wilo 2056576 Protect Module C Instruction Manual
- June 5, 2024
- wilo
Table of Contents
Wilo-Protect-Modul C
Installation and operating instructions
|
---|---
|
|
General
1.1 About this document
These Installation and Operating Instructions are an integral part of the
product. They must be kept readily available at the place where the product is
installed. Strict adherence to these instructions is a precondition for the
proper use and correct operation of the product.
This Installation and Operating Instructions correspond to the relevant
version of the product and the underlying safety standards valid at the time
of going to print. These Installation and operating instructions are an
addition to the Installation and operating instructions for glandless
circulation pump type TOP-S/ TOP-SD/TOP-Z.
Safety
These operating instructions contain basic information which must be adhered to during installation and operation. For this reason, these operating instructions must, without fail, be read by the service technician and the responsible operator before installation and commissioning. It is not only the general safety instructions listed under the main point “safety” that must be adhered to but also the special safety instructions with danger symbols included under the following main points.
2.1 Designation of information in the operating instructions
Symbols:
General danger symbol
Danger due to electrical voltage
NOTE: …
Signal words:
DANGER!
An acutely dangerous situation.
Non-observance results in death or the most serious of injuries.
WARNING!
The user can suffer (serious) injuries. ‘Warning’ implies that (serious)
injury to persons is probable if this information is disregarded.
CAUTION!
There is a risk of damaging the pump/unit. ‘Caution’ implies that damage to
the product is likely if the information is disregarded.
NOTE:
Useful information on using the product. It draws attention to possible
problems.
2.2 Personnel qualifications
The installation personnel must have the appropriate qualification for this
work.
2.3 Danger in event of non-observance of the safety instructions
Non-observance of the safety instructions can result in risk of injury to
persons and damage to pump/unit. Non-observance of the safety instructions can
result in the loss of any claims to damages.
In detail, non-observance can, for example, result in the following risks:
- Failure of important pump/unit functions,
- Failure of required maintenance and repair procedures
- Danger to persons from electrical, mechanical and bacteriological influences,
- Property damage
2.4 Safety instructions for the operator
The existing directives for accident prevention must be adhered to.
Danger from electrical current must be eliminated. Local directives or general
directives [e.g. IEC, VDE, etc.] and local power supply companies must be
adhered to.
2.5 Safety instructions for inspection and installation work
The operator must ensure that all inspection and installation work is carried
out by authorized and qualified personnel, who are sufficiently informed from
their own detailed study of the operating instructions.
Work to the pump/unit must only be carried out when at a standstill.
2.6 Unauthorised alteration and spare part production
Alterations to the pump/unit are only permissible after consultation with the
manufacturer. Original spare parts and accessories authorized by the
manufacturer ensure safety.
The use of other parts can nullify the liability from the results of their
usage.
2.7 Unacceptable operating modes
The operating safety of the supplied pump/unit is only guaranteed for
conventional use in accordance with Section 4 of the operating instructions.
The limit values must on no account fall under or exceed those specified in
the catalog/ datasheet.
Transport and interim storage
On receipt of the product, check it for any damage incurred in transit. In the
event of damage in transit, the necessary steps must be taken with the carrier
before the relevant deadlines.
CAUTION! The danger of damage to the module!
The danger of damage due to improper handling during transport and storage.
- The Protect-Module C must be protected during transport and storage from moisture, frost, and mechanical damage.
- It must not be exposed to any temperature outside the range – 10 °C to +70°C.
Application
The TOP series circulating pumps come equipped with a standard terminal box.
A retrofit plug-in module is available for the pump with the Protect-Module C
(see title illustration). In addition to the pump functions, the Protect-
Module C also enables further signals as well as the performance of control
tasks.
When the Protect-Module C is deployed, external contractors and supplementary
switchgear are no longer required, with a corresponding effect on the
complexity of the installation.
