WINCO WL12000HE-04 208V Electric Start Portable Generator Installation Guide
- June 5, 2024
- WINCO
Table of Contents
WINCO WL12000HE-04 208V Electric Start Portable Generator Installation
Guide
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and maintenance of the generator. Read and understand all instructions in the manual before starting and operating the generator. Keep this manual available for future reference.
USING THIS MANUAL
Congratulations on your choice of a WINCO generator.
You have selected a high-quality, precision-engineered generator designed and
tested to give you years of satisfactory service.
To get the best performance from your new generator, it is important that you carefully read and follow the operating instructions in this manual.
Should you experience a problem please follow the “Troubleshooting Tables”
near the end of this manual.
The warranty listed in the manual describes what you can expect from WINCO
should you need service assistance in the future.
SAFETY
SAVE THESE INSTRUCTIONS
This engine generator set has been designed and manufactured to allow safe, reliable performance. Poor maintenance, improper or careless use can result in potentially deadly hazards; from electrical shock, exhaust gas asphyxiation, or fire. Please read all safety instructions carefully before installation or use. Keep these instructions handy for future reference. Take special note and follow all warnings on the unit labels and in the manuals.
CALIFORNIA PROPOSITION 65
WARNING: This product contains crude oil, gasoline, diesel fuel and other
petroleum products, Antifreeze to which can expose you to chemicals including
toluene and benzene,
Ethylene glycol (ingested) which are known to the State of California to cause
cancer, birth defects or other reproductive harm and developmental issues.
For more information go to
www.P65Warning.ca.gov.
SAFETY DEFINITIONS
DANGER
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
This signal word is to be limited to the most extreme situations.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury. It may also be used to alert against
unsafe practices.
ELECTRICAL SHOCK –
The output voltage present in this equipment can cause fatal electric shock.
This equipment must be operated by a responsible person.
- Do not allow anyone to operate the generator without proper instruction.
- Guard against electric shock.
- Avoid contact with live terminals or receptacles.
- Use extreme care if operating this unit in rain or snow.
- Use only three-pronged grounded receptacles and extension cords.
- Be sure the unit is properly grounded or your application.
FIRE HAZARD –
Gasoline and other fuels present a hazard of possible explosion and/or fire.
- Do not refuel when the engine is running or hot.
- Keep fuel containers out of reach of children.
- Do not smoke or use open flame near the generator set or fuel tank.
- Keep a fire extinguisher nearby and know its proper use. Fire extinguishers rated ABC by NFPA are appropriate.
- Store fuel only in an approved container, and only in a well ventilated area.
- Follow local codes for closeness to combustible material.
DEADLY EXHAUST GAS –
Exhaust fumes from any gasoline engine contain carbon monoxide, an invisible,
odorless and deadly gas that must be mixed with fresh air.
- Operate only in well ventilated areas.
- Never operate indoors including attached garages
- Never operate the unit in such a way as to allow exhaust gases to seep back into closed rooms (i.e. through windows, walls, floors).
NOISE HAZARD –
Excessive noise is not only tiring, but continual exposure can lead to loss
of hearing.
- Use hearing protection when working around this equipment for long periods of time.
- Keep your neighbors in mind when using this equipment.
CLEANLINESS –
Keep the generator and surrounding area clean.
- Remove all grease, ice, snow or materials that create slippery conditions around the unit.
- Remove any rags or other materials that could create a potential fire hazard.
- Carefully clean up any gas or oil spills before starting the unit.
SERVICING EQUIPMENT –
All service, including the installation or replacement of service parts,
should be performed only by a qualified technician.
- Use only factory approved repair parts.
- Do not work on this equipment when fatigued.
- Never remove the protective guards, covers, or receptacle panels while the engine is running.
- Use extreme caution when working on electrical components. High output voltage from this equipment can cause serious injury or death.
- Always avoid hot mufflers, exhaust manifolds, and engine parts. They can cause severe burns instantly.
- The use of the engine-generator set must comply with all national, state, and local codes.
