Divine Keystone Operation Control Reference User Manual
- June 5, 2024
- Divine
Table of Contents
Keystone Operation
Control Reference
Spa Control Manual
Button shapes and labels may vary.
Initial Start-up
Your spa will enter Priming Mode (‘PR’) when it is energized. During Priming Mode, press the “Jets” button(s) repeatedly and be sure all pumps are free of air. Priming Mode lasts less than 5 minutes. Press “Temp” to exit. After Priming Mode, the spa will run in Standard Mode (see Mode section). Some panels may not have a “Temp” button. On these panels, the “Set,” “Warm,” or “Cool” buttons are used.
Temp Control
(80°F-104°F/26°C-40°C) The last measured water temperature is constantly
displayed. The water temperature displayed is current only when the pump has
been running for at least 2 minutes.
On panels with a single “Temp” or “Set” button, to display the set
temperature, press the button once. To change the set temperature, press the
button a second time before the display stops flashing. Each press of the
button will continue to either raise or lower the set temperature. If the
opposite direction is desired, allow the display to revert to the current
water temperature. Press the button to display the set temperature, and again
to make the temperature change in the desired direction.
On panels with “Warm” and “Cool” buttons, to display the set temperature, press “Warm” or “Cool” once. To change the set temperature, press a temperature button again before the display stops flashing. Each press of “Warm” or “Cool” will adjust the set temperature. After three seconds, the display will stop flashing and begin to display the current spa temperature.
Jets 1
Press “Jets 1” to turn pump 1 on or off, and to shift between low and high
speeds (if equipped). The low-speed will turn off after 4hours. High-speed
will turn off after 15 minutes. Low-speed may run automatically at times,
during which it cannot be deactivated from the panel, but high-speed may be
operated.
Jets 2/Jets 3/Blower
(If equipped) Press the corresponding button once to turn the device on or
off. The device will turn off after 15 minutes. Pump 2 may be two-speed on
some systems. Some systems use this one button to control two devices. The
first button press will activate one device. Press again to have both devices
active. Press again to turn off the first device only. Press one more time to
turn both devices off. The pump responsible for heating and filtration (pump 1
low-speed on non-circ system, or the circ pump on circ systems) will be
referred to simply as the pump. In multi-button sequences, if the buttons are
pressed too quickly in In multi-button sequences if the buttons are pressed
too quickly in
Light
Press “Light” to operate the spa light. Turns off after 4 hours.
Mode
Depending on system configuration, mode changing may not be available and will
be locked in Standard Mode. Mode is changed by pressing “Temp,” then “Light”.
Standard Mode maintains a set temperature. ‘SE’ will be displayed
momentarily when you switch into Standard Mode.
Economy Mode heats the spa to the set temperature only during filter
cycles. ‘EC’ will display when the water temp is not current and will
alternate with water temp when the pump is running.
Sleep Mode heats the spa to within 20°F/10°C of the set temperature only during filter cycles. ‘SL’ will display when the water temp is not current and will alternate with water temp when the pump is running.
Preset Filter Cycles
The first preset filter cycle begins 6 minutes after the spa is energized. The second preset filter cycle begins 12 hours later. Filter duration is programmable for 2, 4, 6, or 8 hours or for continuous filtration (indicated by ‘FC’). The default filter time is 2 hours for non circ systems and 4 hours for circ systems. To program, press “Temp,” then “Jets 1.” Press “Temp” to adjust. Press “Jets 1” to exit programming.
For non-circ systems, low-speed pump 1 and the ozone generator (if installed)
run during filtration.
For circulation systems, the circ pump and the ozone generator (if installed)
run
Diagnostic Messages
Message | Meaning | Action Required |
---|---|---|
LF | No message on display. Power has been cut off to the spa. | The |
control panel will be disabled until power returns. Spa settings will be
preserved until the next power-up.
| Temperature unknown.| After the pump has been running for 2 minutes, the
current water temperature will be displayed.
HH| “Overheat” – The spa has shut down. One of the sensors has detected
118°F/47.8°C at the heater.| DO NOT ENTER THE WATER. Remove the spa cover and
allow the water to cool. Once the heater has cooled, reset it by pushing any
button. If the spa does not reset, shut off the power to the spa and call your
dealer or service organization.
OH| “Overheat” – The spa has shut down. One of the sensors has detected
that the spa water is 110°F/43.5°C.| DO NOT ENTER THE WATER. Remove the spa
cover and allow the water to cool. At 107°F/41.7°C, the spa should
automatically reset.
If spa does not reset, shut off the power to the spa and call your dealer or
service organization.
SA| Spa is shut down. The sensor that is plugged into the Sensor “A”
jack is not working.| If the problem persists, contact your dealer or service
organization. (May appear temporarily in an overheat condition.)
Sb| Spa is shut down. The sensor that is plugged into the Sensor “B”
jack is not working.| If the problem persists, contact your dealer or service
organization. (May appear temporarily in an overheat condition.)
Sn|
Sensors are out of balance. If alternating with spa temperature, it may just be a temporary condition. If flashing by itself, spa is shut down.*
| If the problem persists, contact your dealer or service organization.
HL| A significant difference between temperature sensors has been
detected. This could indicate a flow problem.| If the water level is normal,
make sure all pumps have been primed. If the problem persists, contact your
dealer or service organization.
LF| Persistent low flow problems. (Displays on the fifth occurrence of
HL message within 24 hours.)
The heater is shut down, but other spa functions continue to run normally.|
Follow action required for HL message. The heating capability of the spa will
not reset automatically; you may press any button to reset it.
dr| Possible inadequate water, poor flow, or air bubbles in detected in
the heater. The spa is shut down for 15 minutes.| If the water level is
normal, make sure all pumps have been primed. Press any button to reset. This
message will reset within 15 minutes. If the problem persists, contact your
dealer or service organization.
dy| Inadequate water detected in heater. (Displays on third occurrence
of dr message.) The spa is shut down.*| Follow the action required for dr
message. The spa will not automatically reset. Press any button to reset
manually.
IC| “Ice” – Potential freeze condition detected.| No action is required.
All equipment will automatically activate regardless of spa status. The
equipment stays on 4 minutes after the sensors detect that the spa temperature
has risen to 45°F/7.2°C or higher. An optional freeze sensor may be added to
protect against extraordinary freeze conditions. Auxiliary freeze sensor
protection is advisable in colder climates. See your dealer for details.
- – Even when spa is shut down, some equipment will turn on if freeze protection is needed.
Warning! Shock Hazard! No User Serviceable Parts.
Do not attempt service of this control system. Contact your dealer or service
organization for assistance. Follow all owner’s manual power connection
instructions. Installation must be performed by a licensed electrician and all
grounding connections must be properly installed.
Divine Hot Tubs 01-09-2020
Div200 topside control 2020
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>