TIM10 CO2 Temperature and Humidity Monitor
Instruction Manual
INTRODUCTION
Thank you for purchasing this desktop CO2 monitor. It measures carbon dioxide
levels, air temperature and humidity. This makes it ideal for indoor air
quality (IAQ) diagnosis and HVAC system performance verification.
Poor indoor air quality is considered unhealthy. It can lead to drowsiness,
inability to concentrate, and even illness (for example, Sick Building
Syndrome).
IAQ monitoring of CO2 levels is widely used in public areas such as offices,
classrooms, factories, hospitals and hotels. It is also recommended for
industrial hygiene in some countries. (See appendix).
Product Features:
- Large display shows CO2 level, temperature, humidity, date and time
- 15 degree tilt angle makes the display easy to see and read
- Indoor air quality level indication: Good, Normal, and Poor
- Stable NDIR sensor for CO2 detection
- Visible and audible CO2 warning alarm
- ABC (Automatic Baseline Calibration) or manual CO2 calibration
- Maximum or minimum CO2 level recall function
MATERIALS SUPPLIED
This package contains:
- Meter
- Power Supply (5V +/- 10%, >= 0.5A)
- Manual
POWER SUPPLY
The meter is powered by an AC adaptor (5V/0.5A output).
Symbols
ppm | CO2 level in parts-per-million |
---|---|
GOOD | CO2 is in good level |
NORMAL | CO2 is in normal level |
POOR | CO2 is in poor level |
Air Temp. | Air temperature |
Humidity % | Unit of air relative humidity |
oE (C/F) | Celsius/Fahrenheit of temp. |
MAX/MIN | Maximum/Minimum readings |
CO2 alarm icon |
NOTE:
TWA / STEL / VENT.R / cfm/p / lps% icons are not used for this model.
KEYPAD
SET – Enter setup mode -Save and finish settings
ESC- Exit setup page / mode -Terminate CO2 calibration
RESET – Clear MAX/MIN values
▲-Select mode or increase value in setup
MIN/MAX▼ – Activate MAX, MIN function -Select mode or decrease value
during setup
SET+▲+MIN/MAX▼ – CO2 calibration mode
OPERATION
POWER ON/OFF
Plug the wall adaptor into an appropriate receptacle. The meter will turn on
automatically after a short beep. The lit LED indicates full power.
If the voltage is too high or low, “bAt” will display on the LCD and the LED
will flash. Please see page 14 for trouble shooting.
During normal operation, the LCD will display the current CO2 level in ppm,
air quality level, air temperature, humidity, and the current date and time
(Fig.1).
TAKING MEASUREMENTS
The meter starts taking measurements immediately after it is turned on and
updates the readings every second. In the event the operating environment is
quickly changed (for example, from high to low temperature), it will take
approximately 2 minutes for the CO2 and temperature to adjust and 10 minutes
for humidity to stabilize.
NOTE: Do not hold the meter close to your face as your breath will affect
the CO2 level.
MIN/MAX
While the meter is powered on, press the “MIN/MAX▼“ button to see the minimum
and maximum CO2 level, temperature, and humidity in turn. Each press of
“MIN/MAX▼“ will display the MIN and MAX values in order, then return the meter
to normal mode (Fig.2).
During normal operation or while viewing MIN/MAX levels, press and hold the
“RESET“ key for more than 1 second to clear the stored minimum and maximum
values.
HIGH CO2 ALARM
ALARM
The meter features an audible alarm that warns the user when the CO2
concentration exceeds the programmed limit. Users can set 2 limits: a CO2
level that requires ventilation (See P1.3 in setup for setting alarm limits)
and a lower CO2 level when ventilation is no longer required (See P1.2 in
setup CO2 normal limit).
During high alarm, the meter emits an 80dB beep and displays the fan icon on
the LCD. The alarm can be temporarily stopped by pressing any button, or it
will automatically stop when the CO2 level falls below the lower limit.
If the alarm is temporarily silenced, it will resume if the CO2 level fall
below the lower limit then rises above the upper limit again, or if the
“RESET“ button is pressed to re- activate the alarm.
The fan icon remains flashing even if the beeps are silenced. The icon only
stops flashing when the CO2 level fall below the lower limit (Fig.3)
SETUP
There are 4 setup modes: P1-CO2 alarm levels, P2-temperature (C or F),
P3-date/time, and P4-factory reset. When you press “SET” the setup mode will
be shown in the lower right corner of the screen.
To enter setup, while in normal mode, hold down the “SET“ button for 3
seconds. To exit setup, press “ESC“ while P1.0, P2.0, P3.0, or P4.0 is
displayed.