SPECIFICATIONS
WL12000HE-04/A
Volts 120/208 3PH
Surge Watts 12,000
Continuous Watts 10,800
Amps @ 1.0 PF 30
Amps @ 0.8 PF 37.5
WL12000HE-17/A
Volts 132/230 3PH
Surge Watts 12,000
Continuous Watts 10,800
Amps @ 1.0 PF 27
Amps @ 0.8 PF 34
WL12000HE-18/A
Volts 277/480 3PH
Surge Watts 12,000
Continuous Watts 10,800
Amps @ 1.0 PF 13
Amps @ 0.8 PF 16
GENERATOR
120/208 & 132/230
Generator Manufacturer Mecc Alte Spa
Generator Model Number ET20F-200
Part Number 16346-037
Rotor 13.074 Ohms
Stator Resistance 0.16 Ohms
AVR ASR
277/480
Generator Manufacturer Mecc Alte Spa
Generator Model Number ET20F-200
Part Number 16346-038
Rotor 13.309 Ohms
Stator Resistance 1.049 Ohms
AVR ASR
ENGINE
Engine Manufacturer Honda
Engine Model Number GX630RH
Type VXE1 NH1
Code GCAMH
Spark Plug Gap 0.030 in
Intake Valve Clearance 0.006 – 0.010 in
Exhaust Valve Clearance 0.010 – 0.012 in
Oil Capacity 57 – 58 oz (1.78 – 1.81 qts)
INTRODUCTION
TESTING POLICY
Before any generator is shipped from the factory, it is fully checked for performance. The generator is loaded to its full capacity, and the voltage, current, and frequency are carefully checked.
Rated output of generator is based on engineering tests of typical units, and is subject to, and limited by, the temperature, altitude, fuel, and other conditions specified by the manufacturer of applicable engines.
INTENDED USES
This engine generator set has been designed primarily for portable heavy duty commercial use. This portable unit requires large quantities of fresh air for cooling the engine and generator. For safety, long life and adequate performance, these units should never be run in small compartments without positive fresh air flow.
RESTRICTED USES
DO NOT remove from the cradle assembly. Removal of the generator from the cradle assembly may cause excessive vibration and damage to the engine- generator set.
DO NOT operate and/or store the unit outside during inclement weather without adequate protection from the elements. Failure to do so will damage the unit.
DO NOT install and operate this generator in a small compartment., i.e. generator compartments of vehicles, motor homes or travel trailers. These compartments will not allow enough free flow of fresh air to reach the engine generator set for cooling and will cause the unit to overheat, damaging both the engine and generator. Small compartments will also develop hot spots where there is very little air flow and may cause a fire.
PLEASE NOTE There are 3rd party companies making enclosures for generators that have been properly engineered. The use of these 3rd party enclosures is acceptable as long as they have been certified and meet current code.
DO NOT attempt to operate at 50 cycles. These units are designed and governed to operate at 60 cycles only.
UNIT CAPABILITIES
GENERATOR CONNECTIONS
CAUTION: EQUIPMENT DAMAGE
Check phase rotation. Improper phase rotation can result in equipment damage.
WL12000HE: All models us wye (star) dedicated generator ends that cannot be reconnected. All nameplate ratings for amps and KVA are at a 0.8 PF. Some loads operate at 1.0 PF which will reduce the number of amps available but not the available KW. See page 4 of this manual for 1.0 PF amperage capabilities.
Each generator provides loads from three winding groups of equal capacity. It is essential that care is taken to properly balance the load between the winding groups.
When the load is connected between any line and the neutral (example A), the load is concentrated on one winding group with an amperage rating equal to specification at 1.0 PF. You can create a balanced load by dispersing your L-N loads between each leg.
When the load is connected between any Line to Line (example B), the load is concentrated on two of the three winding groups with an amperage rating equal to the specification at 1.0 PF. You can create a balanced load by offsetting connections.
A three phase load connected to all legs (example C), the load is evenly split between all three winding groups. the load can be at 0.8 or 1.0 PF.
You may run multiple connections types at the same time as long as they do not
exceed the machine’s nameplate rating.
Each connection type will reduce the amperage available on each winding group.
STARTING ELECTRIC MOTORS
Electric motors require much more current (amps) to start them than to run them. Some motors, particularly low cost split-phase motors, are very hard to start and require 5 to 7 times as much starting current as running current. Capacitor motors are easier to start and usually require 2 to 4 times as much starting current as running current. Repulsion Induction motors are the easiest to start and require only 1 1/2 to 2 1/2 times as much starting as running current.
Most fractional horsepower motors take about the same amount of current to run them whether they are Repulsion Induction (RI), Capacitor (Cap), or Split- Phase (SP) type.
If the electric motor is connected to a hard starting load such as an air compressor, it will require more starting current. If it is connected to a light load, or no load such as a power saw, it will require less starting current. The exact requirement will also vary with the brand or design of the motor.
Self-exciting generators respond to severe overloading differently than utility power. When overloaded, the engine is not able to supply enough power to bring the electric motor up to operating speed. The generator responds with high initial starting current, but the engine speed drops sharply. The overload may stall the engine. If allowed to operate at very low speeds, the electric motor starting winding will burn out in a short time. The generator winding might also be damaged.
