KMC Simply VAV Zoning Controllers Installation Guide
- June 5, 2024
- KMC
Table of Contents
- KMC Simply VAV Zoning Controllers Installation Guide
- Section 1: A bout the controllers
- Section 2: Installing the controllers
- Section 3: Changing the room setpoint
- Section 4: Configuring the controllers
- Section 5: Balancing air flow
- Section 6: Application drawings
- Section 7: Sequences of operation
- Section 8: System integration and networking
- Appendix A : K-factors
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
KMC Simply VAV Zoning Controllers Installation Guide
©2022, KMC Controls, Inc.
NetSensor, WinControl, and the KMC logo are registered trademarks of KMC
Controls, Inc.
AppStat, BACstage, FlexStat, FullBAC, KMC Connect, TotalControl, SimplyVAV,
and the SimplyVAV logo are trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may be reproduced,
transmitted, transcribed, stored in a retrieval system, or translated into any
language in any form by any means without the written permission of KMC
Controls, Inc.
Printed in U.S.A.
The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this manual. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this manual.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
U.S.A.
TEL: 1.574.831.5250
FAX: 1.574.831.5252
info@kmccontrols.com
Section 1: A bout the controllers
This section provides a description of the SimplyVAV series of controllers. It also introduces safety information. Review this material before selecting, installing, or operating the controllers.
The SimplyVAV series of controllers are an easy and unique approach to operating a wide variety of VAV terminal units. The integrated actuators, internal airflow sensors, and wide variety of application programs make these BACnet Application Specific controllers ideal for either new or retrofit installations.
The controllers feature simple, menu-driven setup choices when used with a SimplyVAV digital sensor. No special programming skills or software tools are required to choose applications, enter setpoints, set network addressing, and balance airflow. All options can be set by using only an STE-8001 sensor, which can be installed as the permanent room sensor or temporarily connected as a technician’s service tool.
All models are BACnet Application Specific Controllers that are ready to
connect to a BACnet
MS/TP network. Device instance, MAC address, and baud rate are set from an
STE-8001 sensor without special software.
BAC-8001 Model BAC-8001 is supplied with inputs, outputs, and sequences of operation for the following functions.
- Single duct heating and cooling VAV
- Automatic heating/cooling changeover including morning warmup
- Occupancy setback—requires STE-8201
- System diagnostic indicators
- Airflow balancing
BAC-8005 and BAC-8205 Models BAC-8005 and BAC-8205 are supplied with inputs,
outputs, and sequences of operation for the following functions.
- Single duct heating and cooling VAV
- Modulating, floating, time proportional, and staged reheat
- Series and parallel fan control
- Automatic heating/cooling changeover including morning warmup
- Discharge air temperature limiting
- Occupancy setback—requires STE-8201
- Actuator position feedback for true damper positioning (BAC-8205 only)
- System diagnostic indicators
- Airflow balancing
BAC-8007 Model BAC-8007 is supplied with inputs, outputs, and sequences of
operation for
the following functions.
- Dual-duct VAV heating and cooling
- Occupancy setback—requires STE-8201
- System diagnostic indicators
- Airflow balancing
Additional topics in this section
Specifications 6
Accessories and replacement parts 9
Available models 10
Safety considerations 11
Specifications
SimplyVAV controller specifications are subject to change without notice.
Inputs and outputs
All inputs and outputs are factory programmed and application specific. No
field configuration is required. For details on input and output connections,
see the topic Application drawings on page 39. For a detailed listing of input
and output objects, see the topic BACnet objects on page 65.
Analog inputs
Analog inputs represent BACnet analog input. Not all input are applicable or
required for all models.
- Key features: Standard units of measure.
- Overvoltage input protection
- Connectors: RJ-45 room sensor jack
- Screw terminals for wire sizes 12-26 AWG
- Conversion: 12–bit analog–to–digital conversion
- Input range: Passive, 10 kΩ pull-up to 3.3 volts DC
Analog outputs
Analog outputs are configured to represent BACnet analog output objects. No
field configuration is required. For details on application specific output
connections see the section Application drawings on page 39.
-
Key features: Output short protection
Standard units of measure -
Connector: Screw terminals for wire size 12-26 AWG
-
Conversion: 12–bit digital-to-analog conversion
-
Output voltage: 0–10 VDC
-
Output current: 30 mA per output, 30 mA total for all analog outputs
Binary outputs
Binary outputs are configured to represent BACnet binary output objects. No
field configuration is required. For details on application specific output
connections see the section Application drawings on page 39.
- Key features: Optically isolated triac output
- Connector: Screw terminals for wire size 12-26 AWG
- Output range: Maximum switching 24 Volts AC
1 ampere per external output, 3 amperes total
Communications—BACnet MS/TP
- EIA–485 operating at rates up to 76.8 kilobaud.
- Removable screw terminal block.
- Wire size 12-26 AWG
- Switch selected end of line termination
Memory
- Programs and program parameters are stored in nonvolatile memory.
- Auto restart on power failure
Air flow sensor features
- Configured as BACnet analog input object.
- CMOS differential pressure 0-2 inches of water (0-500 Pa) measurement range. Internally linearized and temperature compensated.
- Span accuracy 4.5% of reading.
- Zero point accuracy 0.0008 in. H2O/0.2 Pa at 25° C
- Barbed connections for 1/4 inch FR tubing.
Actuator specifications
Regulatory
- UL 916 Energy Management Equipment
- BACnet Testing Laboratory listed as an application specific controller (ASC).
- CE compliant
- FCC Class B, Part 15, Subpart B and complies with Canadian ICES-003 Class B This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Installation
- Supply voltage: 24 volts AC, -15%, +20% 5 VA, 50/60 Hz
- Weight: 13.2 ounces (376 grams)
- Case material: Flame retardant plastic
Environmental limits
- Operating: 32 to 120° F (0 to 49° C)
- Shipping: –40 to 140° F (–40 to 60° C)
- Humidity: 5–93% relative humidity (non-condensing)
Dimensions
Accessories and replacement parts
The following accessories and replacement parts are available from KMC
Controls, Inc.