P1.1 SET CO2 GOOD LEVEL
Press “SET“ to display P1.0 and ”CO2” (Fig.4) on the LCD. Press “SET“ again to
set the CO2 GOOD level. The current set value will be blinking on LCD (Fig.5).
Press “▲“ to increase or “MIN/MAX▼“ to decrease the value. The GOOD alarm
range is from 0 to 700ppm in 100ppm increments. Once the preferred CO2 level
is selected, press ”SET“ to continue on to P1.2 to set the NORMAL level
(Fig.6 ) or press “ESC“ to return to P1.0 without saving changes.
P1.2 SET CO2 NORMAL LEVEL
P1.2 is the upper limit of the CO2 NORMAL level.
The current value will flash on the LCD (Fig.6).
Press “▲“ to increase or “MIN/MAX▼” to decrease the value. The NORMAL level
can be set between 700 and 1,000ppm. Once the preferred value is selected,
press ”SET“ to save P1.2 and continue onto set the P1.3 POOR + ALARM
threshold setting (Fig.7) or press “ESC“ to return to P1.0 without saving
changes.
P1.3 SET CO2 POOR LEVEL + ALARM
P1.3 is used to set the CO2 alarm threshold. The current set value will blink
on the LCD (Fig.7). Press “▲“ to increase or “MIN/MAX▼“ to decrease the value.
The POOR level can be set between 1,000 to 5,000ppm. Press “SET “ to confirm
P1.3 and continue to P1.4 (Fig.8) or press “ESC“ without saving to return to
P1.0
P1.4 SET ALARM ON/OFF
P1.4 is used to set alarm on and off. When entering P1.4, the default “On“
will be blinking on the LCD (Fig.8).
Press “▲“ or “MIN/MAX▼“ to switch the alarm to “Off “. Then press “SET “ to
confirm P1.4 and return to P1.0 (Fig.4) or press “ESC“ to return to P1.0
without saving.
CAUTION:
Although the TIM10 alarm can be set up to 5,000ppm, the accuracy of the CO2
reading is only specified up to 2,000ppm. Alarm values higher than 2,000ppm
are for reference only and should not be used for personal safety.
P2.0 SET TEMPERATURE UNITS
Hold down the “SET” button for at least 3 seconds to enter setup mode, then
press “▲“ in P1.0 mode to access P2.0 to set the temperature scale (Fig.9).
Press “SET“ again to show temperature in ºF on the display (Fig. 10). Press
“▲“ or “MIN/MAX▼ “ to change units, then press “SET “ to save or “ESC” to exit
without saving and return to P2.0 ºC or
P3.0 SET REAL TIME CLOCK
The TIM10 can display time in either 24 hour or 12 hour (am/pm) format. Hold
down the “SET” button for at least 3 seconds to enter setup mode, then press
“▲“ twice to access the P3.0 real-time clock (rtc) setup (Fig.11).
To start, press “SET “ to display P3.1 with “rtc” and the blinking year digits
(Fig.12) in the lower left corner of the display. To change the year, press “▲
“ or “MIN/MAX▼“ to change the value, then press “SET “ to save the year and
continue, or press “ESC “ to exit without saving.
Continue to press “SET“ to change to the month, and then the day. After you
press “SET”, press “▲ “ or “MIN/MAX▼” while the year, month or day values are
flashing to set the correct date. Press “SET“ to save and move forward to set
the time, or press “ESC “ to return to P3.0 mode without saving.
To set the clock, in P3.4 mode with the hours flashing, press “▲“ or
“MIN/MAX▼“ to change from 12 to 24 hour time format (Fig11). Press “SET“ to
save and move forward to P3.5 mode to set the time, or press “ESC “ to return
to P3.0 mode without saving.
While in P3.5 mode, the current hour setting will blink (Fig.14). To change the setting, press“▲“ or “MIN/MAX▼“ to adjust the time. Press “SET“ to save the setting or press “ESC “ to return to P3.0.mode without saving.
P4. RESET
Hold down the “SET” button for at least 3 seconds to enter setup mode, then
press “▲“ 3 times to access P4.0 mode to revert the meter to the factory
default state (Fig.15).
Press “SET“ to go to P4.1 mode. “No” will be blinking on the display (Fig.16).
Press “▲” or ”MIN/MAX▼” to change to “Yes”, then press “SET “ to save the
setting. Press “ESC” to return to P4.0C without saving.
If you choose “Yes”, the meter is reset to the following factory defaults:
Parameter | Default |
---|---|
P1.1 | 700ppm |
P1.2 | 1000ppm |
P1.3
P2.1| 1000ppm
°C
P4.1| No
P5.o|
CO2 CALIBRATION
The meter is calibrated at 400 ppm (parts-per-million) CO2 concentration at
the factory. 400 ppm is comparable to fresh outdoor air.