CAUTION: EQUIPMENT DAMAGE
Running the generator set under these conditions may result in damage to
the generator stator as well as the motor winding.
The heavy surge of current required for starting motors is required for only an instant. The generator will not be damaged if it can bring the motor up to speed in a few seconds of time. If difficulty is experienced in starting motors, turn all other electrical loads off and if possible reduce the load on the electric motor.
PREPARING THE UNIT
UNPACKING
CAUTION: EQUIPMENT DAMAGE
THIS UNIT HAS BEEN SHIPPED WITH OIL. Failure to maintain the engine oil
at the proper level will result in serious engine damage.
When you unpack your engine-generator set be sure to remove all the information sheets and manuals from the carton.
- As you receive your unit, it is critical to check it for any damage. If any damage is noted, it is always easiest to refuse the shipment and let WINCO take care of the freight claim. If you sign for the unit, the transfer of the ownership requires that you file the freight claim
- Before proceeding with the preparations of your new generator for operation, take a couple of minutes to ensure the unit you have received is the correct model and review the specification pages in this manual to ensure that this unit meets your job requirements.
LUBRICATION
Before starting the engine, fill the crankcase to the proper level with a good quality oil. The recommended grade oil and quantity of oil required is listed in the engine operator’s manual and under the service tab in this manual. This unit was shipped with most of the oil. The engine normally holds 57 to 58 ounces (1.78 to 1.81 quarts) of oil. Since there is some trapped in the engine, when filling the crankcase the first time, use the dipstick to ensure that you do not over fill the crankcase. The full oil level mark on the dipstick is depicted in the following image.
Oil is added to the engine by removing the oil cap and adding oil at this point. After filling the crankcase to the proper level, be sure you properly tighten the oil fill cap.
NOTE: This engine generator must be on a level surface before you check or add
oil to the system.
The necessity of using the correct oil and keeping the crankcase full cannot
be overemphasized. Engine failures resulting from inadequate or improper
lubricant are considered abuse and not covered by the generator or engine
manufacturer’s warranty.
OIL RECOMMENDATIONS
Outdoor temperatures determine the proper oil viscosity for the engines. Winco
recommends our 5W-30 fully synthetic oil to give you excellent protection in
cold temperatures while maintaining excellent performance in warmer weather.
OIL ALERT SYSTEM
This generator is equipped with a low oil shutdown system.
This Honda engine uses an float switch mounted inside the engine. If the oil
level drops below a certain point the low oil module on the engine will shut
it down. This low oil warning system will automatically stop the engine
before the oil level reaches critical danger point. This feature is designed
to prevent costly repairs and downtime.
CAUTION: EQUIPMENT DAMAGE
Allowing the engine to shutdown repeatedly on low oil level may cause excessive wear which can be cumulative.
GASOLINE
When using gasoline, always use fresh, clean, unleaded fuel. The engine is certified to operate on unleaded gasoline with a minimum octane rating of 87 or higher. Gasoline containing no more the 10% ethanol is acceptable.
CAUTION: EQUIPMENT DAMAGE
Do not use unapproved gasolines, such as E15 or E85.
Do not mix oil in the gasoline. Use of unapproved fuels will damage the engine
components and void the engine warranty
Use of fuels with content of ethanol greater than shown above may cause
starting and/or performance problems.
Always ensure that the fuel is clean and free of all impurities.
WARNING: FIRE DANGER
Gasoline and its fumes are VERY explosive when proper precautions are not
taken.
Never use gasoline that has been stored for an extended period of time as the fuel will lose its volatile properties and you will be left with varnish residue. The varnish like substance will clog the carburetor and will not burn properly.
The use of fuel additives, such as Sta-Bil, or an equivalent will minimize the formation of fuel gum deposits. If a unit has been out of operation for an extended period of time, it is best to drain old fuel from the engine and replace with fresh fuel before attempting to start.
See the engine manual for special instruction for operating this unit at over 5000 feet.
BATTERY INSTALLATION
This engine generator set is shipped with a battery tie down kit for customer
installation. This kit consists of a battery tie down and hardware for
installation of the customer supplied battery on the unit.
If you intend to use the power plant’s electric start system, you will need to purchase and install a battery to operate it.
WARNING: EQUIPMENT DAMAGE
The battery positive (+) cable is shipped with a plastic protective cap. When
starting manually, this protective cap must remain in place to avoid possible
damage to the engine electrical system and/or generator end.
