KLHA KM12B13 carbon dioxide, illuminance, temperature and humidity integrated sensor User Manual

June 5, 2024
KLHA

KLHA KM12B13 carbon dioxide, illuminance, temperature, and humidity

integrated sensorKLHA KM12B13 carbon dioxide, illuminance, temperature, and
humidity integrated sensor-PRODUCT

KM12B13 using the standard RS485 bus MODBUS-RTU protocol, easy access to PLC, DCS, and other instruments or systems for monitoring temperature,humidity@12 state quantities. The internal use of high-precision sensing core and related devices to ensure high reliability and excellent long-term stability can be customized RS232, RS485, CAN,4-20mA, DC0~5V\10V, ZIGBEE, Lora, WIFI, GPRS and other output methods.

Technical Parameters

Technical parameter Parameter value
Brand KLHA
Temperature measuring range -30℃~80℃
Temperature measuring accuracy ±0.5℃ @25℃
Support sensor SHT30
Channels 10
Input bus II
Communication Interface RS485
Default baud rate 9600 8 n 1
Power DC9~24V 1A
Running temperature -40~80°C

Product Size

KLHA KM12B13 carbon dioxide, illuminance, temperature, and
humidity integrated sensor-FIG-1

How to wiring?

KLHA KM12B13 carbon dioxide, illuminance, temperature, and humidity
integrated sensor-FIG-5

Note: When wiring, the positive and negative poles of the power supply are first connected, and then the signal wire is connected.

Application solution

KLHA KM12B13 carbon dioxide, illuminance,
temperature, and humidity integrated sensor-FIG-2

How to use?

Communication Protocol

The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device is shipped, the default baud rate is 9600, 8, n, 1

Read Data (Function id 0x03)
Inquiry frame (hexadecimal), sending example: Query 1# device 1 data, the host computer sends the command:01 03 00 00 00 0A C5 CD.

Device ID Function id Start Address Data Length CRC16
01 03 00 00 00 0A C5 CD

For the correct query frame, the device will respond with data:01 03 14 00 79 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 26 31 , the response format is parsed as follows:

Device

ID

| Function

id

| Data

Length

| 数据

1

| 数据

2

| 数据

3

| 数据

4

| 数据

5

| 数据

6

| | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---
01| 03| 14| 00

79

| 00

7A

| 00

7B

| 00

7C

| 00

7D

| 00

7E

| | | | |

Data Description: The data in the command is hexadecimal. Take data 1 as an example. 00 79 is converted to a decimal value of 121. If the data magnification is 100, the actual value is 121/100=1.21. Others and so on.

Data Address Table

Address Start Address Description Data type Value range
40001 00 00 1#temperatureregister Read only 0~65535
40002 00 01 2#humidityregister Read only 0~65535
40003 00 02 3#temperatureregister Read only 0~65535
40004 00 03 4#humidityregister Read only 0~65535
40005 00 04 5#temperatureregister Read only 0~65535
40006 00 05 6#humidityregister Read only 0~65535
40023 00 16 23#temperatureregister Read only 0~65535
40024 00 17 24#humidityregister Read only 0~65535
40101 00 64 model code read/write 0~65535
40102 00 65 total points read/write 1~20
40103 00 66 Device ID read/write 1~249
40104 00 67 baud rate read/write 0~6
40105 00 68 mode read/write 1~4
40106 00 69 protocol read/write 1~10

read and modify device address

  1. Read or query device address

If you don’t know the current device address and there is only one device on the bus, you can use the command FA 03 00 64 00 02 90 5F Query device address.

Device ID Function id Start Address Data Length CRC16
FA 03 00 64 00 02 90 5F

FA is 250 for the general address. When you don’t know the address, you can use 250 to get the real device address, 00 64 is the device model register.

For the correct query command, the device will respond, for example, the response data is 01 03 02 07 12 3A 79, the format of which is shown in the following table:

Device ID Function id Data Length Rate ID CRC16
01 03 02 00 03 F8 45

A response should be in the data, the first byte 01 indicates that the real address of the current device is, 55 3C converted to decimal 20182 indicates that the current device’s main model is 21820, and the last two bytes 00 01 Indicates that the device has a status quantity.

Change devise address

For example, if the current device address is 1, we want to change it to 02, the command is:01 06 00 66 00 02 E8 14.

Device ID Function id Start Address Target Baud Rate CRC16
01 03 00 66 00 01 64 15

Change the baud rate from 9600 to 38400, changing the code from 3 to 5. The new baud rate will take effect immediately, at which point the device will lose its response and the baud rate of the device should be queried accordingly. Modified.

Read Correction Value

  1. Read Correction Value

When there is an error between the data and the reference standard, we can reduce the display error by adjusting the correction value. The correction difference can be modified to be plus or minus 1000, that is, the value range is 0-1000 or 64535 -65535. For example, when the display value is too small, we can correct it by adding 100. The command is: 01 03 00 6B 00 01 F5 D6 . In the command 100 is hex 0x64 If you need to reduce, you can set a negative value, such as -100, corresponding to the hexadecimal value of FF 9C, which is calculated as 100-65535=65435, and then converted to hexadecimal to 0x FF 9C. The correction value starts from 00 6B. We take the first parameter as an example. The correction value is read and modified in the same way for multiple parameters.

Device ID Function id Start Address Data Length CRC16
01 03 00 6B 00 01 F5 D6

For the correct query command, the device will respond, for example, the response data is 01 03 02 00 64 B9 AF, the format of which is as shown in the following table:

Device ID Function id Data Length Data value CRC16
01 03 02 00 64 B9 AF

In the response data, the first byte 01 indicates the real address of the current device, and 00 6B is the first state quantity correction value register. If the device has multiple parameters, other parameters operate in this way. The same, the general temperature, and humidity have this parameter, the light generally does not have this item.

Change correction value

For example, if the current state quantity is too small, we want to add 1 to its true value, and the current value plus 100 correction operation command is:01 06 00 6B 00 64 F9 FD.

Device ID Function id Start Address Destination CRC16
01 06 00 6B 00 64 F9 FD

After the operation is successful, the device will return information: 01 06 00 6B 00 64 F9 FD, the parameters take effect immediately after a successful change.

Disclaimer

This document provides all information about the product, does not grant any license to intellectual property, does not express or imply, and prohibits any other means of granting any intellectual property rights, such as the statement of sales terms and conditions of this product, other issues. No liability is assumed. Furthermore, our company makes no warranties, express or implied, regarding the sale and use of this product, including the suitability for the specific use of the product, the marketability, or the infringement liability for any patent, copyright, or other intellectual property rights, etc. Product specifications and product descriptions may be modified at any time without notice.

Contact Us

  • Company: Shanghai Sonbest Industrial Co., Ltd KLHA Brand Division Address: Building 8, No.215 Northeast Road, Baoshan District, Shanghai, China Web:
  • http://www.klha.com
  • Web: http://www.klha.com
  • SKYPE: soobuu
  • Email: sale@sonbest.com
  • Tel: 86-021-51083595 / 66862055 / 66862075 / 66861077