APG MPX-E MPX Magnetostrictive Level Sensors Installation Guide

June 4, 2024
APG

MPX Magnetostrictive Level Sensors
Installation Guide
For MPX-E, MPX-E Chemical, and MPX-R

Thank You

Thanks for purchasing an MPX series magnetostrictive level sensor from us! We appreciate your business and your trust. Please take a moment to familiarize yourself with the product and this manual before installation. If you have any questions, at any time, don’t hesitate to call us at 888525-7300.

NOTE: Scan the QR code to the right to see the full user manual on your tablet or smartphone. Or visit www.apgsensors.com/support to find it on our website.

Description

The MPX series magnetostrictive level sensor provides highly accurate and repeatable level readings in a wide variety of liquid level measurement applications. It is certified for installation in hazardous areas in the US and Canada by CSA for Class I, Division 1 & 2 and Class I, Zones 1 and 2 environments.

How To Read Your Label

Each label comes with a full model number, a part number, and a serial number. The model number for the MPX will look something like this:
SAMPLE: MPX-R3-ZY-F2.5WB-120
The model number correlates with all the configurable options and tells you exactly what you have.
Compare the model number to the options on the datasheet to identify your exact configuration.
You can also call us with the model, part, or serial number and we can help you.
You’ll also find all hazardous certification information on the label.

Warranty

This product is covered by APG’s warranty to be free from defects in material and workmanship under normal use and service of the product for 24 months. For a full explanation of our Warranty, please visit https://www.apgsensors.com /about-us/terms-conditions. Contact Technical Support to receive a Return Material Authorization before shipping your product back. Scan the QR code below to read the full explanation of our Warranty on your tablet or smartphone.

https://www.apgsensors.com/about-us/terms-conditions

Dimensions

APG MPX-E MPX Magnetostrictive Level Sensors| APG MPX-E MPX Magnetostrictive Level Sensors -
---|---

Installation Guidelines & Instructions

The MPX should be installed in an area–indoors or outdoors–which meets the following conditions:

  • Ambient temperature between -40°F and 185°F (-40°C to 85°C)
  • Relative humidity up to 100%
  • Altitude up to 2000 meters (6560 feet)
  • IEC-664-1 Conductive Pollution Degree 1 or 2
  • IEC 61010-1 Measurement Category II
  • No chemical corrosive to stainless steel (such as NH3, SO2, Cl2, etc.)
  • Ample space for maintenance and inspection

Additional care must be taken to ensure:

  • The probe is located away from strong magnetic fields, such as those produced by motors, transformers, solenoid valves, etc.
  • The medium is free from metallic substances and other foreign matter.
  • The probe is not exposed to excessive vibration.
  • The float(s) fit through the mounting hole. If the float(s) does/do not fit, it/they must be mounted on the stem from inside the vessel being monitored.
  • The float(s)/is oriented properly on the stem (See Figure 5.1 below). MPX-E floats will be installed by the factory. MPX-R floats are typically installed by customers.

APG MPX-E MPX Magnetostrictive Level Sensors - Taper

** IMPORTANT:** Floats must be oriented properly on the stem, or sensor readings will be inaccurate and unreliable. Untapered floats will have a sticker or “N” indicating the top of the float. Remove sticker prior to use.

Installation Instructions:

  • If your sensor’s stem and floats fit through the mounting hole, carefully lower the assembly into the vessel, then secure the sensor to the vessel.
  • If the floats do not fit, mount them on the stem from inside the vessel being monitored. Then secure the sensor to the vessel.
  • For sensors with float stops, refer to the assembly drawing included with the sensor for float stop installation locations.
  • For MPX-E Chemical, ensure the probe is concentric with fitting so as not to scrape the chemical-resistant coating off against threads of the fitting.