A 12 Volt battery, BCI group U1 rated at 275 CCA or larger is recommended for
this electric start engine-generator set.
Follow the battery manufacturers recommendations for servicing and charging
prior to use. Connect the battery to the electric start system using the
cables provided.
CAUTION: EQUIPMENT DAMAGE
These electric start engines are NEGATIVE GROUND. Use extreme caution when
connecting the battery. Connect the NEGATIVE battery terminal to GROUND.
For your safety, always connect the positive battery cable to the “bat+” terminal first. Then connect the negative battery cable to the “Bat-” terminal. Make sure all connections areclean an tight. Reverse the sequence when disconnecting, disconnect the negative cable first. These engines produce enough direct current to keep the battery charged under normal operating conditions, but were not intended to be used as a battery charger.
WARNING: PERSONAL INJURY
Lead acid batteries produce explosive hydrogen gas when charging. Keep sparks,
flames, and burning cigarettes away from the battery. Ventilate the area when
charging or using the battery in an enclosed space. Lead acid batteries
contain sulfuric acid, which causes severe burns.
If acid contacts eyes, skin, or clothing, flush well with water. For contact
with the eyes, get immediate medical attention.
BATTERY CHARGING
Units have a small flywheel charger built into the engine flywheel assembly for recharging the starting battery. This flywheel charger generates a small AC current that passes through a diode assembly to produce DC charging current of about 1 to 3 Amps. This circuit is not designed to be used as a battery charging circuit to recharge dead batteries.
OPTIONAL DOLLY KIT
An optional 4-wheel dolly kit is available for this generator. The dolly kit comes with instructions and parts list.
CAUTION: EQUIPMENT DAMAGE
Be sure to check the wheels properly before operating the generator. Ensure
the brake has been applied. Allowing the unit to move will cause damage to the
unit, drop cords or loads.
INITIAL START UP
The throttle control on these generators is preset and locked to operate at 3600 RPM (nominal) with no load speed set at 3690 RPM. Only a trained service technician should be allowed to adjust this speed setting
NOTICE: ENGINE START LOCKOUT
This unit will not start if it is low on oil. The lubricating oil level must be at the full mark before the engine will start and run.
BASIC OPERATION
If the engine is cold and stiff or if the battery is not fully charged, starting can be made easier by slowly hand cranking the engine through the compression stroke before pushing the starter switch. This permits the starter to gain momentum before the heavy load of the compression stroke occurs. This minimizes the drain on the battery and improves the possibility of starting under such adverse conditions. Always keep the battery charged, especially during cold weather operation.
-
Check oil level, refill as needed.
-
Turn on the fuel supply. Ref “A”. Lever pointing up or down is on, lever sideways is off.
-
Engage the choke by pulling it out. A warm engine will require less choking than a cold engine.
-
Turn the engine switch to the “on” position.
-
Operating the starter. Rotate the key switch briefly to the START position. The starter life is improved by using shorter starting cycles with time to cool off between cranking cycles. Do not operate the starter more than 5 seconds and wait at least 10 seconds before operating the starter again. Repeat cycle if necessary.
-
When the engine starts, release the key switch, allowing it to return to the “on” position.
-
Gradually push the choke as the engine warms up.
-
The engine should promptly come up to operating speed.
CAUTION: EQUIPMENT DAMAGE
Never permit the choke to remain on after the engine has run for a short time.
It is not necessary to choke the engine when it is warm. Avoid over-choking.
STARTING HINTS
COLD WEATHER
- Use the proper oil for the temperature expected.
- Use fresh winter grade fuel. Winter grade gasoline is blended to improve starting. Do not use summer grade gasoline.
HOT WEATHER
- Use the proper oil for the temperature expected.
- Use only summer blended gasoline. Using gasoline left over from winter may cause the unit to vapor lock.
STOPPING AND STORING
- Move the key to the “OFF” position.
- Turn off the fuel supply valve.
- Before extended storage (over 30 days) certain precautions must be taken to ensure the fuel doesn’t deteriorate and clog the fuel system.
NOTE: The use of a fuel additive, such as Sta-Bil or equivalent will minimize the formation of gum deposits during storage. The additive may be added to gasoline in the engines fuel tank or to gasoline in a storage container.
-
Add the fuel stabilizer to the fuel in the tank and run for 2 minutes to circulate the stabilizer throughout the fuel system.
-
If you choose to remove the remaining fuel from the fuel tank, it must be drained into an approved container.
-
Start the engine and allow it to run until all the fuel in the carburetor and the fuel lines has been used up and the engine stops.