Power transformer
XEE-6111-50 Transformer, 120-to-24 VAC, 50 VA, single-hub
XEE-6112-50 Transformer, 120-to-24 VAC, 50 VA, dual-hub
XEE-6311-100 Transformer, 120, 277 -to-24 VAC, 50/60 Hz, 96 VA, dual-hub
Sensors
STE-8001W80 SimplyVAV sensor and digital display
STE-8201W80 SimplyVAV sensor and digital display with motion sensor
STE-6010W80 Discrete temperature sensor with RJ-45 connector
STE-6014W80 Discrete temperature sensor with rotary setpoint dial, RJ-45
connector
STE-6017W80 Discrete temperature sensor with rotary setpoint dial, override
button, RJ-45 connector
HPO-9005 Room Sensor Adapter
Sensor cables
HSO-9001 Cable: Ethernet, 50 foot
HSO-9011 Cable: Ethernet, 50 foot, Plenum Rated
Surge suppressors
KMD-5567 EIA-485 surge suppressor for MS/TP networks
Replacement parts
HPO-0054 Replacement bulbs
HPO-0063 Replacement two-pin jumper
Dual duct actuator
TSP-8001 VAV actuator with airflow inputs (required for dual duct)
Airflow sensors
For VAV terminal units without airflow pickup tubes, order one of the
following sensors.
SSS-1012 3-5/32 in. length (80 mm)
SSS-1013 5-13/32 in. length (137 mm)
SSS-1014 7-21-32 in. length (195 mm)
SSS-1015 9-29/32 in. length (252 mm)
KIT-8001 A 3-5/32 inch sensor and 3 feet of FR tubing
Available models
The following is a list of SimplyVAV available models.
Safety considerations
KMC Controls assumes the responsibility for providing you a safe product and safety guidelines during its use. Safety means protection to all individuals who install, operate, and service the equipment as well as protection of the equipment itself. To promote safety, we use hazard alert labeling in this manual. Follow the associated guidelines to avoid hazards.
Section 2: Installing the controllers
This section provides important instructions and guidelines for installing the SimplyVAV controllers. Carefully review this information before installing the controller.
Installing SimplyVAV includes the following topics that are covered in this section.
Installation topics in this section
Setting the rotation limits 13
Mounting on a VAV terminal box 14
Connecting an airflow sensor 15
Connecting inputs and outputs 15
Connecting room temperature sensors 15
Connecting a DAT sensor 16
Connecting power 17
Maintenance 18
Setting the rotation limits
SimplyVAV controllers are manufactured for a damper that rotates 90 degrees
from open to
closed. If the VAV damper is not a 90 degree damper, set the rotation limits
to 45 or 60
degrees before mounting the controller.
Caution: Before setting the rotation limits on the controller, refer to the damper position specifications in the VAV control box to which the controller will be attached. Setting rotation limits that do not match the VAV damper may result in improper operation or equipment damage.
Illustration 2–1 Controller rotation limit selections
To set the rotational limits, do the following
- Turn the controller over so you have access to the back.
- Manually rotate the actuator fully clockwise as viewed from the back.
- Remove the stop screw from its storage location and clean any debris from the threads.
- Insert the screw into the correct stop position hole.
- Tighten the screw only until the head touches the plastic in the bottom of the recess.
Mounting on a VAV terminal box
Mount the controller inside of a metal enclosure. To maintain RF emissions
specifications, use either shielded connecting cables or enclose all cables in
conduit. Mount the controller directly over the damper shaft. A minimum shaft
length of 2.0 inch (51 mm) is required.
Note: SimplyVAV controllers are designed to directly mount to 3/8 to 5/8 inch (9.5 to 16 mm) round or 3/8 to 7/16 inch (9.5 to 11 mm) square damper shafts.
Illustration 2–2 Controls and indicators
Mount the controller as follows:
- Manually rotate the damper on the VAV box to the fully open position.
- On the controller, press the gear clutch button and rotate the drive hub in the same direction that opened the damper. Turn the hub until it reaches a rotation limit.
- Loosen the nuts on the V-bolt until the damper shaft can fit through the collar.
- Place the controller over the damper shaft.
- Finger tighten the nuts on the V-bolt to position the shaft in the drive hub.
- Center the mounting bushing in the mounting tab and fasten it with a #8 sheet metal screw.
- Evenly tighten the V-bolt nuts on the drive hub to 30-35 in-lbs.
Connecting an airflow sensor
An airflow sensor is incorporated as one of the inputs to the controller.
Remove the plugs and connect the tubing from the pitot assembly to the airflow
sensor inputs next to the drive hub.
Illustration 2–3 Airflow sensor inputs
Typically, airflow sensors are supplied by the manufacturer as part of the VAV terminal unit. If a sensor is needed, choose a sensor listed in the topic Accessories and replacement parts on page 9.
Connecting inputs and outputs
SimplyVAV series controllers have preconfigured inputs and outputs to support
only the
supplied programs and applications.
-
For input and output connection information, see the topic Application drawings on page 39.
-
To connect room temperature sensors, see the topic Connecting room
temperature sensors on page 15 -
To connect a DAT sensor, see the topic Connecting a DAT sensor on page 16.
-
For the BACnet object descriptions of the inputs and outputs, see the topic BACnet objects on page 65.
Connecting room temperature sensors
Connect any of the following sensors to the RJ-45 thermostat and sensor jack.
The controller automatically detects the type of sensor. No programming or
configuration is required.
l STE-6010W80
l STE-6014W80
l STE-6017W80
l STE-8001W80
l STE-8201W80
Connect the controller to sensors with standard Ethernet cables up to 75 feet
long. See the
installation guide supplied with the sensors for sensor installation
instructions.