Electrical Installation Instructions:

  • Remove the housing cover of your MPX.
  • Feed system wires into MPX through 3/4” NPT conduit openings. Fittings must be UL/CSA Listed for CSA installation and IP65 Rated or better.
  • Connect wires to MPX terminals. Use crimped ferrules on wires, if possible.
  • Replace housing cover.
  • For EMI protection on MPX-E4 and MPX-R4 models, either connect the grounding screw (see Dimensions section 4) to an earth ground or ensure that the tank mounting of MPX is grounded. See Sensor and System Wiring Diagrams (section 6) for Modbus and 4-20 mA wiring examples.

IMPORTANT: WARNING — A SEAL SHALL BE INSTALLED WITHIN 18 inches OF THE ENCLOSURE;
AVERTISSEMENT – – UN SCELLEMENT DOIT ETRE INSTALLÉ A MOINS DE 18 inches DU BOITIER.

APG MPX-E MPX Magnetostrictive Level Sensors - MPX-R Housing
Dimensions

Sensor and System Wiring Diagrams

Modbus System Wiring

APG MPX-E MPX Magnetostrictive Level Sensors - Modbus System
Wiring

**IMPORTANT:** For EMI protection on an MPX-E4 or -R4, either connect the grounding screw (see section 4) to an earth ground or ensure that the tank mounting of the MPX is grounded.

Modbus System Wiring with RST-6001

APG MPX-E MPX Magnetostrictive Level Sensors - Modbus System Wiring with
RST-6001

IMPORTANT: Refer to section 9 for Hazardous Location Wiring.
NOTE: For APG Modbus programming instructions, please see the MPX user manual. APG Modbus software can be downloaded from www.apgsensors.com/support.

DANGER: WARNING — POTENTIAL ELECTROSTATIC CHARGING HAZARD – CLEAN ONLY WITH A DAMP CLOTH;
AVERTISSEMENT — DANGER DE CHARGE ELECTROSTATIQUE POTENTIEL – NETTOYER SEULEMENT AVEC UN CHIFFON HUMIDE.

General Care

Your level sensor is very low maintenance and will need little care as long as it was installed correctly. However, in general, you should periodically inspect your MPX unit to ensure the stem is free of any heavy buildup that might impede the movement of the float(s). If sediment or other foreign matter becomes trapped between the stem and float(s), detection errors can occur.
If you need to remove the floats(s) from the stem of your MPX, be sure to note the orientation of the float(s) prior to removal. This will help ensure proper re-installation of the float(s).
Also, ensure that the housing cover is snuggly secured. If the cover becomes damaged or is misplaced, order a replacement immediately.

4-20 mA Wiring

APG MPX-E MPX Magnetostrictive Level Sensors - 4-20 mA
Wiring

4-20 mA Programming Wiring

APG MPX-E MPX Magnetostrictive Level Sensors - 4-20 mA Programming
Wiring

IMPORTANT: MPX level sensor MUST be installed according to drawing 9003468 (Hazardous Installation and Non-Incendive Wiring Drawing) in section 9 to meet listed approvals. The faulty installation will invalidate all safety approvals and ratings.
**IMPORTANT:** All repairs and adjustments to the MPX level sensor must be made by the factory. Modifying, disassembling, or altering the MPX is strictly prohibited.

Repair Information

If your MPX level sensor needs repair, contact us via email, phone, or online chat on our website.
We will issue you an RMA number with instructions.

Hazardous Location Wiring

INSTALLATION IN : CLASS I, DIV 1 8c 2, GROUPS C & D, MAX. TEMP. 85° C
Ex d IIB: Ex nA IIB
CLASS I, ZONE 1; AEx d IIB: CLASS I, ZONE 2; AEx nA IIB