Product data
5.1 Type Key
Example: Wilo-Protect-Modul C Type 22 EM
Protect-Modul | Series designation |
---|---|
C | Comfort |
Type 22 | Type designation: 22 or 32-52 |
EM | For mains connection: |
EM = 1~230 V, 50 Hz (single-phase motor)
DM = 3~400 V, 50 Hz (three-phase current motor)
5.2 Technical data
Connection current
Type 22 EM
Type 32-52 EM
Type 22 DM
Type 32-52 DM| 1~230 V, ±10 %, 50 Hz
1~230 V, ±10 %, 50 Hz
3~400 V, ±10 %, 50 Hz
3~400 V, ±10 %, 50 Hz
---|---
Frequency| 50 Hz
Terminal cross-section, all terminals| max. 2.5 mm
Temperature range of flow medium| -20 °C to +110 °C
Max. ambient temperature| +40 °C
Pump protection class| IP 44
Cable connections| 4xPG9
Electromagnetic compatibility:
Emitted interference
Immunity to interference| EN 61000-6-3
EN 61000-6-2
5.3 Scope of supply
- Protect-Module C
- Plug strip control and signal terminals
- Plug strip mains connection terminals and connection terminals WSK/SSM with connection cables
- Fixing screws (4)
- Installation and operating instructions
Description and function
6.1 Description of the Protect-Module C
The functions of the pump housing in the terminal box (mains connection,
thermal winding contact WSK or potential-free collective fault signal) are
transferred to the terminal box when the Protect-Module C is installed. The
fault acknowledgment button and the direction of the rotation control lamp, if
fitted, as well as the manual speed stage switching of the standard terminal
box continue to function when the Protect-Module C is installed.
The Protect-Module C is fitted to the standard terminal box of the pump in
place of the terminal box cover.
6.2 Functions and operation of the Protect-Module C
6.2.1 Light signals
There are three possible light signals on the display field:
-
Operation light signal (figure 1, position 1)
WARNING! The danger of electric shock
Even when the operation light signal is off, the voltage may be present on the Protect-Module. -
Fault signal light “Stoppage” (figure 1, position 2)
-
Fault signal light “Winding Overheat” (figure 1, position 3)
6.2.2 Fault acknowledgment buttons
-
Fault acknowledgment button on the pump (figures 3b, 3d, position 4)
If fitted, this button is used to reset the response of the integrated full motor protection. This fault reset is done before the fault reset on the Protect-Module C. -
Fault acknowledgment button on Protect-Module C (figure 1, position 4)
-
A fault displayed on the Protect-Module C is reset by briefly pressing this button ( < 1s).
-
Pressing and holding down the button ( ≥ 1s) triggers pump cycling in dual pump operation with integrated dual pump management.
6.2.3 Faults, light signals, signal contacts -
Single pump
The following table shows the links between possible faults and the reactions of light signals and signal contacts:
Operating element | Status | Possible causes |
---|---|---|
Operation light signal green | off | •No supply voltage. |
•Control input “Ext. Off” opened.
•Fault is present and has not yet been acknowledged.
flashing| •DP communication fault (only with a double pump).
Fault signal light “Stoppage” red| off| •No motor stoppage.
on| •Motor stoppage recognized.
•Mechanical blockage of pump
•Winding fault
flashing| •Motor stoppage acknowledged, the pump is in control loop 1).
Fault signal light “Winding Overheat” red| off| •No overheating.
on| •Overheat recognized.
•Pump overload
•Winding fault
•Unacceptable combination of medium temperature — ambient temperature
flashing| •Overheat acknowledged, the pump is in control loop 1).
Operating signal contact| open| •No supply voltage.
•Control input “Ext. Off” opened.
•Fault is present and has not yet been acknowledged.
closed| •Pump functioning, no-fault recognized.
Fault signal contact| open| •Fault is present.
•Pump is still in control loop 1).
closed| •Fault-free operation.
Fault signal light “Stoppage” red| off| •No motor stoppage.
on| •Motor stoppage recognized.
•Mechanical blockage of the pump.
•Winding fault.
After acknowledging a fault, the Protect-Module C will be in a special control
loop for up to 10 sec, depending on pump type and fault. If the fault is
recognized again during this process, the pump returns to fault status.
Table 1
-
Double pump:
The relationships between possible faults and the reactions of light signals and signal contacts depend on the following factors: -
Parametrization of signal contacts in individual operation/individual fault signal or joint operation/collective fault signal (function see Table 2)
-
Allocation of “Ext. Off” control inputs to master and slave
6.2.4 Double pump operation
A Protect-Module C must be installed for each of the two pumps.
The double pump functions on the Protect-Module C are:
- Main/Reserve operation with automatic switching to the standby reserve pump after 24 hours of real running time, the external control command “Ext. Off” interrupts the running time counter.
- Switching takes place through an overlap, i.e. at the time of switching, both pumps run simultaneously (for approx. 10 sec.). This avoids pressure surges and undersupplies in cooling and air-conditioning systems for example.
- The DIP switch 1 (figure 2b, position 1) determines which pump is the master (MA) and which pump is the slave (SL) (function see Table 2).
- The DIP switch 2 (figure 2b, position 1) determines whether the signal contacts “SSM” and “SBM” are individual or collective signals (function see Table 2).
- In the case of a fault in the working pump, the system switches to the standby pump after approx. 3 sec.
Single pump | Double pump |
---|---|
Master (MA) | Slave (SL) |
DIP Switch1: MA
DIP Switch2: I
Allocate terminals to Ext. Off| DIP Switch1: MA
DIP Switch2: Allocate terminals to Ext. Off| DIP Switch1: SL
DIP Switch2: Bridge
terminals to Ext. Off
DIP Switch1: MA
DIP Switch2: I
SSM: Collective fault signal for pump| DIP Switch1: MA
DIP Switch2: I
SSM: Individual fault signal for MA
DIP Switch2: I + II
SSM: Collective fault signal for MA + SL| DIP Switch1: SL
DIP Switch2: SSM:
Individual fault signal for SL DIP
Switch2:
SSM: Individual fault signal for SL
DIP Switch1: MA
DIP Switch2: I
SBM: Individual operating signal for pump| DIP Switch1: MA
DIP Switch2: I
SBM: Individual operating signal for MA
DIP Switch2: I + II
SBM: Collective operating signal for MA + SL| DIP Switch1: SL
DIP Switch2: SBM: Individual operating signal for SL
DIP Switch2:
SBM: Individual operating signal for SL
-: Setting of DIP switch not relevant
Installation and electrical connection
Installation and the electrical connection must be carried out in accordance
with local regulations and only by qualified personnel.
WARNING! The danger of personal injury
The applicable regulations on the prevention of accidents must be observed.
WARNING! The danger of electric shock
Potential dangers from electrical currents must be eliminated.
Local directives or general regulations [e.g. IEC, VDE, etc.] and those issued
by the local power supply company must be adhered to.
7.1 Installation and electrical connection of mains cable
-
Switch off the power supply to the pump,
CAUTION! The danger of damage to Protect-Module C
The module may only be plugged in and unplugged when the pump has been completely disconnected. -
Loosen the terminal box lid screws on the pump,
-
Remove terminal box lid,
-
Pinch off the power supply cable except for the protective lead PE: EM version (1~230V): L, N DM version (3~400V) L1, L2, L3 (figure 2a)
-
Remove plug strip with power supply terminals and connection terminals MP1/MP2 (figure 2b, position 5) with connection cables (figure 2b, position. 2.3) from the Protect-Module C. When removing, do not pull straight out, but begin at one corner of the plug strip,
-
Apply the plug strip cables to the corresponding terminals on the pump terminal box (figure 2c, figure 3),
-
Fit the power supply cable to the plug strip, Table 3 shows the allocation of module types to the terminal diagrams.
Protect-Module C| Terminal diagram
---|---
Type 22 EM
Type 32-52 EM
Type 22 DM
Type 32-52 DM| 3a
3b
3c
3d
Table 3
-
Remove the plug strip with control and signal terminals (figure 2b, position 4) from the Protect-Module C. When removing, do not pull straight
out, but begin at one corner of the plug strip,
8.1 Dismantle cable connection (PG 9) of the Protect-Module C,
8.2 Cut diaphragm seal,
8.3 Thread individual parts of the cable connection onto the control cable (figure 2d),
Pos. 1: Union connection
Pos. 2: Seal
Pos. 3: Strain relief
8.4 Insert control cable through cable connection into Protect-Module C,
8.5 Assemble cable connection, fastening union nuts tightly enough so that the cable can no longer be pulled out of the cable connection by hand.
CAUTION! The danger of damage to Protect-Module C
An incorrectly assembled cable connection may lead to a short-circuit in the module due to water penetration. This is a particular danger in cold water installations in which condensation constantly forms. -
Fix the control cable to the plug strip (figure 2 e),
-
Plug the plug strip with the control cable to the corresponding place in the Protect-Module C,
-
Set DIP switch (figure 2b, position 1) in accordance with Table 2,
-
Plug the Protect-Module C onto the plug strip with the power connections (figure 2f),
Note: Arrange power cables and leads so that they cannot be crushed when finally tightening the module installation.
In DM versions, it is essential before the final tightening of the module installation to check the direction of rotation with the direction of the rotation control lamp in the pump terminal box (figures 3c, 3d, position 1). -
Arrange the Protect-Module C over the terminal box structure and screw to the domes of the terminal box using the screws provided, tighten screws evenly diagonally (figure 2g).
• Stages 1 to 4 are not required for a new installation. Power connection is made directly on the corresponding plug strip with power connection terminals and connection terminals MP1/MP2.
• For a double pump, as previously described, two Protect-Modules C must be fitted. For integrated dual pump management, the DP terminals of the two Protect-Modules C must be connected to each other, see also figure 3e.
7.2 Electrical connection of control and signal clamps
For connection to a remote control center or building automation, the
following connections are provided:
-
Ext. Off: Control input with “drive priority off” for potential-free normally closed contacts, contact charge 24V, 10 mA.
In dual pump operation, Ext. Off on the master must be assigned to a potential-free normally closed contact, and Ext. Off on the slave must remain bridged.
The Ext. Off of the masterworks on the entire double pump, i.e. master and slave. -
SBM: Programmable run signal, potential-free normally opened contact, maximum contact capacity 250 VAC, 1 A.
-
SSM: Programmable fault signal, potential-free normally closed contact, maximum contact capacity 250 VAC, 1 A.
A serial interface is provided for integrated dual pump management: -
DP: Interface for integrated dual pump management, the connection terminals cannot be twisted. The connection cable (2 x 0/75 mm2) must be provided on-site. Wiring for all Protect-Modules is shown in the example in figure 3e.
Commissioning
CAUTION! The danger of damage to Protect-Module C
When commissioning, the Installation and operating instructions of the
glandless circulation pump types TOP-S/TOP-SD/TOP-Z must be observed.
NOTE: Rotation control (only for three-phase motors)
In pumps with a three-phase connection, before the final tightening of the
module installation, it is essential to check the direction of rotation with
the direction of the rotation control lamp in the pump terminal box (figures
3c, 3d, position 1).
- When the Protect-Module C is fully installed, switch on the power supply.
Maintenance
Maintenance and repair work must only be carried out by professionally
qualified personnel.
WARNING! The danger of electric shock
Potential dangers from electrical currents must be eliminated.
During all maintenance and repair work, the pump must be disconnected from the
power supply and secured against possible unauthorized reconnection.