NOTE: Running the engine to use up the fuel in the lines and carburetor will still leave a small amount of fuel in carburetor. It is best extended storage to treat the fuel before draining. -
While the engine is warm, drain the oil and refill with fresh oil.
-
Clean dirt and chaff from cylinder, cylinder head fins, blower housing, screen, and muffler areas.
-
Store in a clean and dry area.
OPERATING SPEED
The engine-generator must be run at the correct speed in order to produce the proper electrical voltage and frequency.
CAUTION: EQUIPMENT DAMAGE
The output voltage should be checked to ensure the generator is working
properly prior to connecting a load to the generator. Failure to do so could
result in damage to equipment plugged into the unit and possible injury to the
individual.
All engines have a tendency to slow down when a load is applied. When the
electrical load is connected to the generator, the engine is more heavily
loaded, and as a result, the speed drops slightly. This slight decrease in
speed, together with the voltage drop within the generator itself, results in
a slightly lower voltage when the generator
is loaded to its full capacity than when running no load.
The slight variation in speed also affects the frequency of the output
current. This frequency variation has noappreciable effect in the operation of
motors, lights, and most appliances. However, electronic equipment and clocks
will be affected if correct RPM is not maintained. See Load vs. Output chart.
Although individual units and models vary slightly, the normal voltage and frequency of the engine-generator described in this manual are approximately as follows, under varying loads:
LOAD vs. OUTPUT
Generator Load| Speed (RPM)| Frequency (Hz)| Voltage
None| 3690| 61.5| 125V
Half| 3600| 60.0| 120V
Full| 3510| 58.5| 115V
The speed of the engine was carefully adjusted at the factory so that the generator produces the proper voltage and frequency. For normal usage, the speed setting should not be charged. If the generator is being run continuously on a very light load, it is often advisable to lower the operating speed slightly.
Reference “D” in the following image is the speed adjustment for this engine.
CAUTION: EQUIPMENT DAMAGE
SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A QUALIFIED SERVICE TECH. Whenever
making any speed adjustments, check the unit with a voltmeter and a frequency
meter or a tachometer and be sure the voltage and speed are correct.
Lower voltage may damage both the generator and any load connected to it. Running the engine at excessively high speeds results in high voltage, which may significantly shorten the life of appliances being used.
Output voltage should be checked periodically to ensure continued proper operation of the generating plant and appliances. If the generator is not equipped with a voltmeter, it can be checked with a portable meter.
CONNECTING THE LOADS
The engine-generator covered in this manual was designed for portable use. Do NOT operate indoors. The unit should be stored in a warm, dry location. Move the unit outdoors to a flat, dry location for use.
WARNING: PERSONAL DANGER
Operating any engine driven generator without proper air flow can result in
personal injury or death. DO NOT operate this unit inside a home or garage,
near vents or windows, or anywhere carbon monoxide gas could accumulate.
APPLYING THE LOADS
Allow the engine to warm up for two or three minutes before applying any load. This will allow the engine to reach normal operating temperature and oil to circulate throughout the engine. A short warm-up time will permit the engine to work more efficiently when the load is applied and will reduce the wear in the engine, extending its life.
Receptacles have been provided to allow loads to be connected to the generator. The loads should be added one at a time. If a large motor is being started: or multiple motors are being started, they should be started individually and the largest should be started first.
CAUTION: EQUIPMENT OVERLOAD
Keep the generator load within in the generator and receptacle nameplate
rating. Overloading may cause damage to the generator and/or the loads. Most
electric tools and appliances will have the voltage and amperage requirements
on their individual nameplates.
When in doubt, consult the manufacturer or a local electrician. The nameplate
amperage rating for electric motors can be misleading. See “Starting Electric
Motors” in the Unit Capabilities.
These engine-generator sets are inherently self regulating based on engine speed. The engine governor will automatically adjust itself to the load. No harm to the generator will result if it is operated with no load connected. Proper utilization of the receptacles located on the control panel is necessary to prevent damage to either the receptacles or the generator. The generator is a limited source of electrical power, therefore, pay special attention to the receptacle and generator ratings. The nameplate rating can be obtained through a single receptacle as long as the receptacles amperage rating is not exceeded.
GROUNDING
Proper grounding of your generator is application dependent. Carefully
evaluate your planned use of your generator to understand which grounding you
require.
If you are not sure what to do, contact a competent professional to assist
you. The NFPA 70 250:34-35 are good technical references.
