heater at a place directly exposed to the wind from the air conditioner. Incomplete combustion of the burner or heater may result.
  • Do not allow a child to mount on the outdoor unit or avoid placing any object on it. Falling or tumbling may result in injury.
  • Do not expose animals and plants directly to the wind.
  • Adverse influence to animals and plants may result. Do not wash the air conditioner with water. Electric shock or fire may result.
  • Do not install the air conditioner at any place where flammable gas may leak out.
  • If the gas leaks out and stays around the air con-ditioner, a fire may break out.
  • Execute complete drain piping for perfect drainage.
  • Incomplete piping may result in a water leakage.
  • The appliance is not intended for use by young children or infirm persons without supervision.
  • Young children should be supervised to ensure that they do not play with the appliance.
  • Consult with installation contractor for cleaning the inside of the air conditioner. Wrong cleaning may make the plastics parts broken or cause failure of water leakage or electric shock. Do not touch the air inlet or aluminium fin of the air conditioner.
  • Otherwise, injury may be caused.
  • Do not start or stop operating the air condi-tioner with the power supply breaker turned ON or OFF.
  • Otherwise, fire or water leakage may result. Furthermore, the fan will rotate abruptly if power failure compensation is enabled, which may result in injury.
  • Do not place objects in direct proximity of the outdoor unit and do not let leaves and other debris accumulate around the unit.
  • Leaves are a hotbed for small animals which can enter the unit. Once in the unit, such animals can cause malfunctions, smoke or fire when making contact with electrical parts.
  • Never touch the internal parts of the remote controller.
  • Do not remove the front panel. Some parts inside are dangerous to touch, and a machine trouble may happen.
  • For checking and adjusting the internal parts, contact your dealer.
  • Avoid placing the remote controller in a spot splashed with water.
  • Water coming inside the machine may cause an elec-tric leak or may damage the internal electronic parts. Watch your steps at the time of air filter cleaning or inspection.
  • High-place work is required, to which utmost attention must be paid.
  • If the scaffold is unstable, you may fall or topple down, thus causing injury.

OPERATION RANGE

If the temperature or the humidity is beyond the fol-lowing conditions, safety devices may work and the air conditioner may not operate, or sometimes, water may drop from the indoor unit.

COOLING

OUTDOOR UNIT INDOOR OUTDOOR TEMPERA- TURE

TEMPERA-

TURE

| HUMIDITY
RZQ100| DB| 18 to 37| 80% or below| DB| – 15 to 50
WB| 12 to 28
RQ100| DB| 18 to 37| 80% or below| DB| – 5 to 46
WB| 12 to 28
RR100| DB| 18 to 37| 80% or below| DB| – 15 to 46
WB| 12 to 28

HEATING

OUTDOOR UNIT| INDOOR

TEMPERATURE

| OUTDOOR

TEMPERATURE

---|---|---
RZQ100| DB| 10 to 27| DB| –19.5 to 21
WB| – 20 to 15.5
RQ100| DB| 10 to 27| DB| – 9 to 21
WB| – 10 to 15

COOLING

OUTDOOR UNIT INDOOR OUTDOOR TEMPERA- TURE

TEMPERA-

TURE

| HUMIDITY
RZQ100| DB| 20 to 37| 80% or below| DB| – 5 to 46
WB| 14 to 28

HEATING

OUTDOOR UNIT| INDOOR

TEMPERATURE

| OUTDOOR

TEMPERATURE

---|---|---
RZQ100| DB| 10 to 27| DB| –14 to 21
WB| – 15 to 15.5

INSTALLATION SITE

  •  Is the air conditioner installed at a well-ventilated place where there are no obstacles around?
  •  Do not use the air conditioner in the following places.
  •  Filled with much mineral oil such as cutting oil
  •  Where there is much salt such as a beach area
  •  Where sulfured gas exists such as a hot-spring resort
  • Where there are considerable voltage fluctua-tions such asa a factory or plant
  • Vehicles and vessels
  • Where there is much spray of oil and vapor such as a cookery, etc.
  • Where there are machines generating electro-magnetic waves
  • Filled with acid and/or alkaline steam or vapor
  • Is a snow protection measure taken?For details, consult your dealer.