Illustration 2–4 Connecting to a sensor
Connecting a DAT sensor
The Discharge Air Temperature sensor is required for automatic changeover and
for VAV terminal units with reheat.
Illustration 2–5 Discharge air temperature sensor location
Connect a 10 kΩ, Type 3 thermistor temperature probe to the discharge air temperature input. The input includes the internal pull-up resistor. An STE-1401 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
- For DAT limiting and reheat, install the sensor in the airflow after the reheat unit. See the topic Advanced options on page 31 to enable discharge air temperature control.
- When the DAT sensor is used only to detect primary air temperature, the sensor can be placed in either location shown in the illustration Discharge air temperature sensor location.
Illustration 2–6 Discharge air temperature input details
Connecting power
The controllers require a 24 volt, AC power source. Use the following
guidelines when choosing and wiring transformers to the controller.
- Use a Class–2 transformer of the appropriate size to supply power to the controller.
- KMC Controls recommends powering only one controller from each transformer.
- Do not run 24 volt, AC power from within an enclosure to external controllers.
Connect the 24 volt AC power supply to the power terminal block on the lower right side of the controller. Connect the ground side of the transformer to the ground terminal and the AC phase to the phase terminal. Power is applied to the controller when the transformer is connected to power.
Illustration 2–7 Controller power terminals
Maintenance
SimplyVAV controllers require no routine maintenance. If necessary, clean with
a damp cloth and mild soap.
Section 3: Changing the room setpoint
This section covers topics for the end user in a facility.
Changing the SimplyVAV user functions with an STE-8001 or STE-8201 are limited to changing the active setpoints in a room. The setpoints are entered or changed using the buttons and display on the front of the sensor.
To enter or change the active setpoints, you may need Password 1.
Tip: Once the following procedure is started, all steps must be completed
in order.
Changing room setpoints
Section 4: Configuring the controllers
This topics in this section are advanced topics for control technicians and engineers.
The configuration functions that are accessible through an STE-8000 series digital sensor are all of the values and settings that are entered during the installation and commissioning of a VAV terminal unit. Typically, these functions do not change after the installation and commissioning process.
To set up the configuration functions, you will need the following items and information.
- Details about the VAV terminal unit including the configuration for fans and reheat.
- An STE-8001 or STE-8201 digital sensor to use as a configuration tool.
- The building automation system plans for controllers connected to a network.
Users may change the active heating and cooling setpoints without accessing the configuration functions. This procedure is covered in the topic Changing the room setpoint on page 19.
Note: The instructions for the configuration functions cover all of the functions that a digital sensor can set up in the SimplyVAV series of controllers. Not all functions are available on every model of controller.
Getting started with configuration
For access to the configuration functions you will need the Password 2.
- If the controller has not been previously set up, no password is required.
- A new Password 2 can be entered or changed in the advance functions. See the topic Advanced options on page 31.
Enter the configuration mode
Entering system temperature setpoints and limits
The system temperature setpoints set the operational parameters and limits for
the VAV
terminal unit.
The temperature setpoints include the following items.
- Minimum cooling and maximum heating setpoints
- Occupied and unoccupied cooling setpoints
- Occupied and unoccupied heating setpoints
- Changeover differential setpoint
- Standby differential setpoint
Setting the temperature setpoints requires entering Password 2, which is described in detail in the topic Getting started with configuration on page 22.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure to set the temperature setpoints
Configuring the VAV Box options
The box options set the controller for the specific mechanical installation of
the VAV
terminal unit. The box options include the following items.
- The K-factor for the VAV terminal unit. If the K-factor is not available, see the topic K-factors on page 69.
- Reheat configuration (optional)
- Fan configuration (optional)
- Direction of damper to close
Setting the box options requires entering Password 2, which is described in the topic Getting started with configuration on page 22.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure to set the box functions
Set the airflow setpoints
The airflow setpoints set the airflow limits for the VAV terminal unit.
- Airflow heating and cooling minimum and maximum limits
- Auxiliary flow setpoint (optional)
- Minimum and maximum fan speeds (optional)
Setting the airflow setpoints requires entering Password 2 which is described in the topic Getting started with configuration on page 22.
Note: All CFM settings must be entered. For cool/heat only units, set unused mode CFM values within the range of the used mode; for example, cooling min/max 250/800, heating min/max 250/450, aux flow 350. No CFM setpoint can be set to 0. Failure to set the unused setpoints correctly will result in unpredictable or erroneous behavior.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure to set the airflow setpoints
Advanced options
The advanced options set up passwords and special features in the controller.
- Establish or change Password 1 and Password 2
- Set timers for standby and override (optional)
- Enable automatic occupancy (optional)
- Enable discharge air temperature control (optional)
- Calibrate the sensor
Setting the advance options requires entering Password 2, which is described in the topic Getting started with configuration on page 22.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure to set the advanced options
Restore Application
Choose the RSTR function to reset the SimplyVAV controller to the original
configuration and settings. Use it also to change the units of measure to
display on a SimplyVAV sensor. There are two versions of the application
program in the controller.
- The Metric version displays temperature in Celsius and uses metric values for units of measure.
- The English version displays temperature in Fahrenheit and uses English values for units of measure.
Access to the Restore Application function requires entering Password 2, which is described in the topic Getting started with configuration on page 22.
Tip: Once the following procedure is started, all steps must be completed in order.
Caution: Choosing RSTR deletes all previously configured values including balancing values and passwords. Only the BACnet communications settings will remain unchanged.
Procedure to restore application
Section 5: Balancing air flow
Topics in this section are for control technicians or engineers who will be balancing the airflow in the controllers.
The airflow balancing procedure described in this section requires the following items.
- A flow hood or other accurate method to measure airflow.