STANDARD PORTABLE GENERATOR
Your WINCO portable generator ships with a bonded neutral. You can safely use this generator without external grounding as long as all loads are powered through the receptacle panel.
VEHICLE-MOUNTED GENERATOR
Your WINCO portable generator ships with a bonded neutral. When mounted to a vehicle to safely distribute power it is necessary that the generator frame is bonded to the vehicle frame. The generator should only supply equipment that is cord and plug connected through receptacles mounted on the generator or the vehicle.
PERMANENTLY INSTALLED GENERATORS
This WINCO portable generator ships with a bonded neutral and overcurrent
protection. NFPA 70 refers to this as a “separately derived system.” When
connecting it to a building a transfer switch specifically designed for GFCI
and bonded neutral generators is required.
WIRING
Plug your tools such as drills, saws, blowers, sump pump, and other items to be powered directly into the generator receptacles. Before plugging in all the tools and cord sets, recheck the rating of the generator set. Be sure it can handle the intended load and is compatible with the voltage, phase, and current ratings. ‘Hard wiring’ this unit directly into a temporary construction site electrical system is NOT A SIMPLE DO-IT-YOURSELF JOB. For your safety, all wiring must be done by a qualified electrician and conform to the National Electric Code and comply with all state/local codes and regulations. Check with local authorities before proceeding.
WARNING: PERSONAL DANGER
A fully isolated, three-pole double throw manual transfer switch must be
installed any time a generator is being connected to an existing distribution
system.
CAUTION: EQUIPMENT DAMAGE
Check phase rotation. Improper phase rotation can result in equipment damage.
-
These engine-generator sets are designed for portable heavy duty commercial use. On 208/230V machines, receptacles are provided on the control panel to permit both L-N and L-L connections. Each of the three L-N receptacles is connected to one leg allowing for an evenly balanced loads. The full power plug is capable of three phase power.
The 480V machines are not equipped with any L-N plugs and come with a full power receptacle.
Each generator ships with a compatible full power plug. Consult a licensed electrician for wiring the TemPower plug and connecting it as temporary service. -
If the generator set is connected to an existing distribution system, a fully isolated manual transfer switch must be installed. The transfer switch prevents damage to the generator and the other circuit components if main line power is restored while the generator is connected.
Installing a transfer switch also permits the use of normal fusing. -
Many homes and construction sites are wired for at least 60 to 100 Amp entrance service, much greater than the capacity of this portable generator. When installing the generator at these sites, a secondary emergency distribution panel may have to be installed. The emergency distribution panel must be installed by a licensed electrician according to all applicable codes. The electrician will move the critical circuits to be powered during the outage to the emergency panel.
Keep in mind only a limited amount of amperage is available from the generator set. Some circuit breakers may still have to be turned off to prevent an overload on the generator during the initial start up. See the nameplate on your generator for the amperage capabilities of your unit.
CAUTION: EQUIPMENT DAMAGE
Failure to properly limit and balance the load applied to the generator will
cause the generator to produce low voltage and may damage the engine generator
set. It may also cause severe damage to the loads connected to the generator
at that time. Improper loading of the generator set constitutes abuse and will
not be covered by warranty.
ENGINE CARE
MAINTENANCE SCHEDULE
If major engine service or repair is required, contact an authorized engine service center. The manufacturer of these engines has established an excellent world-wide engine service organization. Engine service is very likely available from a nearby authorized dealer or distributor. See following table
REGULAR SERVICE PERIOD (3)
Perform at every indicated month or operating hour interval, whichever comes
first.| Each Use| First Month or 20 Hrs| Every 6 Months or 100 Hrs| Every Year
or 300 Hrs| Every 2
Years
or
500 Hrs
| Refer
to
Page
---|---|---|---|---|---|---
ITEM
Engine oil| Check level| | | | | | 8
Change| | | | | | 8
Engine oil filter| Replace| Every 200 Hrs.| 9
Air cleaner| Check| | | | | | 9
Clean| | | (1)| | | 9
Replace| | | | | *
Spark plug| Check-adjust| | | | | | 10
Replace| | | | |
Spark arrester (applicable types)| Clean| | | | | | 11
Idle speed| Check-adjust| | | | (2)| | **
Valve clearance| Check-adjust| | | | (2)| | **
Combustion chamber| Clean| After every 1000 Hrs. (2)| **
Fuel filter| Replace| | | | (2)| | **
Fuel tube| Check| Every 2 years (Replace if necessary) (2)| **
-
Replace the paper filter element only.
-
- Refer to the Shop Manual.
- Service more frequently when used in dusty areas.
