Knightsbridge SURF418EMHF Fluorescent Emergency Lighting Instruction Manual
- June 3, 2024
- Knightsbridge
Table of Contents
Knightsbridge SURF418EMHF Fluorescent Emergency Lighting
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by
the end user for future reference and maintenance.
These instructions should be used to aid installation of the following
product: SURF418EMHF
SAFETY
- This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
- Please isolate mains prior to installation or maintenance
- Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
- Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
- This product is for indoor use only
- This product is Class I and must be earthed
- This product is IP20 rated
INSTALLATION
- Provide power to the required point of installation
- Using the plastic glove provided carefully remove the louvre by pressing in the retaining clips
- Mark the location of the fixing holes and drill the holes ensuring not to infringe with any gas/water pipes or electrical cables
- Feed the mains cable through the cable entry point and secure the luminaire to the surface
- Connect to the mains supply ensuring the correct polarity is observed: L – Live, SL – Switched Live (brown), E – Earth (green & yellow), N – Neutral (blue) (see Fig. 1)
- Insert4X SUItable 18 fluorescent lamps
- Connect the earth fly lead to the louver and click the louver into place
- Switch on and check for correct operation, ensuring the green indicator LED is illuminated
- We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying out an emergency duration test
- If the batteries have been left in a discharged state for an extended period, we recommend that one or more charge and discharge cycles are completed which should help to restore the battery capacity
WARNING
- This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.
- The louvre is easily marked by handling. the protective glove provided should be used
GENERAL
This product contains a control gear that can be replaced by a professional.
Clean with a soft dry cloth only, do not use aggressive cleaning products or
solvents which may damage the product.
This product is non-dimmable.
This product should be dismantled for di of its life. Please see the website
for dismantling instructions.
This product should be recycled in the coaches the end of its life. Check
local authorities for where facilities exist.
The batteries in this luminaire are Nickel Cadmium and must be disposed of
correctly. Please contact the local authorities for the disposal of this toxic
w
WARRANTY
This product has a warranty of 1 year from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free-of-charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
- Daily check – check LED charge indicator is illuminated
- Monthly functional test – simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- Annual three-hour duration test – simulate a mains supply failure for a three-hour continuous test by operating of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record sheet
TEST RECORD SHEET
Installed by
Installation date:
Contact number:
ML Accessories Limited LU5 4LT
www.mlaccessories.co.uk