- An STE-8001 or STE-8201 wall sensor. If the system does not include one of these sensors, temporarily disconnect the installed sensor and connect an STE-8001 as a service tool.
- The engineering design specifications for the minimum and maximum airflow setpoints.
- Password 2, which is described in the topic Getting started with configuration on page 22.
Note: If the VAV unit is a heat only or cooling only unit, the airflow setpoints for the unused mode must be set within the range of the mode in use. Failure to set the unused setpoints correctly will result in unpredictable or erroneous air balancing settings. See Set the airflow setpoints on page 28 for the procedure to adjust the setpoints.
Note: Starting the balancing procedure erases all previous airflow correction factors. The airflow readings displayed by the digital sensor are the actual uncorrected airflow readings as measured by the controller.
Tip: Once the following procedure is started, all steps must be completed in order.
The airflow balancing procedure
Section 6: Application drawings
This section covers the drawings, materials, and instructions for specific VAV applications.
Each SimplyVAV model is designed for a specific set of applications. The following topics are for control technicians and engineers who will plan for and install controllers for SimplyVAV applications.
Submittal sheets for all of these applications are available from the BAC-8000
series page at
KMCControls.com.
Cooling or heating without reheat
The BAC-8001 is configured for single-duct cooling VAV control without reheat.
A BAC-8005
or BAC-8205 may also be used for this application. Connect the controller as
shown in the
illustration Cooling or heating application drawing on page 40.
For cooling and heating, a duct temperature sensor is required for Discharge Air Temperature limiting and automatic changeover. See the topic Advanced options on page 31 for instructions to enable Discharge Air Temperature limiting.
Submittal sheets for several variations of this application are available from the BAC-8000 series page at KMCControls.com.
Illustration 6–1 Cooling or heating application drawing
Fan powered VAV terminal with staged reheat
The staged reheat application is for BAC-8005 or BAC-8205 controllers. Series
or parallel fan
power is optional. The controllers are configured to switch reheat units that
are controlled
with 24 volts AC. Reheat units with up to three stages of reheat can be
controlled by these
controllers.
-
For one-stage, electric reheat or hot water reheat with an on/off valve, use only output
terminal BO6. -
For two-stage reheat, use output terminals BO6 and BO7.
-
For three-stage reheat, use output terminals BO6, BO7, and BO8.
For cooling and heating, a duct temperature sensor is required for Discharge Air Temperature limiting and automatic changeover. See the topic Advanced options on page 31 for instructions to enable Discharge Air Temperature limiting.
When connecting the controller to a fan powered VAV unit, the fan circuits
must be
compatible with the following specifications.
- The fan start circuit is a 24 volt AC pilot duty output.
- The fan speed output is 0-10 volts DC.
Submittal sheets for several variations of this application are available from the BAC-8000 series page at KMCControls.com.
Illustration 6–2 Fan powered VAV terminal with three-stage reheat
Fan powered VAV terminal with modulating reheat
The modulating reheat application is for a BAC-8005 or BAC-8205 controller.
Series or parallel fan powered operation is optional. The modulating option
for reheat can control either an electric reheat unit with an analog input or
a modulating hot water valve. The analog reheat output at output terminal AO3
varies between 0 and 10 volts DC.
For cooling and heating, a duct temperature sensor is required for Discharge Air Temperature limiting and automatic changeover. See the topic Advanced options on page 31 for instructions to enable Discharge Air Temperature limiting.
When connecting the controller to a fan powered VAV unit, the fan circuits must be compatible with the following specifications.
- The fan start circuit is a 24 volt AC pilot duty output.
- The fan speed output is 0-10 volts DC.
Submittal sheets for several variations of this application are available from the BAC-8000 series page at KMCControls.com.
Illustration 6–3 Fan powered VAV terminal with modulating reheat
Fan powered VAV terminal with time proportional reheat
The time proportional reheat application is for BAC-8005 or BAC-8205
controllers. Series or parallel fan power is optional. This application is
typically used in hydronic systems with a hot water reheat coil and a wax top
control valve. The reheat output is a triac that can switch up to 1 ampere at
24 volts AC.
For cooling and heating, a duct temperature sensor is required for Discharge Air Temperature limiting and automatic changeover. See the topic Advanced options on page 31 for instructions to enable Discharge Air Temperature limiting.
When connecting the controller to a fan powered VAV unit, the fan circuits must be compatible with the following specifications.
- The fan start circuit is a 24 volt AC pilot duty output.
- The fan speed output is 0-10 volts DC.
Submittal sheets for several variations of this application are available from the BAC-8000 series page at KMCControls.com.
Illustration 6–4 Fan powered VAV terminal with time proportional reheat
Fan powered VAV terminal with floating reheat
The floating reheat application is for BAC-8005 or BAC-8205 controllers.
Series or parallel
fan power is optional. Use this application in hydronic systems that are
controlled by an
actuator with tri-state inputs. The reheat outputs are triacs that can switch
up to 1 ampere
at 24 volts AC.
For cooling and heating, a duct temperature sensor is required for Discharge Air Temperature limiting and automatic changeover. See the topic Advanced options on page 31 for instructions to enable Discharge Air Temperature limiting.
When connecting the controller to a fan powered VAV unit, the fan circuits must be compatible with the following specifications.
- The fan start circuit is a 24 volt AC pilot duty output.
- The fan speed output is 0-10 volts DC.
Submittal sheets for several variations of this application are available from the BAC-8000 series page at KMCControls.com.
Illustration 6–5 Fan powered VAV terminal with floating reheat
Dual-duct application
The dual-duct application is for a BAC-8007 controller. Dual-duct VAV requires
a TSP-8001 actuator to be used with the BC-8007 as shown in the illustration
Dual-duct wiring diagram on page 45.
Submittal sheets for several variations of this application are available from the BAC-8000 series page at KMCControls.com.