There are 2 types of calibration available: ABC (Automatic Baseline
Calibration) or manual calibration. One or the other should be used regularly
to maintain good accuracy.
Note:
If TIM10 accuracy becomes a concern after long use or other special
conditions, return the meter to the dealer for calibration.
CAUTION:
Do not calibrate the meter with air or bottled gas that contains an unknown
CO2 level. The meter will assume it is 400 ppm CO2 and will give inaccurate
measurements.
ABC Calibration
ABC (Automatic Baseline Calibration) is designed to eliminate the zero drift
over time of the infrared CO2 sensor. The ABC function is enabled by default
from the factory.
For ABC to work properly, the meter must continuously monitor CO2 levels for
at least 7.5 days (power on). During that time, it will record the lowest CO2
level and set that as the 400 ppm baseline for future readings. Therefore, it
is critical when using ABC calibration that the meter be exposed to fresh air
at least once every 7.5 days. If this is not possible, then manual
calibration is recommended.
Manual Calibration
Manual calibration requires fresh, dry outdoor air when CO2 levels are
approximately 400 ppm. Do not calibrate during rainy days. High humidity will
affect the CO2 levels in air.
During manual calibration, avoid placing the meter in areas crowded with
people or close to structures that might give off CO2 like air ventilation
pipes, chimneys, or automobiles.
To manually calibrate the meter, place it outdoors, and turn it on for at
least 2 minutes. Then hold down “SET“ ,”▲” and “MIN/MAX▼” simultaneously more
than 1 second to enter CO2 calibration mode (Fig.17). 400 ppm and
“CO2” will blink during calibration.
Wait about 5 minutes until the blinking stops.
Calibration is completed automatically. To stop manual calibration, press
“RESET“ for at least 1 second.
Note:
Keep the meter away from any animals, humans or plants which might affect the
CO2 concentration nearby during the calibration.
RH CALIBRATION
This humidity accuracy of this desktop CO2 meter is set at the factory, and cannot be re-calibrated.
SPECIFICATIONS
Measuring Range| CO2 : 0 – 9999 ppn
Air: Temp : -10°C – 60°C (14°F – 140°F)
Al RH% : 20.0%RH – 99.9%RH
---|---
Resolution| CO2: 1ppm
Al lamp. : 0.1°C/0.1°F
Ak RH% : 0.1%RH
Accuracy| CO2 : 50ppm 35%o1 reeding
Ae lamp. : ±0.6°C. 10.9°F:
Air RH% : 15%RH (at 25°C.10 – 90% RH )
t7%FtH (at 25°C. <10% a >se% RH )
Response| CO2: <2 mins (90′. step change
Air temp,: <2 mins 90% step change ,
Air RH% : <10 mins (90% step change.
Max/Min function| Included
Air quality level
CO2 concentration| Good: <700ppm (Programmable by user)
Normal: 700-1000ppm (Programmable by user) Poor >*Ncernal”
Alarm| Alarm: >1000ppm (Programmable by user)
Operating Condition| -10-50°C, 5-80%RH (13e sure to avail condense)
Storage Condltbn| -20-60°C. 5-90%RH (be sure to avoid condense)
Display| LCD & green LED
Power Supply| DC5V (4.10%).>4500mA.
TROUBLESHOOTING
? Cannot power on
Check whether the adaptor has power and that the meter is firmly plugged in.
? Slow response
Check that the air flow channels on the rear of the meter are not blocked.
? No change in readings
Check whether the meter is in maximum or minimum mode. Reset factory defaults.
? “BAt” and green LED keep flashing
The adaptor output voltage is too high or too low. Use the supplied adaptor
with correct 5V (+10%) >=0.5A ratings.
? Error Codes
Error Code | 1 Problem | Solution |
---|
CO2 Reading (See example of Fig. A)
0.00E+00| CO2 sensor is damaged| Send back for repair
0.00E+00| CO2 reading is under the lower limit| Re-calibrate the CO2. if it
still appear. send back for repair
0.00E+00| CO2 reading is above the upper limit| Put the meter in fresh air and
wait for 5minutes. if it still appear, re-calibrate the meter if above two
methods are failed. send back for repair
0.00E+00| ABC mode of CO2 senor is failed and might cause wrong CO2 readings|
Send back for repair
Error Code| Problem| Solution
---|---|---
Air Temp. Reading (See example of Fig. B)
0.00E+00| Air temp. measurement is under the lower limit| Put the meter in
regular room temperature for 30 minutes, if it still appear, send back for
repair
0.00E+00| Air temp. measurement is over the upper limit| Put the meter in
regular room temperature for 30 minutes, if it still appear, send back for
repair
0.00E+00| Temp. sensor or measuring circuit is damaged| Send back for repair
Air Humidity Reading (See example of Fig. C)
0.00E+00| Air humidity measurement is under the laver limit.| Put the meter in
regular room where humidity is more than 20% for 30 min. If error
continuessetum for repairs
Ell| The RH calibration is failed| Please re-calibrate the RH, if it still
appear, send back for repair
0.00E+00| RH sensor or measuring circuit is failed| Send back for repair
SUPPORT & WARRANTY
Support
The quickest way to obtain technical support is via email. Please send all
support enquires to support@co2meter.com. In
your email, please include a clear, concise definition of the problem and any
relevant troubleshooting information or steps taken so far, so we can
duplicate the problem and quickly respond to your inquiry.