Faults, causes, and remedies
see paragraph 6.2
If an operating fault of the pump / the Protect-Module C / system cannot be
corrected, please consult a professional technician or contact your nearest
Wilo Customer Service point or representative.
Spare parts
Spare parts may be ordered through local professional technicians and/or Wilo
Customer Service.
To avoid queries and order errors, all data on the rating plate must be given
along with every order.
Subject to technical changes!
Wilo – International (Subsidiaries)
Argentina
WILO SALMSON
Argentina S.A.
C1295ABI Ciudad
Autónoma de Buenos Aires
T+ 54 11 4361 5929
info@salmson.com.ar
Austria
WILO Pumpen
Österreich GmbH
1230 Wien
T +43 507 507-0
office@wilo.at
Azerbaijan
WILO Caspian LLC
1065 Baku
T +994 12 5962372
info@wilo.az
Belarus
WILO Bel OOO
220035 Minsk
T +375 17 2503393
wilobel@wilo.by
Belgium
WILO SA/NV
1083 Ganshoren
T +3224823333
info@wilo.be
Bulgaria
WILO Bulgaria Ltd.
1125 Sofia
T +359 2 9701970
info@wilo.bg
Canada
WILO Canada Inc.
Calgary, Alberta T2A 5L4
T +1 403 2769456
bill.lowe@wilo-na.com
China
WILO China Ltd.
101300 Beijing
T +861058041888
wilobj@wilo.com.cn
Croatia
WILO Hrvatska d.o.o.
10090 Zagreb
T +38 51 3430914
wilo-hrvatska@wilo.hr
Czech Republic
WILO Praha s.r.o.
25101 Cestlice
T +420 234 098711
info@wilo.cz| Denmark
WILO Danmark A/S
2690 Karlslunde
T +45 70 253312
wilo@wilo.dk
Estonia
WILO Eesti OÜ
12618 Tallinn
T +372 6509780
info@wilo.ee
Finland
WILO Finland OY
02330 Espoo
T +358 207401540
wilo@wilo.fi
France
WILO S.A.S.
78390 Bois d’Arcy
T +33 1 30050930
info@wilo.fr
Great Britain
WILO (U.K.) Ltd.
DE14 2WJ BurtonUpon-Trent
T +44 1283 523000
sales@wilo.co.uk
Greece
WILO Hellas AG
14569 Anixi (Attika)
T +302 10 6248300
wilo.info@wilo.gr
Hungary
WILO Magyarország Kft
2045 Törökbálint
(Budapest)
T +36 23 889500
wilo@wilo.hu
India
WILO India Mather and
Platt Pumps Ltd.
Pune 411019
T +91 20 27442100
service@pun.
matherplatt.co.in
Indonesia
WILO Pumps Indonesia
Jakarta Selatan 12140
T +62 21 7247676
citrawilo@cbn.net.id| Ireland
WILO Engineering Ltd.
Limerick
T +353 61 227566
sales@wilo.ie
Italy
WILO Italia s.r.l.
20068 Peschiera Borromeo
(Milano)
T +39 25538351
wilo.italia@wilo.it
Kazakhstan
WILO Central Asia
050002 Almaty
T +7 727 2785961
in.pak@wilo.kz
Korea
WILO Pumps Ltd.
621-807 Gimhae
Gyeongnam
T +82 55 3405890
wilo@wilo.co.kr
Latvia
WILO Baltic SIA
1019 Riga
T +371 67 145229
mail@wilo.lv
Lebanon
WILO SALMSON
Lebanon
12022030 El Metn
T +961 4 722280
wsl@cyberia.net.lb
Lithuania
WILO Lietuva UAB
03202 Vilnius
T +370 5 2136495
mail@wilo.lt
The Netherlands
WILO Nederland b.v.
1551 NA Westzaan
T +31 88 9456 000
info@wilo.nl
Norway
WILO Norge AS
0975 Oslo
T +47 22 804570
wilo@wilo.no
Poland
WILO Polska Sp. z.o.o.