Illustration 6–6 Dual-duct wiring diagram
Section 7: Sequences of operation
Topics in this section cover the sequences of operation for the SimplyVAV
controllers.
These are advanced topics for control technicians and engineers.
These sequences of operation are descriptions of each major component of the SimplyVAV programming. They are provided as an aid to understanding on how the controllers operate.
Input sources
The SimplyVAV controllers require specific sensors to measure room
temperature, airflow, and discharge air temperature. All sensors are
automatically detected and the programming is automatically set up for the
sensors.
- SimplyVAV digital wall sensors
- STE-6000 series discreet temperature sensors
- Discharge air temperature sensor
- Airflow sensors and pickups
SimplyVAV digital wall sensors—The SimplyVAV digital wall sensors include a room temperature sensor, a digital display, and a push button interface for entering setpoints and configuring the controllers. If a SimplyVAV digital wall sensor is detected, the sensor’s temperature is mapped to the Space Temperature Reference value object as the temperature input value. See the topic BACnet objects on page 65 for additional information on value objects.
The SimplyVAV digital wall sensor model BAC-8201 includes also a motion sensor to detect when the zone is temporary unoccupied. This is described in the topic Occupancy sequence on page 48.
STE-6000 series discreet temperature sensors—There are three models of the STE-6000 series sensors compatible with the SimplyVAV controllers. If one of the three sensors is detected, the sensor’s temperature is mapped to the Space Temperature Reference value object as the temperature input value. See the topic BACnet objects on page 65 for additional information on value objects.
Models STE-6014 and STE-6017 also include a dial for adjusting the setpoint . If either of these two sensors is detected, the dial position sets the Active setpoint a few degrees above or below the Occupied setpoint.
The STE-6017 includes a button that when pushed will override the unoccupied state. This is described in the topic Occupancy sequence on page 48.
Discharge air temperature sensor—The DAT sensor is an optional Type-III, 10 kΩ thermistor and is required for VAV heating applications. If the controller detects that this sensor is connected, then the controller will use discharge air temperature to determine when to change between heating and cooling. The DAT sensor input is used also to control reheat. See the topics Discharge Air Temperature (DAT) limiting on page 51 and Changeover on page 51.
Airflow sensors and pickups—VAV airflow is calculated by measuring the high and low duct pressures with the built-in airflow sensor which is connected to airflow pickup tubes. The high and low pressure measurements along with the K-factor of the VAV terminal unit are used to calculate the airflow through the VAV unit.
Occupancy sequence
A SimplyVAV controller is designed to operate as a stand-alone controller and
determine occupancy based only on the availability of primary airflow and
motion in the zone. The controller can be in any one of the following
occupancy states.
- Occupied on page 48
- Unoccupied
- Standby
Occupancy can also be commanded by another BACnet device or an operator workstation connected the building automation network. See the topic System integration and networking on page 61 for details.
Automatic occupancy
If Automatic Occupancy is enabled, the controller will automatically toggle
between Unoccupied, Occupied, and Standby based on the presence of primary
airflow and motion in the zone.
The default for Automatic Occupancy is Disabled. See the topic Advanced options on page 31 to change Automatic Occupancy.
Occupied
For controllers without a connected motion sensor, the controller changes to
Occupied upon the detection of primary airflow.
Controllers with a connected motion sensor change to Occupied upon the detection of primary airflow and motion in the space. The unit will remain in the OCCUPIED state as long as periodic motion is detected and primary airflow continues. If motion stops, the controller changes to STANDBY.
Unoccupied
The controller Occupancy mode changes to UNOCCUPIED when it detects a loss of
primary airflow. While in the UNOCCUPIED state, the controller will fully open
the damper in an attempt to reach the maximum airflow setpoint.
Loss of primary airflow is defined as less than 25% of the requested flow for at least 5 minutes. The Occupancy mode changes to Occupied or Standby once the actual airflow is at least 30% of the requested flow.
Standby
In units with a connected motion sensor, the controller starts in STANDBY and
changes to OCCUPIED after detecting motion in the space. Motion in the space
is defined as two movements detected within 5 minutes. The controller will
change back to STANDBY after a lack a lack of motion for the period specified
by the variable Standby Time.
Standby mode is not valid for controllers without a motion sensor, unless commanded by a building management system.
Space setpoints
There are four temperature setpoints each for heating and cooling for a total
of eight setpoints.
- Active cooling
- Occupied cooling
- Unoccupied cooling
- Standby cooling
- Active heating
- Occupied heating
- Unoccupied heating
- Standby heating
Types of setpoints
The SimplyVAV controllers may use any of the following setpoints based on a
user entered setpoint or the state of occupancy and standby which is described
in the topic Occupancy sequence on page 48.
Active setpoint —The active setpoint is the current setpoint. The active setpoint is determined by the following.
-
If the space is occupied, the controller uses the occupied setpoint as the active setpoint.
-
If an STE-6014 and STE-6017 is connected, the Active setpoint is set by the dial to be a
few degrees above or below the Occupied setpoint. The range of adjustment is set by
the variable STBY OFFSET. The dial setting does not change the setpoint when in the Unoccupied or Standby state. -
If the space is unoccupied the controller uses the unoccupied setpoint as the active setpoint.
-
If controller is in standby, the controller calculates the standby setpoint.
-
A user with Password 1 can enter an active setpoint from a SimplyVAV digital wall sensor. This entry will change the occupied setpoint within the setpoint limits.
Occupied setpoint —A temperature setpoint entered by the controls technician during controller setup and system commissioning. This is the setpoint used when the controller is occupied which is determined by primary airflow and, on controllers equipped with motion sensors, motion in the zone.
Unoccupied setpoint —A temperature setpoint entered by the controls
technician during
controller setup and system commissioning. This is the setpoint used when the
system is unoccupied .
Standby setpoint —The standby setpoint is used when the controller is in the standby state. It is a value calculated from the occupied setpoint and the variable STBY OFFSET. The standby offset value is entered by the controls technician during controller setup and system commissioning. See the topic Occupancy sequence on page 48.