Regarding wiring

  •  All wiring must be performed by an authorized electrician.
  • To do wiring, ask your dealer. Never do it by yourself.
  •  Make sure that a separate power supply circuit is provided for this air conditioner and that all electrical work is carried out by qualified per-sonnel according to local laws and regulations.
  • Pay attention to running noises, too
  •  Are the following places selected?
  •  A place that can sufficiently withstand the weight of the air conditioner with less running noises and vibrations.
  •  A place where the hot wind discharged from the air outlet of the outdoor unit and the running noises.
  • Are you sure that there are no obstacles near the air outlet of the outdoor unit?
  • uch obstacles may result in declined perfor-mance and increased running noises.
  •  If abnormal noises occur in use, consult your dealer.

Is the drain piping executed to perform com plete drainage?

  • If proper drainage is not carried out from the out-door drain pipes during air-conditioning operation, chances are that dust and dirt are clogged in the pipe. This may result in a water leakage from the indoor unit. Under such circumstances, stop the operation of the air conditioner, and then consult your dealer or our service station.
  •  To protect the unit, turn on the main power switch 6 hours before operation.
  •  If the main power supply is turned off during oper-ation, operation will restart automatically after the power turns back on again.

[EXPLANATION OF HEATING OPERATION] DEFROST OPERATION

  •  As the frost on the coil of an outdoor unit increase, heating effect decreases and the system goes into DEFROST OPERATION.
  •  The indoor unit fan stops and the remote control-ler display shows “ ”.
  •  After 6 to 8 minutes (maximum 10 minutes) of DEFROST OPERATION, the system returns to HEATING OPERATION.

Regarding outside air temperature and heat-ing capacity

  •  The heating capacity of the air conditioner declines as the outside air temperature falls. In such a case, use the air conditioner in combina-tion with other heating systems.
  • A warm air circulating system is employed, and therefore it takes some time until the entire room is warmed up after the start of operation.
  •  An indoor fan runs to discharge a gentle wind automatically until the temperature inside the air conditioner reaches a certain level. At this time, the remote controller displays “ ”. Leave it as it stands and wait for a while.
  • When the warm air stays under the ceiling and your feet are cold, we recommend that you use a circulator (a fan to circulate the air inside the room). For details, consult your dealer.

AIRFLOW DIRECTION ADJUST

  • There are 2 ways of adjusting the air discharge angle.

  • UP AND DOWN DIRECTION
    Press the AIR FLOW DIRECTION ADJUST button to select the air direction as shown below.

  • The AIR FLOW FLAP display swings as shown below and the air flow direction continuously varies. (Automatic swing set-ting)

  • Press AIR FLOW DIRECTION ADJUaST button to select the air direction of your choice.

  • The AIR FLOW FLAP display stops swinging and the air flow direction is fixed (Fixed air flow direction setting).

MOVEMENT OF THE AIR FLOW FLAP
For the following conditions, micro computer con-trols the air flow direction so it may be different from the display.

Operation mode Cooling Heating

Operation condition

| •    When room temperature is lower than the set temperature

•    When operating continuously at horizontal air flow direction

| •    When room temperature is higher than the set temperature

•    At defrost opera- tion

Operation mode includes automatic operation.

We recommend using the fan in the position listed above when fixing the fan direction.

LEFT AND RIGHT DIRECTION
Grasp the air flow blades at the tip and move the blades to the left and right.

NOTE

  •  Only make adjustments after you have stopped the air flow direction swing in a position where adjustments are possible. Your hand may get caught if you attempt to make adjustments while the unit is swinginga.

OPTIMUM OPERATION

Observe the following precautions to ensure the system operates.