APG MPX-E MPX Magnetostrictive Level Sensors - Hazardous Location
Wiring

WARNING — OPEN THE CIRCUIT BEFORE REMOVING THE COVER OR KEEP THE COVER TIGHT.” WHILE CIRCUITS ARE ALIVE.
AVERTISSEMENT — CIRCUIT OUVERT AVANT DE LE DeMONTER OU DE GARDER LA COUVERTURE SERREE PENDANT QUE LES CIRCUITS SONT VIVANTS. WARNING EXPLOSION HAZARD — SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2. AVERTISSEMENT RISQUE D’EXPLOSION — LA SUBSTITUTION DE COMPOSANTS PEUT NUIRE A LA CONFORMITe POUR LA CLASSE I, DIVISION 2. WARNING — EXPLOSION HAZARD — DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON—HAZARDOUS. AVERTISSEMENT — RISQUE D’EXPLOSION — NE PAS DECONNECTER L’EQUIPEMENT, A MOINS QUE L’ALIMENTATION EST COUPE OU QUE LA ZONE EST CONNUE POUR ETRE NON DANGEREUX. SENSORS WITH COATING OR SLEEVE OPTION: CAPTEURS AVEC DE L’ENDUIT OU DE LA MANCHE OPTION: WARNING (WRN) — POTENTIAL ELECTROSTATIC (ES) CHARGING HAZARD —CLEAN WITH DAMP CLOTH or AVOID STATIC DISCHARGE BY WIPING PLASTIC WITH DAMP CLOTH.

REVISIONS

ZONE| REV| DESCRIPTION| CHANGE ORDER| DATE| APPROVED
–| D| INCLUDE MPX-G.| CO- 2406| 4/21/16| K. REID
–| E| ADD MPX-E & -R TO ES WRN.| CO-3436| 3/6/19| R. OBORN

  • INSTALL IN ACCORDANCE WITH SECTION 18 OF THE CEC OR ARTICLE 500 OF THE NEC.
  • CSA LISTED OR NRTL/UL LISTED CONDUIT SEAL AT LOCATIONS A & B.

APG MPX-E MPX Magnetostrictive Level Sensors - class

PROPRIETARY AND CONFIDENTIAL

THIS DRAWING IS THE PROPERTY OF AUTOMATION PRODUCTS GROUP, INC. LOGAN, UTAH, AND MAY NOT BE USED, REPRODUCED, PUBLISHED, OR DISCLOSED TO OTHERS WITHOUT THE WRITTEN CONSENT OF THE COMPANY. IF LOANED, IT IS SUBJECT TO RETURN UPON DEMAND AND MAY NOT BE USED IN ANY WAY DIRECTLY OR INDIRECTLY DETRIMENTAL TO THE COMPANY.
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES AND TOLERANCES ARE AS FOLLOWS:
TOLERANCE ON ANGLE: ±r
2 PLACES: ±.01″ 3 PLACES: ±.005″
INTERPRET DIMENSIONS AND TOLERANCES PER ASME Y14.5-2009
THIRD ANGLE PROJECTION

APPROVALS| DATE| 1025 West 1700 North
Logan, Utah USA
AUTOMATION PRODUCTS GROUP, INC, 888.525.7300
---|---|---
MN
K. REID| 9/8/10
Ct HUTCHINS| 9/11/10
MAGNETOSTRICTIVE PROBE, MPX-E, MPX-R, & MPX-G
HAZARDOUS INSTALLATION DRAWING
EX WIRING, CSA
APVD
K. REID| 9/11/10
CONTRACT
SIZE
C| CAGE CODE
52797| PART NO| DOCUMENT NO
9003468| REV
E
MAIL
FINISH| SCALE NONE UINL
IN| DO NOT SCALE DRAWING| SHEET 1 OF 3

DANGER: OPEN CIRCUIT BEFORE REMOVING COVER or KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE;
DANGER: WARNING — EXPLOSION HAZARD — SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
DANGER: WARNING — EXPLOSION HAZARD — DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS;
DANGER: WARNING — POTENTIAL ELECTROSTATIC CHARGING HAZARD – CLEAN ONLY WITH A DAMP CLOTH;

Automation Products Group, Inc.
1025 W 1700 N Logan, UT 84321
www.apgsensors.com
phone:888-525-7300 
email:sales@apgsensors.com
Part # 122950-0003
Doc #9004081 Rev E

Documents / Resources

| APG MPX-E MPX Magnetostrictive Level Sensors [pdf] Installation Guide
MPX-E, MPX Magnetostrictive Level Sensors, MPX-E MPX Magnetostrictive Level Sensors, Magnetostrictive Level Sensors, Level Sensors, Sensors
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals