STELPRO VUH Series Vertical Unit Heater User Guide
- June 5, 2024
- StelPro
Table of Contents
USER’S GUIDE
VUH SERIES
VERTICAL UNIT HEATER
REPLACEMENT COMPONENT LIST INCLUDED
This unit complies with CSA standards
For further information or to consult this guide online, please visit our website at www.stelpro.com
WARNING
Before installing and operating this product, the user and/or installer must
read, understand and follow these instructions and keep them handy for future
reference. If these instructions are not followed, the warranty will be
considered null and void and the manufacturer deems no further responsibility
for this product.
This product must be installed by a qualified person and connected by a
certified electrician , according to the electrical and building codes
effective in your region.
Make sure that all screws and electrical terminal connections are tightly
secured before operating the unit in case they would have loosened during
transportation.
The following instructions must be adhered to in order to avoid personal
injuries or property damages, serious injuries, and potentially fatal electric
shocks.
Make sure that all screws and electrical terminal connections are tightly
secured before operating the unit in case they would have loosened during
transportation.
Protect the heating unit with the appropriate circuit breaker or fuse, in
accordance with the nameplate.
Make sure the line voltage (volt) is consistent with that indicated on the
unit’s nameplate.
This unit must be grounded. Switch off the power at the circuit breaker/fuse
before installing, repairing and cleaning the unit.
Make sure the unit is appropriate for the intended use (if needed, refer to
the product catalog or a representative).
RECOMMENDED HEATING CAPACITY:
1.25 W/cubic foot (0.03 m³).
It corresponds to 10 W/square foot (0.09 m²) based on a standard ceiling
height of 8 feet (2.44 m). Do not install the unit where objects or pieces of
furniture could be heat damaged.
If the unit’s capacity is insufficient for the size of the room, it will be in
operation continuously, and may become defective earlier and turn yellow.
Respect distances and positions indicated in the installation section. If
the installer or user modifies the unit, they will be held responsible for any
damage resulting from this modification, and the CSA certification could be
void. This unit must not come into contact with a water source and must be
protected from splashes (e.g. a wet mop). Do not use it if any part has been
immersed. Moreover, do not turn it on or off when standing in water or if your
hands are wet.
When cutting or drilling into a wall, do not damage electrical wiring and
other hidden utilities.
Do not install this product on walls made of synthetic material such as, but
not limited to, carpet and wallpaper.
When starting up the unit for the first time or after a long period, it is
normal that it produces some temporary odours and whitish smoke. Because this
unit is hot when in use, it may pose risks even in normal operation.
Therefore, be careful and responsible when using it. To avoid burns, do not
let bare skin touch hot surfaces. Let the unit cool down for few minutes
before handling (it will stay warm for some time after shut-down).
It is the user’s responsibility to ensure that objects including, but not
limited to, shelves or plastic containers do not come in contact with the unit
and to keep them at least 24 inches (61 cm) from the unit. Never block air
vents. This obstruction could lead to overheating, which could result in a
fire. Do not insert or allow foreign objects to enter any air vent as this may
cause electric shocks, a fire, or damages to the unit. This unit has hot and
arcing or sparking parts inside. It is not designed to be used or stored in
wet areas or areas containing flammable liquids, combustible materials, or
corrosive, abrasive, chemical, explosive, and flammable substances such as but
not limited to, gasoline, paint, chlorine, sawdust, and cleaning products.
Some areas are dustier than others. Thus, it is the user’s responsibility to
evaluate if the unit must be cleaned based on the amount of dirt accumulated
on and inside air vents. Accumulated dirt can lead to a component malfunction
or give a yellowish colour to unit. Failure to install and maintain unit in
accordance with these instructions poses a fire hasard.
Thermal protection activation indicates that the unit has been subjected to
abnormal operating conditions. If the thermal protection remains activated or
activates and deactivates repeatedly, it is recommended that a qualified
electrician or a certified repair centre examine the unit in order to make
sure it is not damaged. (Refer to the limited warranty)
If the unit is damaged or defective, cut off power supply at circuit breaker and call a certified repair centre. (Refer to the limited warranty)
Note: When a part of the product specification must be changed to improve operability or other functions, priority is given to the product specification itself. In such instances, the instruction manual may not entirely match all the functions of the actual product. Therefore, the actual product and packaging, as well as the name and illustration, may differ from the manual.
SPECIFICATIONS
VERTICAL UNIT HEATER
MODEL | VUH |
---|---|
WATTS | 5 TO 10 KW |
VOLTS | 208 V, 240/208 V, 347 V, 600 V |
WEIGHT | 75 LB / 34 KG |
TECHNICAL DRAWINGS
INSTALLATION ****
For the best results, the following distances should be respected when installing these unit heaters :
MINIMUM HEIGHT FROM THE FLOOR | MINIMUM DISTANCE FROM THE WALL |
---|---|
8 FT (2.4 M) | 24 IN (61 CM) |
- When using a wall-mounted thermostat, install the thermostat on an interior wall or beam, away from cold airflow, other internal heat sources or the hot air discharge coming directly from the actual unit heater itself. Make sure to insulate the thermostat when installed on a steel beam.
- These unit heaters are designed to be hung from overhead, with chain, cable, or rigid supports. (not included with heater)
- On top of 5 to 10 kW unit heaters, there is four (koe Ø1/2″) 13-thread mounting holes for threaded rods.
- On top of 15 to 60 kW unit heaters, there are four eyebolts for chain suspension.
- Several optional cone diffusers are offered.
See the optional components section to obtain a complete list of cone diffuser available for optional orders.
MOUNTING HEIGHTS VS DIFFUSION SURFACES
kW| WITHOUT CONE| SINGLE CONE| TRIPLE CONE| QUADRUPLE
CONE
---|---|---|---|---
HEIGHT (A)| SURFACE (B)| HEIGHT (A)| SURFACE (B)|
HEIGHT (A)| SURFACE (B)| HEIGHT (A) SURFACE (B)
M| FT| M| FT| M| FT| M| FT| M| FT| M| FT| M| FT| M| FT
5-10| 4.| 12| 6.| 19| 3.| 10| 7.| 22| 3.| 10| 10.| 31| 3.| 10| 10.| 34
15-30| 6.| 20| 8.| 27| 4.| 12| 10.| 31| 4.| 15| 14| 46| 4.| 15| 15.| 50
40-60| 9.| 30| 14| 46| 5.| 16| 10| 33| 6.| 20| 15| 49| 6.| 20| 17.| 56
OPERATION
This heater must be controlled with a wall thermostat. (Thermostat not included with heater)
ELECTRICAL WIRING
All heaters are factory wired so only field supply wires 90°C and thermostat leads are brought to the heater. Connections are made to contactor or terminal block as shown on wiring diagram inside the powerbox cover. The ground fault protection connection must be made by connecting the green wire originating from the circuit breaker panel to the green screw situated inside the powerbox of the heater.
N.B.This product must be installed by a certified master electrician, in accordance with all local and national building codes.
MAINTENANCE ****
The motor and element of this heater are protected against overheating by heat
sensors called automatic thermal protections (cut-outs). If these thermal
protectors are activated continuously, this would indicate that the heater may
be defective and it should be verified immediately.
If the heater operates under normal circumstances, it is not necessary to
grease the motor. All of the motors installed in this series of unit heaters
have been permanently lubricated.
WARNING
- Cut off power supply before manipulating any internal wiring.
- Periodically remove dust and debris from elements and fan blade.
- Do not operate in environments where there are flammable materials.
- Unit heaters must be installed so that they are kept out of the reach of individuals.
REPLACEMENT COMPONENT LIST
REF. # | PART # | DESCRIPTION | MODEL(S) |
---|---|---|---|
1 | CONT-3022 | CONTACTOR 30A/240/208V 2 POLES | 15 TO 60 KWV |
2 | CONT-3512 | CONTACTOR 2P/120V/35A RESISTIVE | 15 TO 30 KW |
2 | CONT-3523 | CONTACTOR 35A/240/208V 3 POLES | 5 TO 30 KW |
2 | CONT-4013 | CONTACTOR 3P/120V/40A RESISTIVE | 5 KW |
2 | CONT-4023 | CONTACTOR 40A/240/208V 3 POLES | 40 TO 60 KW |
2 | CONT-5023 | CONTACTOR 50A/240/208V 3 POLES | 15 TO 30 KW |
2 | CONT-5099 | AUXILIARY CONTACT 15A/600V SERIES 42 | 15 TO 30 KW |
3 | EVUH1616 | ELEMENT 1666W/600V | 5 AND 7.5 KW |
3 | EVUH1613 | ELEMENT 1666W/347V CVB & VUH 5KW | 5 KW |
3 | EVUH1633 | ELEMENT 3333W/600V | 7.5 AND 10 KW |
3 | EVUH2625 | ELEMENT 2500W/600V | 15 KW |
3 | EVUH2633 | ELEMENT 3333W/600V | 20 AND 25 KW |
3 | EVUH2650 | ELEMENT 5000W/600V | 25 AND 30 KW |
3 | EVUH3644 | ELEMENT 4445W/600V | 40 AND 50 KW |
3 | EVUH3666 | ELEMENT 6667W/600V | 50 AND 60 KW |
3 | EVUH2513 | ELEMENT 2500W/347V VUH 7.5KW | 7.5 KW |
3 | EVUH3313 | ELEMENT 3333W/347V VUH 10KW | 5 KW |
3 | EVUH1618 | ELEMENT 1666W/208 VOLTS VUH1 | 5 KW |
3 | EVUH2512 | ELEMENT 2500W/240V VUH1 | 7.5 KW |
3 | EVUH2622 | ELEMENT 2500W/240V VUH2 | 15 KW |
3 | EVUH2632 | ELEMENT 3333W/240V VUH2 | 15 KW |
3 | EVUH2638 | ELEMENT 3333W/208V VUH2 | 15 TO 30 KW |
3 | EVUH2652 | ELEMENT 5000W/240V VUH2 | 15 TO 30 KW |
3 | EVUH2658 | ELEMENT 5000W/208V VUH2 | 15 TO 30 KW |
3 | EVUH3312 | ELEMENT 3333W/240V VUH1 | 7.5 KW |
3 | EVUH3318 | ELEMENT 3333W/208V VUH1 | 10 KW |
4 | FD-001 | FAN DELAY | ALL |
5 | FS-005 | FUSE 15A CLASS CC 600V T.D. | ALL |
5 | FS-024 | FUSE 20A CLASS CC 600VAC T.D. | 15 TO 60 KW |
6 | BLA-015 | FAN BLADE 12″ | 5 KW |
6 | BLA-017 | FAN BLADE 12″ | 7 AND 10 KW |
6 | BLA-018 | FAN BLADE 16″ | 15 KW |
6 | BLA-019 | FAN BLADE 16″ | 20 KW |
6 | BLA-021 | FAN BLADE 16″ | 25 AND 30 KW |
6 | BLA-023 | FAN BLADE 23″ | 40 TO 60 KW |
7 | MO-022 | MOTOR 575V 60HZ 0.32A 3PH | 15 TO 30 KW |
7 | MO-028 | MOTOR 1125HP 240V 3PH | 5 TO 10 KW |
7 | MO-029 | MOTOR 1/8HP 600V 3PH | 15 TO 30 KW |
7 | MO-030 | MOTOR 3/4HP 600V 3PH | 40 TO 60 KW |
7 | MO-068 | 208-240V, 3.3 / 1.7A. 1/3HP, 1PH, 60HZ, CL.B. 1140 RPM | 15 TO 30 KW |
8 | PROT-016 | PROTECTION | 5 TO 10 KW |
8 | PROT-018 | PROTECTION | 15 TO 60 KW |
9 | R841C1029 | RELAY 240/24V (OPTIONAL) | ALL |
9 | R841C1169 | RELAY MEC. A/TRANSFORMER 208-240/24V | 15 TO 30 KW |
10 | TRF210100 | TRANSFORMER 240/120/100VA | 20 KW |
10 | TRF310025D | TRANSFORMER 347-380/120-240/25VA | 10 KW |
10 | TRF320250 | TRANSFORMER 347/240V/250VA | 10 KW |
10 | TRF610025D | TRANSFORMER 480-600/120-240/25VA | 10 KW |
10 | TRF610050D | TRANSFORMER 480/600-120/240 50VA | 15 TO 30 KW |
10 | TRF620200C | TRANSFORMER 600/240/200VA | 5 TO 10 KW |
10 | TRF620050C | TRANSFORMER 600/240/50VA | 15 TO 60 KW |
10 | TRF620250C | TRANSFORMER 480-600/120-240/250VA CLOSED (VUH) | 10 KW |
10 | TRF810025D | TRANSFORMER 208-416/120-240/25VA | 15 TO 30 KW |
11 | HOLD-005 | FUSE HOLDER 2 POLES 600V | ALL |
12 | HOLD-011 | FUSE HOLDER 3 POLES 600V | ALL |
13 | FS-017 | FUSE 50A CLASS J 600VAC, LOW-PEAK. T.D. | 15 TO 60 KW |
13 | FS-027 | FUSE 35A CLASS J 600VAC. LOW-PEAK. T.D. | 15 TO 60 KW |
13 | FS-027 | FUSE 45A CLASS J 600VAC, LOW-PEAK. T.D. | 15 TO 60 KW |
13 | FS-018 | FUSE 60A CLASS J. 600VAC, LOW-PEAK. T.D | 15 TO 30 KW |
13 | FS-016 | FUSE 40A CLASS J 600V T.D. | 20 KW |
13 | FS-025 | FUSE 30A. TYPE CC 600VAC.T.D | 15 TO 30 KW |
OPTIONAL COMPONENTS
CONE DIFFUSERS
PART # | CONE | KW |
---|---|---|
VUHSC1 | SINGLE | 05-10 |
VUHSC2 | SINGLE | 15-30 |
VUHSC3 | SINGLE | 40-60 |
VUH3C1 | TRIPLE | 5-10 |
VUH3C2 | TRIPLE | 15-30 |
VUH3C3 | TRIPLE | 40-60 |
VUH4C1 | QUADRUPLE | 5-10 |
VUH4C2 | QUADRUPLE | 15-30 |
VUH4C3 | QUADRUPLE | 40-60 |
DISCONNECT SWITCHES
# PIECE | DESCRIPTION |
---|---|
SWI-003 | VARIO DISCONNECT 63A/3 POLE |
SWI-016 | DISCONNECT, HANDLE, |
ROD 700V 100A/ 3POLE
SWI-018| DISCONNECT, HANDLE
ROD 700V 200N3 POLE
ACCESSORIES
PART # | DESCRIPTION |
---|---|
VUHC24 | 24V CONTROL CIRCUIT |
VUHFS | FAN SWITCH |
LIMITED WARRANTY
This limited warranty is offered by Stelpro Design Inc. (“Stelpro”) and applies to the following product made by Stelpro: model VUH. Please read this limited warranty carefully. Subject to the terms of this warranty, Stelpro warrants its products and their components against defects in workmanship and/or materials for the following periods from the date of purchase: 3 years. This warranty applies only to the original purchaser; it is non-transferable and cannot be extended.
CLAIM PROCEDURE
If at any time during the warranty period the unit becomes defective, you must
cut off the power supply at the main electrical panel and contact 1) your
installer or distributor, 2) your service center or 3) Stelpro’s customer
service department. In all cases, you must have a copy of the invoice and
provide the information written on the product nameplate. Stelpro reserves the
right to examine or to ask one of its representatives to examine the product
itself or any part of it before honoring the warranty. Stelpro reserves the
right to replace the entire unit, refund its purchase price, or repair a
defective part. Please note that repairs made within the warranty period must
be authorized in advance in writing by Stelpro and carried out by persons
authorized by Svtelpro.
Before returning a product to Stelpro, you must have a Stelpro authorization
number (RMA). To obtain it, call the customer service department at:
1-800-363-3414 (electricians and
distributors – French), 1-800-343-1022
(electricians and distributors – English), or
1-866-766-6020 (consumers). The
authorization number must be clearly written on the parcel or it will be
refused.
CONDITIONS, EXCLUSIONS, AND DISCLAIMER OF LIABILITY
This warranty is exclusive and in lieu of all other representations and
warranties (except of title), expressed or implied, and Stelpro expressly
disclaims and excludes any implied warranty of merchantability or implied
warranty of fitness for a particular purpose.
Stelpro’s liability with respect to products is limited as provided above.
Stelpro shall not be subject to any other obligations or liabilities
whatsoever, whether based on contract, tort, or other theories of law, with
respect to goods or services furnished by it, or any undertakings, acts, or
omissions relating thereto. Without limiting the generality of the foregoing,
Stelpro expressly disclaims any liability for property or personal injury
damages, penalties, special or punitive damages, damages for lost profits,
loss of use of equipment, cost of capital, cost of substitute products,
facilities, or services, shutdowns, slowdowns, or for other types of economic
loss or for claims of a dealer’s customers or any third party for such
damages. Stelpro specifically disclaims all consequential, incidental, and
contingent damages whatsoever.
This warranty does not cover any damages or failures resulting from: 1) a
faulty installation or improper storage; 2) an abusive or abnormal use, lack
of maintenance, improper maintenance (other than that prescribed by Stelpro),
or a use other than that for which the unit was designed; 3) a natural
disaster or an event out of Stelpro’s control, including, but not limited to,
hurricanes, tornadoes, earthquakes, terrorist attacks, wars, overvoltage,
flooding, water damages, etc. This warranty does not cover any accidental or
intentional losses or damages, nor does it cover damages caused by negligence
of the user or owner of the product. Moreover, it does not cover the cost of
disconnection, transport, and installation.
The warranty is limited to the repair or the replacement of the unit or the
refund of its purchase price, at the discretion of Stelpro. Any parts replaced
or repaired within the warranty period with the written authorization of
Stelpro will be warranted for the remainder of the original warranty period.
This warranty will be considered null and void and Stelpro will have the right
to refuse any claims if products have been altered without the written
authorization of Stelpro and if the nameplate numbers have been removed or
modified. This warranty does not cover scratches, dents, corrosion, or
discoloration caused by excessive heat, chemical cleaning products, and
abrasive agents. It does not cover any damage that occurred during the
shipping.
Some states and provinces do not allow the exclusion or limitation of
incidental or consequential damages and some of them do not allow limitations
on how long an implied warranty lasts, so these exclusions or limitations may
not apply to you. This warranty gives you specific legal rights and you may
have other rights which vary from state to state or from province to province.
STELPRO DESIGN INC.
Saint-Bruno-de-Montarville
Québec
J3V 6L7
INSVUH0622
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>