Setpoint limits
The programming in the controller limits the setpoint entry so that no heating
setpoint is set
higher than its corresponding cooling setpoint.
If a user is adjusting a setpoint and it falls within the range set by the
value of Minimum
Setpoint Differential, the corresponding setpoint will be changed to maintain
the differential.
For example, the Minimum Setpoint Differential is 4° F and the Occupied
Heating setpoint is
70° F. If the user lowers the Occupied Cooling setpoint to 71° F, the
controller recalculates
the Occupied Heating setpoint and changes it to 67° F.
PID control loops
A PID control loop calculates an error value from the difference between the
measured room
temperature and the active setpoint. The error value is expressed as a
percentage and is typically used in a BAS controller to control the state of
an output. When the difference between the setpoint and room temperature is
large, the error is large. As the system reduces the difference between the
setpoint and space temperature, the error becomes smaller.
The SimplyVAV controllers use up to three PID loops.
- The heating PID loop.
- The cooling PID loop.
- The discharge air temperature (DAT) loop.
For SimplyVAV controllers, the output of either the cooling and heating PID
loop is used to
calculate the position of the damper. If present, the DAT input and DAT loop
controls the
Reheat loop.
The PID loops in the SimplyVAV controllers are standard BACnet objects and are
described
in the topic BACnet objects on page 65.
Airflow setpoints sequence
Airflow Setpoint is calculated based on the demand for cooling or heating
depending on
whether the Cooling loop or Heating loop is greater than zero.
If no room sensor is connected to the controller, the controller uses the
Minimum Cooling
Airflow setpoint to maintain airflow.
Cool Air Sequence As the Cooling loop increases from 0% to 100%, Primary
Airflow
Setpoint is proportionally calculated between Minimum Cooling Airflow and
Maximum
Cooling Airflow.
If there is a call for reheat to maintain room temperature, the primary
airflow is set to the
value of Auxiliary Flow.
Warm Air Available In the heating mode, as the Heating Loop increases from 0%
to 100%,
Primary Airflow Setpoint is proportionally calculated between Minimum Heating
Airflow and
Maximum Heating Airflow.
See also the topics, Changeover on page 51 and Input sources on page 47.
Changeover
The Discharge Air Temperature input is used by the controller to determine the
type of air that is being supplied by the AHU. The sensor is required for
applications that require automatic change over between cooling and heating.
When the Heating loop is inactive, the Discharge Air Temperature input is compared to the SAT Changeover Temp. If the Discharge Air Temperature is below the SAT Changeover Temp minus 2°, the SAT Changeover Mode is set to COOL. If the Discharge Air Temperature is above the SAT Changeover Temp plus 2° Fahrenheit, the SAT Changeover Mode is set to HEAT. The default changeover temperature is 74° Fahrenheit.
See the topic Discharge Air Temperature (DAT) limiting on page 51 and Input sources on page 47.
Discharge Air Temperature (DAT) limiting
A Discharge Air Temperature senor and DAT limiting is required to control VAV
units with
reheat. If a Discharge Air Temperature (DAT) sensor is detected and DAT
Limiting is enabled, the VAV terminal will be controlled by the DAT loop. The
unit will also limit the Discharge Air Temperature to within 15° F of the
Space Temp Reference.
When there is a call for heat and the primary air is cool air, the reheat
outputs are directly controlled by the DAT Loop and the DAT Setpoint reset
based on the output of the Heating
loop. As the Heating loop increases from 0% to 50%, DAT Setpoint is
proportionally calculated between Space Temp Reference and Space Temp
Reference + 15° F up to maximum 90° F. This allows the reheat to be controlled
by the DAT loop over the first 50% of
a call for heating.
Illustration 7–1 DAT limiting operation
If DAT Limiting is enabled, and a DAT sensor is not connected, the controller will lockout reheat control only in the cooling mode. The unit will operate this way until a DAT sensor is detected or until the unit is commanded to control to the Active Heating Setpoint by a supervisory BMS.
If the unit has detected a DAT sensor and DAT Limiting is not enabled, the unit’s reheat is controlled by the Heating loop instead of the DAT loop.
See also the topics Changeover on page 51 and Input sources on page 47.
System diagnostic indicators
The controller programming includes four system diagnostic indicators in the
form of
BACnet value objects.
- NEED AHU (BV1)
- NEED COLDER SUPPLY (BV2)
- NEED MORE STATIC (BV3)
- NEED HOTTER SUPPLY (BV7)
These diagnostic indicators or flags are monitored by other BACnet devices, such as air handling units, connected to the same building automation system as the controller. How the indicators are used is beyond the scope of these instructions.
NEED AHU (BV1)
The Need AHU Start value object is set to TRUE (1) for any of the following
conditions.
- The system mode is UNOCCUPIED and the Cooling loop or the Heating loop is greater than 100% for longer than 10 minutes.
- The system mode is OCCUPIED or STANDBY.
- Either of the Motion Override or Local Override variable objects are TRUE (1).
The Need for AHU Start object changes to FALSE (0) when both loops drop below 5% and the system mod is not OCCUPIED or STANDBY and both override variable objects are FALSE (0).
NEED COLDER SUPPLY (BV2)
The Need Colder Supply value object is set to TRUE (1) when the system mode is
STANDBY or OCCUPIED and the Cooling loop is greater than 95% for 30 minutes.
The indicator changes to FALSE (0) when the Cooling loop falls below 90% or
when the system mode is UNOCCUPIED.
NEED MORE STATIC (BV3)
The Need More Static value object is set to TRUE (1) when the controller has
attempted to drive the damper fully open for longer than 2 minutes 30 seconds
and any of the following are TRUE (1).
- The system mode is OCCUPIED or STANDBY.