- These items should be serviced by your Honda servicing dealer, unless you have the proper tools and are mechanically proficient. Refer to the Honda shop manual for service procedures.
- For commercial use, log hours of operation to determine proper maintenance intervals.
CHECKING THE OIL LEVEL
The oil level must always be checked before the engine is started. Refer to page 6 of this manual for instructions on checking the oil level. Take care to remove any dirt or debris from around the oil plug before removing. Be sure the oil level is maintained.
CHANGING THE OIL
Refer to the Maintenance Schedule Chart for required oil change intervals.
Outdoor temperatures determine the proper oil viscosity for the engines. Winco recommends our 5W-30 fully synthetic oil to give you excellent protection in cold temperatures while maintaining excellent performance in warmer weather
-
Start the engine and warm it up, stop the engine and remove the spark plug wire to prevent it from accidentally being started.
-
This engine has an oil drain valve for your convenience. Attach a neoprene hose and drain the oil into an approved container.
-
Remove the oil filter and dispose of it properly.
-
Before you install the new oil filter, clean the filter mounting base and coat the seal of the new oil filter will clean engine oil.
-
Install the oil filter by hand until the gasket contacts the oil filter adapter, then tighten the oil filter 1/2 to 3/4 turns.
-
Replace oil drain bolt making sure the sealing washer is in place.
-
Remove the oil filter plug and refill with new oil. Make sure to use the proper grade oil based on your operating temperature.
NOTE: This engine requires 57 to 58 ounces (1.78 to 1.81 quarts) of oil if it is completely drained. Use caution when refilling the engine as some residual oil may have remained in the engine. Always use the dipstick when filling the engine with oil to prevent overfilling. -
Replace filter plug.
-
Start the engine and warm it up.
-
After warming up the engine, recheck the oil level and refill as necessary to bring it to the proper level.
DUAL ELEMENT AIR FILTER
Clean and/or replace the foam pre-cleaner and the air filter annually or every 100 hours. Service more often under dusty conditions.
WARNING: EQUIPMENT DAMAGE
Never start or run the engine with the air filter removed.
-
Unsnap the air cleaner cover latches and remove the cover.
-
Remove the wing nut.
-
Remove the paper filter element and foam element from the air cleaner case.
-
Remove the foam filter elements from the paper filter element.
-
Inspect both filter elements and replace them if damaged. Always replace the paper filter element at the scheduled interval.
-
To loosen debris, gently tap the air filter on a hard surface. If the air filter is excessively dirty replace with a new filter. You can use pressurized air (not to exceed 30 psi) to clean the filter. Always blow the compressed air from inside to the outside.
-
Wash the foam filter element in liquid detergent and water. Then allow it to thoroughly air dry. Dip the foam filter element in clean engine oil and squeeze out all the excess before reinstalling it. The engine will smoke when started if too much oil is left in the foam.
-
Clean the dirt from the inside of the air cleaner body and cover. Reinstall the air filter in housing making sure the packing is in place beneath the filter element.
Tighten the wing nut securely. -
Install and secure the cover.
SPARK PLUG
Replace annually or every 300 hours of operation. Always replace with the same
spark plug that came in the engine and check gap before installing. Spark plug
gap is 0.030”.
Poor spark will also occur if spark plug wire does not fit firmly on spark
plug. If this happens, reform the terminal to fit firmly on spark plug tip.
CARBON CANISTER
Designed to collect, store, and dispose of fuel vapors created in the fuel tank/fuel system. The canister should last the life of the unit as long as it stays dry
AVR WIRING
AUTOMATIC VOLTAGE REGULATOR
The following is a list of connections on the AVR. These have been factory set
and other than voltage adjustment, should never be changed.
VOLT: Voltage. Rotate clockwise to increase voltage.
STAB: Stability.
HZ: Low Frequency.
AMP: Overload.
GENERATOR CARE
Proper care and maintenance of the generator is necessary to ensure a long trouble free life.
EXERCISING THE GENERATOR
The generator should be operated every three to four weeks. It should be operated for a period of time sufficient to warm the unit up and to dry out any moisture that has accumulated in the windings. If left, this moisture can cause corrosion in the winding. Frequent operation of the enginegenerator set will also ensure that the set is operating properly should it be needed in an emergency.
GENERATOR MAINTENANCE
Any major generator service, including the installation or replacement of parts, should be performed only by a qualified electrical service technician. USE ONLY FACTORY APPROVED REPAIR PARTS.
- Bearing – The bearing used in these generators is a heavy duty, double sealed ball bearing. They require no maintenance or lubrication.
