The Elite 500 multi-function meter has advanced power monitoring
functionality, making it a suitable instrument both as a standalone device and
as part of BMS, process industrial controls, and SCADA systems.
It also offers data logging, control IOs, and modular communication with
multiple protocols for third-party system integration.
Based on the application, Elite 500 allows customers to select conventional
type CT or Rogowski coil input, which can be directly connected to the meter
without the need for any additional integrator.
Application
-
Energy transfer measurement and reconciliation
-
Power plants, feeder monitoring, grid substations, wind turbines, renewables, industrial and commercial premises
-
Online monitoring of energy exchange at various interface points
-
Automation and system integration
-
Process and factory automation
-
Retrofit applications up to 4000A can be served by using
Rogowski coil along with Modbus / BACnet / Profinet / IEC 61850 protocol support, analogue output and control IOs · Oil and gas / Mining / Hospitals / Malls / Datacentres -
LV / MV / HV Switchgear
Benefits
- Minimal integration costs by combining hot-pluggable modular communication and analog output ports in conjunction with a digital pulse I / O and alarms.
- A single instrument covers a wide and versatile range of potential communication options. Both Modus RTU and TCP along with Profinet, BACnet and IEC61850 for SCADA are supported.
- Supports measurements for Energy Efficiency / LEED certification
- Large, high-resolution graphical color display for analytical and graphical views
- Options to have conventional CT or Rogowski coil
Features
- 17 energy measurements support including net and absolute energy parameters
- Energy resolution: 7+3 digit, Instantaneous parameters: 4+3 digit
- Class 0.2S / 0.5S accuracy for active and 0.5S accuracy for reactive measurement
- TFT display showing vector diagram, bar chart, weekly / monthly energy consumption comparison
- Configurable favorite parameter on the display page
- Time synchronization options through SNTP
- Power quality features include individual harmonics, THD, sag, swell, voltage unbalance, and interruption counter
- Total demand distortion (TDD) factors and waveform quality indices like K factor and crest factor
- Positive, negative, and zero sequence components
- Flexible time-of-day tariff, maximum demand/demand support, DST (daylight saving time)
- Supports PIPO / DIDO, alarm, and analog output module
- Alerts and events on configured parameters
- Dual loggers for instantaneous and energy parameters
- Dual socket support on the Ethernet TCP IP module allows for simultaneous communication over Modbus.
- Supports RS485 Modbus along with any chosen Ethernet protocol
- A high-resolution page for configured energy channel
Technical specifications
| Conventional| Rowe/ski
---|---|---
Electrical|
Connection type| LV 3P4W / 1-1V 3P4W / 1CT 3PT / LV KT / HV 3P3W / 3C1 2PT /
2CT 2PT / 1P 2W
Measurement voltage range| 35 V to 500 V (L-L) max, 20 V to 300 V (1.-N) max
Measurement current range| 10mA – 6 A (configurable)| 5961. -I. Or -1000 A or
4000 A)
Starting current range| 1mA| 1A for 1000A /4 A for 4000A
Frequency| 50 / 60 Hz
Burden| Current circuit: < 0.2 VA/phase @ lA & @ 5A
Voltage circuit: < 0.2 VA/phase
Sampling rate| 156 samples / cycle / channel
Accuracy|
Active energy| Class 0.25 / class 0.55 I Class 0.55
Reactive energy| Class 0.55
Voltage, Current, Power| 0.2% for measurement range
Frequency| 40.05 K2
Power factor| *0.005 (0.5 lag to 0.5 lead)
Maximum withstand Voltage| 2 times of nominal voltage value for 1 Sec repeated
10 times at 10 second interval
Maximum withstand current| 1.2 times of lb continuously| –
Short time over current| 20 times In„ for 1 second| –
Overload (continuous)| 1.5 times of lb, Up to 7.5A (only measurement)| –
Standards| IEC 62052-11, IEC 62053-22, IEC 62053-24, IEC61557-12, IEC