- Either of the Motion Override or Local Override variable objects are TRUE (1).
When any of these conditions are no longer true, the indicator changes to FALSE (0).
NEED HOTTER SUPPLY (BV7)
The Need Warmer Supply value object is set to TRUE (1) when the system mode is
STANDBY or OCCUPIED and the Heating loop is greater than 95% for 30 minutes.
The indicator changes to FALSE (0) when the Heating loop falls below 90% or
when the system mode is no longer OCCUPIED.
Damper operation
Damper movement is determined by comparing the actual airflow reading to the
airflow setpoints. If the actual airflow is within 5% of the setpoint, no
damper action is initiated. Once within the 5% deadband, the actual airflow
must be outside a 7% deadband before damper position changes.
To improve stability near setpoint, the damper motor is pulsed when the actual flow rate is within 15% of the requested flow rate. The pulse rate is 5 seconds and the duty cycle is controlled by analog variable MOTOR PAUSE. In addition, the motor will pause for 10 seconds before the damper changes direction.
Fan operation
The SimplyVAV controllers support both series and parallel fan powered VAV
units. For either type of fan operation, the fan is controlled through the
following terminals.
- A binary output triac controls a 24-volt fan starting circuit. See the topic Configuring the VAV Box options on page 26 for the procedure to configure the controller for a fan.
- A 0-10 volt DC analog output controls the speed of the fan. The output controls fan speed at either Min Fan Speed or Max Fan Speed. See the topic Set the airflow setpoints on page 28 for the procedure to set the fan speeds.
If the VAV unit is not configured for a fan, the two outputs are not used and
remain inactive
regardless of the occupancy state.
Series Fan
If the controller is configured for a series fan, any time the Occupancy mode
of the controller
is set to either OCCUPIED or STANDBY, the fan runs continuously. The fan speed
is set to Maximum Fan Speed when the state is OCCUPIED and set to Minimum Fan
Speed when the state is STANDBY.
When the Occupancy state is UNOCCUPIED, the fan starts and runs at minimum speed only on a call for heating. The fan starts when the Heating loop is greater than 5% and stops when the Heating loop is less than 1%.
Illustration 7–2 Series fan operation
Parallel Fan
If the controller is configured for a parallel fan, any time the Occupancy
mode of the controller is set to either OCCUPIED or STANDBY and there is a
call for heat, the fan runs continuously. The fan starts when the Heating loop
is greater than 5% and stops when the Heating loop is less than 1%.
When the unit Occupancy state is UNOCCUPIED, the fan starts and runs at minimum speed only on a call for heating. The fan starts when the Heating loop is greater than 5% and stops when the Heating loop is less than 1%.
Illustration 7–3 Parallel fan operation
Reheat sequence
The SimplyVAV controllers can control four types of reheat installations.
- Modulating reheat
- Staged reheat
- Time proportioned reheat
- Floating reheat
All reheat is controlled by either the Heating loop or the Discharge Air Temp
Limiting (DAT)
PID loop. Loops are described in the topic PID control loops on page 50.
- If Discharge Air Temp Limiting is enabled, reheat is controlled by the DAT PID loop.
- If DAT control is not enabled, reheat is controlled by the Heating loop.
In the following descriptions, the loop controlling reheat is referred to as the Reheat loop.
Modulating reheat
If the controller is configured for modulating reheat, it controls an analog
reheat unit with 0- 10 volts DC at the analog reheat output. On a call for
reheat, the reheat output is modulated over the span of the Reheat loop. If
the Reheat loop is less than 10%, the reheat output remains at zero. The
reheat is set to zero if the Cooling loop is active.
See the topic Fan powered VAV terminal with modulating reheat on page 42 for an application drawing.
Illustration 7–4 Modulating reheat operation
Staged reheat
If the controller is configured for staged reheat, it can control up to three
stages of reheat through binary triac outputs. The reheat outputs are
commanded On when the Reheat loop
rises above the ON threshold and OFF when the loop drops below the OFF
threshold. Thresholds are described in the following chart, Staged reheat
thresholds on page 56.
See the topic Fan powered VAV terminal with staged reheat on page 41 for an application drawing.
Table 7–1 Staged reheat thresholds
Time proportioned reheat
For controllers configured for time proportional reheat, the duty cycle of a
binary triac output
varies over a 10 second period. For example, if the Reheat loop is at 50%, the
reheat output is ON for 5 seconds and OFF for 5 seconds. If the Reheat loop is
less than 10%, the reheat output remains at zero.
See the topic Fan powered VAV terminal with time proportional reheat on page 43 for an application drawing.
Illustration 7–5 Time proportional reheat operation
Floating reheat
If the controller is configured for floating reheat, it controls two binary
triac outputs to drive the inputs of a tri-state actuator connected to a
valve. If the Reheat loop is less than 30%, the valve is driven closed. If the
loop is greater than 70%, the valve is driven open. If the loop is in between
30% and 70%, no valve action is taken.
See the topic Fan powered VAV terminal with floating reheat on page 44 for an application drawing.
Illustration 7–6 Floating reheat operation
Balancing airflow sequence
Balancing airflow is the process of calibrating the internal airflow sensor to
a known standard. In the field, airflow is measured with an airflow hood or
other measuring instrument and then compared to the airflow measurements from
the sensor in the controller. The balancing process requires an STE-8001 or
STE-8201 digital sensor as the technicians setup tool for initiating the
balancing sequence and entering actual flow measurements.
When the balancing sequence starts, all other functions of the controller are locked out. At the start of the sequence, the controller drives the damper open until the airflow reaches the highest value of either the cooling or heating maximum airflow setpoints. An airflow measurement is made with an airflow hood and the actual airflow value is entered into the controller. Once the actual airflow is entered, the controller drives the damper closed to the lower value of either the cooling or heating minimum airflow. Another measurement is made with the flow hood and that measurement is entered into the controller.