- Receptacles – Quality receptacles have been utilized. If a receptacle should become cracked or otherwise damaged, replace it. Using damaged or cracked receptacles can be both dangerous to the operator and destructive to the equipment.
CLEANING
Remove dirt and debris with a cloth or brush. DO NOT use high pressure spray to clean either the engine or the generator. The high pressure spray could contaminate the fuel system and the generator components.
-
Keep the air inlet screen on both the engine and generator free of any dirt or debris to ensure proper cooling. At least yearly, remove the blower housing on the engine and clean the chaff and dirt out of the engine cooling fins and fly wheel. Clean more often if necessary.
Failure to keep these areas clean may cause overheating and permanent damage to the unit. -
Periodically clean muffler area to remove all grass, dirt, and combustible debris to prevent a fire.
-
On engine mufflers equipped with spark arresters, the spark arrester must be removed every 50 hours for cleaning and inspection. Replace if damaged.
TROUBLESHOOTING TABLE
Problem | Possible Causes |
---|---|
Won’t start | Low oil level Fouled spark plug Out of fuel |
Start switch in OFF position Fuel Valve turned off Plugged fuel filter
Blown fuse in key switch
Voltage too low| Engine speed is too low Generator overloaded Defective stator
Defective rotor (field) Adjust AVR
Defective AVR
Circuit breaker trips| Defective load Defective receptacle Excessive load
Voltage too high| Engine speed is too high
Generator overheating| Overloaded Insufficient ventilation
No output voltage| Short in load (disconnect)
Tripped or defective circuit breaker Broken or loose wire
Defective receptacle
No residual magnetism (in generator) Defective stator
Defective rotor (field) GFCI receptacle tripped
Adjust AVR
Defective AVR
WIRING DIAGRAM
208V & 230V
480V
WINCO warrants to the original purchaser for 36 months or 1000 hours, whichever occurs first, that goods manufactured or supplied by it will be free from defects in workmanship and material, provided such goods are installed, operated and maintained in accordance with WINCO written instructions and applicable codes.
WINCO’s sole liability, and Purchaser’s sole remedy for a failure under this warranty, shall be limited to the repair of the product. At WINCO’s option, material found to be defective in material or workmanship under normal use and service will be repaired or replaced. For warranty service, return the product within the warranty period, to your nearest WINCO Authorized Service Center or to WINCO in Le Center Minnesota.
Duration Consumer, Commercial and Rental
Parts & Labor: 24 Months
Parts Only: 24-36 Months
EXCLUSIONS:
- Normal maintenance consumables or labor.
- This warranty does not cover travel time, mileage or labor for removal or re-installation of WINCO product from its application.
- Normal wear and tear.
- Costs of rental equipment.
- WINCO does not warrant engines. Engines are covered exclusively by the warranties of their respective manufacturers.
- WINCO does not warrant component parts that are warranted by their respective manufacturers.
- WINCO does not warrant modifications or alterations which were not made by WINCO.
- WINCO does not warrant products which have been subjected to misuse and/or negligence or have been involved in an accident. Proof of proper maintenance must be furnished upon request.
THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN. THERE ARE NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, OR OTHERWISE CREATED, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY, OR WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.
WINCO is liable for the repair or replacement of the product only and is not liable for incidental or consequential damages as permitted by your state. This warranty gives you specific legal rights which may vary from state to state.
CALIFORNIA EVAPORATIVE EMISSION CONTROL
WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board is pleased to explain the evaporative emission control system’s warranty on your model 2020 generator. In California, new equipment that uses small off-road engines must be designed, built, and equipped to meet the State’s stringent anti-smog standards. WINCO must warrant the evaporative emission control system on your generator for the period listed below provided there has been no abuse, neglect or improper maintenance of your equipment leading to the failure of the evaporative emission control system.
Your evaporative emission control system may include parts such as: carburetor, fuel tank, fuel cap, fuel lines (for liquid fuel and fuel vapors), fuel line fittings, fuel line clamps, carbon canisters, and carbon canister mounting brackets.
MANUFACTURER’S WARRANTY COVERAGE
The evaporative emission control system is warranted for two years. If any evaporative emission related parts on your equipment are defective, the parts will be repaired or replaced by WINCO.
COPY YOUR MODEL AND SERIAL NUMBER HERE
No other WINCO generator has the same serial number as yours.
If you should ever need to contact us concerning this unit, it will help us to
respond to your needs faster.
MODEL __
SERIAL NUMBER
PURCHASE DATE
DEALER NAME ___
DEALER PHONE # ____
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>