05-090 Raszyn
T +48 22 7026161
wilo@wilo.pl| Portugal
Bombas Wilo-Salmson
Portugal Lda.
4050-040 Porto
T +351 22 2080350
bombas@wilo.pt
Romania
WILO Romania s.r.l.
077040 Com. Chiajna Jud.
Ilfov
T +40 21 3170164
wilo@wilo.ro
Russia
WILO Rus ooo
123592 Moscow
T +7 495 7810690
wilo@wilo.ru
Saudi Arabia
WILO ME – Riyadh
Riyadh 11465
T +966 1 4624430
wshoula@wataniaind.com
Serbia and Montenegro
WILO Beograd d.o.o.
11000 Beograd
T +381112851278
office@wilo.co.yu
Slovakia
WILO Slovakia s.r.o.
82008 Bratislava 28
T +421 2 45520122
wilo@wilo.sk
Slovenia
WILO Adriatic d.o.o.
1000 Ljubljana
T +38615838130
wilo.adriatic@wilo.si
South Africa
Salmson South Africa
1610 Edenvale
T +27 11 6082780
errol.cornelius@
salmson.co.za
Spain
WILO Ibérica S.A.
28806 Alcalá de Henares
(Madrid)
T +34 91 8797100
wilo.iberica@wilo.es| Sweden
WILO Sverige AB
35246 Växjö
T +46 470 727600
wilo@wilo.se
Switzerland
EMB Pumpen AG
4310 Rheinfelden
T +41 61 83680-20
info@emb-pumpen.ch
Taiwan
WILO-EMU Taiwan Co. Ltd.
110 Taipeh
T +886 227 391655
nelson.wu@
wiloemutaiwan.com.tw
Turkey
WILO Pompa Sistemleri
San. ve Tic. A.S¸.
34530 Istanbul
T +90 216 6610211
wilo@wilo.com.tr
Ukraina
WILO Ukraina t.o.w.
01033 Kiew
T +38 044 2011870
wilo@wilo.ua
United Arab Emirates
Wilo Middle East FZE
Jebel Ali – Dubai
T +971 4 8864771
info@wilo.com.sa
USA
WILO-EMUUSA LLC
Thomasville,
Georgia 31792
T +1 229 5840097
info@wilo-emu.com
WILO USA LLC
Melrose Park, Illinois 60160
T +1708 3389456
mike.easterley@wilo-na.com
Vietnam
WILO Vietnam Co Ltd.
Ho Chi Minh City, Vietnam
T +84 8 38109975
nkminh@wilo.vn
---|---|---|---|---
Wilo – International (Representation offices)
Algeria
Bad Ezzouar, Dar El Beida
T +213 21 247979
Armenia
375001 Yerevan
T +374 10 544336
Bosnia and Herzegovina
71000 Sarajevo
T +387 33 714510| Georgia
0179 Tbilisi
T +995 32 306375
Macedonia
1000 Skopje
T +389 2 3122058
Mexico
07300 Mexico
T +52 55 55863209| Moldova
2012 Chisinau
T +373 2 223501
Rep. Mongolia
Ulaanbaatar
T +976 11 314843
Tajikistan
734025 Dushanbe
T +992 37 2232908| Turkmenistan
744000 Ashgabad
T +993 12 345838
Uzbekistan
100015 Tashkent
T +998 71 1206774
---|---|---|---
WILO SE
Nortkirchenstraße 100
44263 Dortmund
Germany
T 0231 4102-0
F 0231 4102-7363
wilo@wilo.com
www.wilo.de
References
- Commercial Distributor & Supply Company | North American
- crisol.ch – Crisol Holding GmbH
- Wilo Corporate - Pioneering for You | Wilo
- Wilo - Premiumanbieter von Pumpen und Pumpensystemen | Wilo
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>