Warranty
This unit comes with a 1YEAR (warranty period) limited manufacturer’s
warranty, starting from the date the unit was shipped to the buyer. During
this period of time, CO2Meter.com warrants our products to be free from
defects in materials and workmanship when used for their intended purpose and
agrees to fix or replace (at our discretion) any part or product that fails
under normal use.
To take advantage of this warranty, the product must be returned to
CO2Meter.com at your expense. If, after examination, we determine the product
is defective, we will repair or replace it at no additional cost to you.
This warranty does not cover any products that have been subjected to misuse,
neglect, accident, modifications or repairs by you or by a third party.
No employee or reseller of CO2Meter.com’s products may alter this warranty
verbally or in writing.
Returns
If the product fails under normal use during the warranty period, an RMA
(Return Material
Authorization) number must be obtained from CO2Meter.com. After the item is
received, CO2Meter.com will repair or replace the item at our discretion.
To obtain an RMA number, please call
CO2Meter.com at 877-678-4259 Toll Free
or (386)
310-4933. When requesting an RMA number, please provide the reason for return
and original order number.
If we determine that the product failed due to improper use (water damage,
dropping, tampering, electrical damage etc.) or abuse, or if it is beyond the
warranty period, we will inform you of the cost to fix or replace your
device.
If you are returning your device due to a warranty claim (with an RMA number)
and you still have the unit original package, please use it to ship your unit
to us. Please make sure to include the provided RMA number on the outside of
the box, preferably on the shipping label. Make sure you secure the unit
inside the package properly to prevent any damage during transit that could
void your device’s warranty. Finally, please ship your device to the address
shown under the “Contact Us” section below. CO2Meter will not, under any
circumstances, be responsible for your shipment expenses and no refund will be
issued for shipping charges necessary for you to ship the unit to us.
Liability
All liabilities under this agreement shall be limited to the actual cost of
the product paid to CO2Meter.com. In no event shall we be liable for any
incidental or consequential damages, lost profits, loss of time, lost sales
or loss or damage to data, injury to person or personal property or any other
indirect damages as the result of use of our products.
Contact us: We’re here to help!
If the troubleshooting guide above doesn’t help you solving your problem or
for more information, please contact us using the information below.
support@co2meter.com
877-678-4259 Toll free (M-F 9-6:00pm
EST)
386-310-4933 Technical
Support/International calls.
CO2Meter, Inc.
131 Business Center Drive
Ormond Beach, FL 32174 USA
www.CO2Meter.com
Appendix
CO2 LEVELS AND GUIDELINES
Non-Enforced Reference levels
NIOSH recommendations
400 ppm: normal outdoor ambient concentrations
600 ppm: minimal air quality complaints
600-1,000 ppm: less clearly interpreted
1000 ppm: indicates inadequate ventilation; complaints such as headaches,
fatigue, and eye/throat irritation will be more widespread. 1,000 ppm should
be used as an upper limit for indoor levels.
EPA Taiwan: 600ppm and 1,000 ppm
Type 1 indoor areas such as department stores, theaters, restaurants,
libraries, the acceptable CO2 concentration for an 8 hours average (TWA) is
1,000ppm.
Type 2 indoor areas with special requirements for good air quality such
as schools, hospitals, and day care centers, the suggested CO2 level is
600ppm.
Regulatory Exposure limit
ASHRAE Standard 62-1989: 1,000ppm CO2 concentration in occupied building
should not exceed 1,000ppm.
Building bulletin 101 (Bb101): 1,500ppm
UK standards for schools state that CO2 levels over a day(i.e. 9 am to 3.30
pm) should not exceed 1,500ppm.
OSHA: 5,000ppm
Time weighted average over an 8-hour work day should not exceed 5,000ppm.
Germany, Japan, Australia, UK: 5,000ppm
Occupational exposure limit is 5,000ppm over an 8 hour work day.
References