  •  Adjust the room temperature properly for a com-fortable environment. Avoid excessive heating or cooling.
  •  Prevent direct sunlight from entering a room dur-ing cooling operation by using curtains or blinds.
  •  Ventilate the room regularly.
  • Using the unit for long periods of time requires attentive ventilation of the room.
  •  Keep doors and windows closed. If the doors and windows remain open, room air will flow out and cause to decrease the effect of cooling and heating.
  •  Do not place other heaters directly below the indoor unit.
  • They may deform due to the heat.
  •  Never place objects near the air inlet and the air outlet of the unit. It may cause deterioration in the effect or stop in the operation.
  •  Turn off the main power supply switch when it is not used for long periods of time. When the main power switch is turned on, some watts of electricity is being used even if the system is not
  • operating. Turn off the main power supply switch for saving energy. When reoperating, turn on the main power supply switch 6hours before operation for smooth running (Refer to MAINTENANCE).
  •  When the display shows “ ”, ask a qualified service person to clean the filters (Refer to MAIN-TENANCE).
  •  Fully use the function of air flow direction adjust. Cold air gathers on the floor, and warm air gathers in the ceiling.
  • Set the air flow direction parallel during cooling or dry operation, and set it downwards during heat-ing operation.
  • Do not let the air blow directly to a person.

MAINTENANCE (FOR SERVICE PERSONNEL)

  •  BEFORE OBTAINING ACCESS TO TERMINAL DEVICES, ALL POWER SUPPLY CIRCUITS MUST BE INTERRUPTED
  • To clean the air conditioner, be sure to stop oper-ation, and turn the power switch off. Otherwise, an electric shock and injury may result.
  •  Do not wash the air conditioner with water Doing so may result in an electric shock.
  •  Be careful with a scaffold or staging
  • Caution must be exercised because of work at a high place.

HOW TO CLEAN THE AIR FILTER

Clean the air filter when the display shows “ Increase the frequency of cleaning if the unit is installed in a room where the air is extremely contaminated. (As a yardstick for regulating yourself, consider cleaning the filter once every two weeks.)

  1. Pull the handle in the direction of the arrow.
  2.  Clean the air filter. Use vacuum cleaner A) or wash the air filter with water B). Using a vacuum cleaner
  3. Washing with water When the air filter is very dirty, use soft brush and neutral detergent. Remove water and dry in the shade.
    •  Do not wash the air conditioner with hot water of more than 50°C, as doing so may result in discol-oration and/or deformation.
    •  Do not expose it to fire, as doing so may result in burning.
  4. Reset the air filter in place. After cleaning the filter, do not forget to put it back the way it was before.
  5. After turning on the power, press AIR FILTER CLEANING TIME ICON RESET BUTTON. The display “ ” vanishes.

HOW TO CLEAN AIR OUTLET AND OUTSIDE PANELS

  •  Clean with soft cloth.
  •  When it is difficult to remove stains, use water or neutral detergent.
  •  Do not use gasoline, benzene, thinner, polishing powder, liquid insecticide. It may cause discolor-ing or warping.
  •  Do not use water or air of 50°C or higher for clean-ing air filters and outside panels.
  •  Check that the air inlet and outlet are not blocked. Remove any obstacle.
  •  Check if the earth is connected.
  • Might there be a broken wire somewhere?Contact your dealer if there are any problems.
  •  The display on the remote controller will be shown when the power is turned on.
  •  To protect the unit, turn on the main power switch at least 6 hours before operation.
  •  When the main power switch is turned on, some watts of electricity is being used even if the sys-tem is not operating.
  • Turn off the main power supply switch for saving energy.
  •  The display on the remote controller will vanish when the main power switch is turned off.