After the minimum airflow measurement is entered, the programming in the controller calculates airflow correction factors which are used to adjust measurements from the internal airflow sensor. Balancing is complete and the controller is returned to normal operation.
See the topic Balancing airflow on page 35 for the procedure to balance the airflow with a digital sensor.
Dual duct
A dual duct installation consists of separate primary heating and cooling
ducts, both with control dampers and airflow monitoring. For this type of
installation a SimplyVAV BAC-8007 controls the cooling air (primary) damper
and a TSP-8001 actuator controls the heating air (secondary) damper.
- As the space temperature rises above the cooling setpoint, the primary airflow is modulated from the Cooling Minimum flow to the Cooling Maximum Flow.
- As the space temperature falls below the heating setpoint, the secondary airflow is modulated from the Heating Minimum flow to the Heating Maximum Flow.
- Between the heating and cooling setpoints, both the primary airflow and secondary airflow are modulated to maintain the Dual Duct Minimum airflow.
See the topic, Dual-duct application on page 45 for an application drawing.
Illustration 7–7 Dual duct sequence
Section 8: System integration and networking
Topics in this section cover integrating the controllers into a building automation network. These are advanced reference topics for control technicians and engineers.
The controllers can be installed as standalone controllers or they can be connected to a BACnet MS/TP network. The topics in this section are reference material for control technicians or engineers who are planning, installing, and setting up controllers that are connected to a network.
In addition to the information in this section, you will also need the following information.
- Detailed plans and drawings for the building automation system.
- Information about the facility LAN including routers, switches, and network firewalls.
- Sequences of operation for other BACnet devices that will monitor or interact with
SimplyVAV controllers.
Connecting to an MS/TP network
SimplyVAV controllers are BACnet MS/TP compliant controllers. Connect them
only to a
BACnet MS/TP network.
To enter the BACnet device instance, MAC address, and network baud, see the
topic Setting
up network communications on page 63.
Illustration 8–1 MS/TP network wiring and EOL switches
Connections and wiring
Use the following principles when connecting a controller to an MS/TP network:
- Connect no more than 128 addressable BACnet devices to one MS/TP network. The devices can be any mix of controllers or routers.
- For best network performance, limit the MS/TP network size to 32 controllers.
- Use twisted pair, shielded cable with capacitance of no more than 51 picofarads per foot for all network wiring. See Technical Bulletin TB190529B, EIA-485 Network Wire Recommendations available from the BAC-8000 series page at KMCControls.com.
- Connect the -A terminal in parallel with all other – terminals.
- Connect the +B terminal in parallel with all other + terminals.
- Connect the shields of the cable together at each mid line controller. For SimplyVAV controllers use the S terminal.
- Connect the shield to an earth ground at one end only.
- Use a KMD–5575 repeater if the cable length will exceed 4000 feet (1220 meters). Use no more than four repeaters per MS/TP network.
- Place a KMD–5567 surge suppressor in the cable where it exits a building.
End of line termination switches
The controllers on the physical ends of the EIA-485 wiring segment must have
end of line termination added for proper network operation.
- For controllers at the end of the network set the EOL switches to On
- For mid line controllers at the end of the network set the EOL switches to Off
Network bulbs
SimplyVAV controllers include network bulbs located near the MS/TP network
connector.
These bulbs serve three functions:
- Removing both bulbs will disconnect the controller from the MS/TP network.
- If one or both bulbs are lit, it indicates the network connection or controller power is not properly wired.
- If the voltage or current on the network exceeds safe levels, the bulbs may open and protect the controller from damage.
Bulbs are illuminated If one or both bulbs are illuminated, it indicates the network is not phased correctly. The ground potential of the controller is not the same as other controllers on the network. The brighter the isolation bulbs on a controller are illuminated, the closer that controller is to the source of the problem. Remove power and check the network and power connections.
Bulbs are open If one or both bulbs are open—as tested with an ohm meter—it indicates the voltage or current on the network exceeded safe levels. Correct the conditions and replace the bulbs.
Bulbs not inserted correctly One lead from one or both of the bulbs are not inserted into the socket.
Setting up network communications
Set the network communication settings before placing a controller on the
network. Setting network settings requires entering Password 2 which is
described in the topic Getting started with configuration on page 22.
Procedure to set up network communications
BACnet objects
The SimplyVAV controllers are BACnet Application Specific Controller (ASC)
that are composed of standard BACnet objects. This section lists the objects
that are likely to be monitored by a standard BACnet operator workstation to
verify system operation.
Caution: Changing the configuration of any object may result in unpredictable operation of a controller and damage to equipment that is under control of a SimplyVAV controller.
Input objects
The following BACnet input objects represent values at the physical inputs of
the controller.
For wiring details, see the topic Application drawings on page 39.
Table 8–1 Input objects
Output objects
The following BACnet output objects represent values at the physical outputs
of the controller. For application specific output wiring details, see the
topic Application drawings on page 39.
Table 8–2 Output objects
Value objects
BACnet value objects represent setpoints or other operational conditions in
the controller.
Note: Not all objects are present in every model.
Table 8–3 Analog value objects
Table 8–4 Binary value objects
Table 8–5 Multistate value objects
Loop objects
BACnet PID loops are used for modulating the damper and controlling reheat.
Table 8–6 PID control loop objects
Appendix A : K-factors
To set up a VAV controller, a K-factor must be entered into the controller. Typically, this is part of the airflow chart that the manufacturer places on the VAV unit.
Note: The data supplied by the manufacturer of the VAV box is the best source for a K-factor. If this information is missing or not available from the manufacturer, use a K-factor from the following chart.
Table A–1 Start point K-factors
Read More About This Manual & Download PDF:
References
- KMC Controls | Building Automation and Control Solutions
- KMC Controls | Building Automation and Control Solutions
- SimplyVAV | KMC Controls
- SimplyVAV | KMC Controls