62053-31, IEC 60529, IEC 61010-1, IEC 61010-2-030, IEC 61326-1,1514697, CE,
UKCA
IEC 61850-6, 7-1,7-2, 7-3, 7-4,8-1, (as per edition 1 and 2)
Environmental|
Ingress protection| IP 54 (front fascia): IP20 (at terminals), IP 65 with
gasket (Optional)
Insulation| 3.5 kV RMS 50 Hz, 5 seconds
Impulse withstand| 6A kV
Operating temperaWre| -10°C to t 60°C
Storage temperature| -25K to • 70K
Temperature coefficient| 0.02% / °C I 0.196 PC
Mechanical dimension (H x W x 0)| 96 x 96 x 57.6 mm (6 0.5 mil), 96 x 96 x
111.5 mm (a 0.5 mm) with module
Weight| 365 g 1280 g
Software| – TWo data loggers (16 MB memay)c
| Primary data logger
Logging of up to 20 energy channels values, with integration
period 5,15, 30 860 minutes
-12500 parameter-days capacity at 30-minute interval
Secondary data logger
Logging of up to 20 instantaneous values with integration period
1, 2, 5,10,15 & 30 minutes
-40000 parameter-days capacity at 30-minute interval
– Configurable parameters:
•8 time-of-use tariffs (TOU), 8 Seasons, 8 day types, DST dates, 6 billing
history
•Logging daily energy snapshots values up to 90 days
•Alarms and event logging
•Up to 311′ individual harmonic component measurement
•Up to or total harmonic distortion (THD) measurement
•K-factor, Crest Factor, TOD, sequence components
•Power quality features including voltage sag, swell
Features|
Power supply| Range: 48-300VDC / 85-300VAC
Burden| Base product: <3W, < 6.5VA at 240V AC. With all modules: <6.5W, <16VA
Display| TFT for graphical and analytics (3.5 inch)
Size: 53 x 70 mm (H x VV), 320×240 pixels. Pixel size: 0.22 mm2
Battery| Battery for RTC backup
Connector| Ring type for current terminal, combicon for voltage, Aux and
modbus RTU| all are combicon
Inputs and Outputs| 2 configurable pulse inputs / outputs, 1 fixed pulse
output, 1 Alarm output
•Pulse outputs:
24-230V DC or 48-230 V AC 0 100mA
Type: volt-free, pulse width: 20 – 300 ms (for 50Hz); 16 – 300 ms (for 60Hz)
•Pulse Input: 24-60 V AC/DC @ 100mA
•3 Alarm output: Type: volt-free, 230 V AC/ 30V DC at 2 A
•Analogue output (self-powered): 4 configurable AO, 0-20mA, 4-20mA
•Indicator – 2 LEDs: one for metrology (red), one for alarms / events (amber)
Communication|
RS485 port| Protocol: Modbus RTU
Baud rate: 1200 – 38400 bps, parity- none, even, odd
Ethernet port| Ethernet over R.1-45, 10 / 100 Mbit / s, SNTP time sync
| Optional: Modbus TCP / IP, Modbus Gateway, BACnet IP, ProfiNET, IEC61850
Software support| Configview (for configuration / reading), Optional eWatch
100 / eWatch Online
Time synchronization| Through SNTP protocol /through pulse input
Order codification
Conventional Current input | Rogowski Current input |
---|---|
Elite500 | E500 |
Current Input | |
Conventional | C |
Accuracy | |
Class 0.2S | 2 |
Class 0.5S | 5 |
PQ parameters | |
Ind harmonics up to 15th order | 1 |
Ind harmonics up to 15th order, PQ parameters* | 2 |
order, PQ parameters* | 2 |
Ind harmonics up to 31th order | 3 |
Ind harmonics up to 31th order, PQ parameters* | 4 |
order, PQ parameters* | 4 |
Fix digit | 0 |
For Secure | 2 |
e.g. model number: E500C-2102 | |
F | |
For Secure | |
e.g. model number: E500R-51C2 |
Com Modules
Modbus TCP/IP – E500M-1012 | Modbus TCP/IP GW – E500M-1022 | BACnet IP –
E500M-1032 | Profinet – E500M-1042 | EC61850 – E500M-1052
For PIPO and AO module refer manual
*PQ Parameters sag, swell, interruption, TDD, K factor, crest factor, TEHD, TOHD, positive, negative and zero sequence components.
UK sales_uk@securemeters.com
www.securemeters.com
Specifications are subject to change without prior notice
M722 V 2.0
Documents / Resources
|
SECURE Elite 500 IEC61850 Protocol Multi-Function Panel
Meters
[pdf] Instruction Manual
Elite 500, IEC61850, Protocol Multi-Function Panel Meters, IEC61850 Protocol
Multi-Function Panel Meters, Elite 500 IEC61850 Protocol Multi-Function Panel
Meters, Multi-Function Panel Meters, Panel Meters, Meters
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>