 NO MALFUNCTION OF THE AIR CONDITIONER

The following symptoms do not indicate air conditioner malfunction

  1. THE SYSTEM DOES NOT OPERATE
    •  The system does not restart immediately after the ON/OFF button is pressed.
    • If the OPERATION lamp lights, the system is in normal condition.
    • It does not restart immediately because a safety device operates to prevent overload of the sys-tem. After 3 minutes, the system will turn on again automatically.
    •  The system does not restart immediately when TEMPERATURE SETTING button is returned to the former position after pushing the button. If the OPERATION lamp lights, the system is in normal condition.
    • It does not restart immediately because a safety device operates to prevent overload of the sys-tem. After 3 minutes, the system will turn on again automatically.
    •  The system does not start when the display shows “ ” and it flashes for few sec-onds after pressing an operation button. This is because the system is under centralized con-trol. Flashes on the display indicates that the system cannot be controlled by the remote controller.
    •  The system does not start immediately after the power supply is turned on.
    • Wait one minute until the micro computer is pre-pared for operation.
  2.  WHITE MIST COMES OUT OF A UNIT
    •  When humidity is high during cooling opera-tion (In oily or dusty places)
    • If the inside of an indoor unit is extremely contam-inated, the temperature distribution inside a room becomes uneven. It is necessary to clean the inside of the indoor unit. Ask your Daikin dealer for details on cleaning the unit. This operation requires a qualified service person.
    •  When the system is changed over to HEATING OPERATION after DEFROST OPERATION. Moisture generated by DEFROST becomes steam and exists.
  3. NOISE OF AIR CONDITIONERS
    •  A ringing sound after the unit is started. This sound is generated by the temperature regu-lator working.
    • It will quiet down after about a minute.
    •  A continuous flow “Shuh” sound is heard when the systems is in COOLING or DEFROST OPERATION.
    • This is the sound of refrigerant gas flowing through both indoor and outdoor units.
    •  A “Shuh” sound which is heard at the start or immediately after the stop of operation or which is heard at the start or immediately after the stop of DEFROST OPERATION.
    • This is the noise of refrigerant caused by flow stop and flow change.
    •  A continuous low “Shah” sound is heard when the system is in COOLING OPERATION or at a stop.
    • The noise is heard when the drain pump is in operation.
    •  A “Pishi-pishi” squeaking sound is heard when the system is in operation or after the stop of operation.
    • Expansion and contraction of plastic parts caused by temperature change makes this noise.
  4. DUST FROM THE UNITS
    • Dust may blow out from the unit after starting operation from long resting time.
    • Dust absorbed by the unit blows out.
  5. THE UNITS GIVE OFF ODORS’
    • The unit absorbs the smell of rooms, furniture, cigarettes, etc., and then emits them.
    • THE LIQUID CRYSTAL OF THE REMOTE CON-TROLLER SHOW “ ”
    •  It happens immediately after the main power supply switch is turned on.
    • This shows that the remote controller is in normal condition.
    • This continues taemporary.

TROUBLESHOOTING

  • When the air conditioner is in abnormal con-ditions (smell of something burning, etc), unplug the power cord from the outlet, and contact your dealer
  • Continued operation under such circumstances may result in a failure, electric shock, and fire.
  •  If a safety device such as a fuse, a breaker or an earth leakage breaker frequently actuates; Measure: Do not turn on the main power switch.
  •  If the ON/OFF switch does not properly work; Measure: Turn off the main power switch.
  • If water leaks from unit. Measure: Stop the operation.
  • If the display “ ”, “UNIT No.”, and the OPERA-TION lamp flash and the “MALFUNCTION CODE” appears.
  • If the system does not operate at all.  Check if there is a power failure.
  • Wait until power is restored. If power failure occurs during operation, the system automati-cally restarts immediately after the power sup-ply recovers.
  •  Check if no fuse has blown.
  • Turn off the power supply.
  •  Check if the breaker is blown. Turn the power on with the breaker switch in thea off position.Do not turn the power on with the breaker switch in the trip position.(Contact your dealer.)
  •  If the system stops operating after operating the system
  •  Check if the air inlet or outlet of outdoor or indoor unit is blocked by obstacles.
  • Remove the obstacle and make it well-venti-lated
  •  Check if the air filter is clogged.
  • Ask a qualified service person to clean the air filters (Refer to MAINTENANCE).
  •  The system operates but it does not suffi-ciently cool or heat.
  • If the air inlet or outlet of the indoor or the outdoor unit is blocked with obstacles.
  • Remove the obstacle and make it well-ventilated.
  • If the air filter is clogged.
  • Ask a qualified service person to clean the air filters (Refer to MAINTENANCE).
  • If the set temperature is not proper (Refer to ADJUSTMENT).
  • If the FAN SPEED button is set to LOW SPEED (Refer to ADJUSTMENT).
  • If the air flow angle is not proper (Refer to ADJUSTING THE AIR FLOW DIRECTION).
  • If the doors or the windows are open. Shut doors or windows to prevent wind from coming in.
  • If direct sunlight enters the room (when cooling). Use curtains or blinds.
  • When there are too many inhabitants in the room (when cooling).
  • coiling effect decreases if heat gain of the room is too large.
  • If the heat source of the room is excessive when cooling).
    • Cooling effect decreases if heat gain of the room is too large.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Daikin User Manuals

Related Manuals