KMC SSS-1013 Differential Pressure Flow Pickup Tubes Installation Guide

June 5, 2024
KMC

**KMC SSS-1013 Differential Pressure Flow Pickup Tubes Installation Guide

**

Installation Guide

NOTE: This installation guide is for installing SSS-10xx models. For guidance in installing SSS-111x models, see the KMC Conquest Airflow Measurement System Installation Guide.

Mounting for Differential Pressure Flow

To mount the pickup tubes for differential pressure:

  1. Determine the duct’s flow direction and install the pickup tubes based on the flow arrow imprint.
    Mounting for Differential Pressure Flow
    NOTE: The pickup tubes must be mounted with the FLOW arrow imprint pointing in the direction of the air flow.

  2. Cut a 7/8″ (22 mm) hole in the duct to accept the pickup tubes.
    Mounting for Differential Pressure Flow

  3. Attach the pickup tubes to the duct using two selftapping screws inserted through the 3/16″ (5 mm) mounting holes.
    Mounting for Differential Pressure Flow

Connections

Use appropriately sized polyethylene tubing to connect the pickup tubes to the controller:

  •  For connecting SSS-10xx pickup tubes with CSC-3000 series, CSP-4000/5000 series, KMD-7000 series, and BAC-7000/8000/9000 series controllers, use a barb union adapter and tubing sized appropriately to the pickup tubes and controller. For  aximum accuracy in the CSP-5000 series, KMD-7000 series, and BAC-7000 series controllers, the 3/8″ OD tubing between the pickup tubes and the adapter should be as short as possible, and the 1/4″ OD tubing from the adapter to the controller should be 24″ long (on both the High and the Low sides).
  • OR use the equivalent SSS-101x pickup tubes and just 1/4″ OD tubing (no adapter is necessary). For maximum accuracy in the CSP-5000 series, KMD-7000 series, and BAC-7000 series controllers, the 1/4″ OD tubing from the pickup tubes to the controller should be 24″ long (on both the High and the Low sides).
    NOTE: For other controllers, the length of the tubing should not be longer than necessary.
    NOTE: CSC-2000 series controllers have ports for 3/8″ tubing (the same as the SSS-10xx pickup tubes).

Check that there are no sharp bends in the tubing at any connection. Bends and creases may leak as tubing ages.

  1. Connect the Port “H” to the “High” input on the VAV controller.
  2. Connect the Port “L” to the “Low” input on the VAV controller.
Mounting for Static Pressure

To mount the pickup tubes for static pressure:

  1. Determine the duct’s flow direction and install the pickup tubes so that the FLOW arrow imprint is perpendicular to the direction of the air flow.
    Mounting for Static Pressure
    NOTE: The FLOW arrow imprint on the pickup tubes can point either up or down.
    NOTE: It is recommended that an indication or marking be applied to the SSS-10xx probe to indicate the intended orientation.

  2. Cut a 7/8″ (22 mm) hole in the duct to accept the pickup tubes.
    Mounting for Static Pressure

  3. Attach the pickup tubes to the duct using two self tapping screws inserted through the 3/16″ (5 mm) mounting holes.
    Mounting for Static Pressure
    NOTE: If mounting SSS-10xx pickup tubes perpendicular to a relatively small diameter round duct, take care not to break the pickup tubes by overtightening the screws and over flexing the plastic mount.

Connections

Using appropriately sized polyethylene tubing, connect either the H or L port on the pickup tubes to the High port on the controller.
NOTE: The other port of the pickup tubes is left unconnected and open to air.
NOTE: Tubing should be free of kinks and restrictions.
Connections

Select Specifications

Material: Light gray (SSS-100x) or almond (SSS-101x) ABS/polycarbonate (UL94-5V)
Connection: 1/4″ nipple (SSS-100x) for 3/8″ OD polyethylene tubing or 3/16″ nipple (SSS-101x) for 1/4″ OD tubing.
K Factors: Refer to the data sheet for additional information!

NOTE: The appropriate “K” factor for the pickup tubes depends upon the type of setup required by the VAV controller with which it will be used:

  • For VAV controllers that require KCFM for setup, refer to the “Cubic Feet Per Minute (CFM)” chart below and the device documentation for additional information.
    For rectangular ducts, KCFM = KFPM x (W” x H”/144) (with duct cross-section measurements in inches).

  • For VAV controllers that require KFPM for setup, refer to the “Feet Per Minute” chart below and the device documentation for additional information

“Cubic Feet Per Minute (CFM)” K Factors


Round Duct Size (Diameter)| KCFM Factor
SSS-10×2| SSS-10×3| SSS-10×4| SSS-10×5
4| 301| NA| NA| NA
5| 470| NA| NA| NA
6| 677| 648| NA| NA
7| 922| 882| NA| NA
8| 1204| 1152| 1117| NA
9| 1524| 1458| 1414| NA
10| 1882| 1800| 1745| 1745
12| 2710| 2592| 2513| 2513
14| 3688| 3528| 3421| 3421
16| 4817| 4608| 4468| 4468
18| 6097| 5832| 5655| 5655
22| 9107| 8711| 8447| 8447
24| 10838| 10367| 10053| 10053

“Feet Per Minute” K Factors


Pickup Tube Model| KFPM
SSS-10×2| 3450
SSS-10×3| 3300
SSS-10×4| 3200
SSS-10×5| 3200

Maintenance

The air pickup orifices must be kept free of dust accumulation or debris. The pickup tubes are designed for dependable, long-term reliability and performance.

More Information

For additional K factor and other information, see the data sheet for the SSS-1000 series on the KMC web site (https://[www.kmccontrols.com/)](http://www.kmccontrols.com/)

Important Notices

The KMC logo and KMC Controls are registered trademarks of KMC Controls, Inc.

All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc.

The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the
use of this document.

KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
[email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

KMC User Manuals

Related Manuals