eipl ECO85 INDUSTRIAL DEHUMIDIFIER Owner’s Manual
- June 5, 2024
- EIPL
Table of Contents
ECO85
INDUSTRIAL DEHUMIDIFIER
**OWNER’S MANUAL
INTRODUCTION
Designed for a wide range of applications, the ECO85 dehumidifier is a rugged,
industrial unit that utilizes an energy-efficient compressor and a compact
portable design to provide easy efficient drying.
The ECO85 has a number of special features:
- Compact Size
- High-efficiency rotary compressor
- Ebac’s “Hot Gas” defrost system
- Exterior epoxy powder-coated finish
- Provision for permanent drainage
- Extra long power cord
The fan draws the moist air through the cold evaporator coil, which cools the
air below its dew point. Moisture forms on the evaporator coil and is
collected in the condensate tray, which is equipped with a permanent drain.
The cooled air then passes through the hot condenser coil where it is reheated
using the same energy removed during the cooling phase, plus the additional
heat generated by the compressor. The air is, therefore, discharged from the
dehumidifier at a slightly higher temperature with lower absolute humidity
than that which entered. Continuous circulation of air through the
dehumidifier gradually reduces the relative humidity within the area.
The ECO85 dehumidifier is a rugged, reliable drying unit designed to operate
effectively over a broad range of temperature and humidity conditions. An
active hot gas defrosts system, controlled by an electronic timer, guarantees
positive de-icing, thereby optimizing operation at low temperatures.
The unit incorporates a welded and galvanized steel chassis and is finished in
an epoxy coating for resilience to damage caused by rough handling.
SPECIFICATIONS
MODEL:
HEIGHT:
WIDTH:
DEPTH:
WEIGHT:
AIRFLOW:
EXTRACTION:
POWER SUPPLY:
FINISH:
OPERATING RANGE:
REFRIGERANT:| ECO85
700mm
480mm
390mm
40 kg
650 M3/Hr
30L / Day
230V/ 50Hz/ 1 ph
Powder-coated Epoxy
3°C – 35°C
R-407c ( g)
---|---
“This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol. The refrigeration system is hermetically sealed.
The Global Warming Potential (GWP) of refrigerants used in products
manufactured by Ebac
Industrial Products Ltd is as follows
R134a – 1300
R407c – 1610
For the type and weight of refrigerant contained in this unit, please refer to
the product data label”
OPERATION
The following procedures should be followed to test the CD85 for correct operation:
- After unpacking, examine all external features to confirm damage-free shipment. Report all defects and damage at once. Connect the power cable to a grounded electrical outlet. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain.
- Check the dehumidification process as follows:
TO ENSURE CONTINUED FULL EFFICIENCY OF THE DEHUMIDIFIER, MAINTENANCE PROCEDURES SHOULD BE PERFORMED AS FOLLOWS:
A. Place the unit on a level surface.
B. Start up the unit by connecting to the mains supply and switching the on-
off switch to the ‘I’ position.
C. Check that the compressor is running.
D. Leave the machine running for 15 minutes.
E. Observe the evaporator coils through the evaporator filter panel
i. If the air temperature is below 80° F, an even coating of
frost should cover the entire evaporator coil
ii. If the air temperature is above 80° F, frost and/or droplets of condensed
water should cover the entire evaporator coil.
F. After a continuous running time of approximately 55 minutes, the unit will
enter “Hot Gas” defrost mode for 5 minutes and then automatically return to
normal operation.
If, after carrying out the above procedures, the unit does not appear to
function properly, refer to the Trouble Shooting section, which follows, or
contact the Factory Service Center.
CAUTION:
ONCE THE UNIT HAS BEEN SWITCHED OFF, WAIT AT LEAST FIVE MINUTES BEFORE
RESTARTING.
After using the ECO85, turn it off for 5 minutes to allow the condensate on
the coils to drain into the pump reservoir, then turn it back on and press the
momentary purge switch for twenty to thirty seconds to evacuate the water
from the pump reservoir.
ROUTINE SERVICE
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows:
WARNING:
ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE
CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD
ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON.
-
Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air. Hold the nozzle of the air hose away from the coil to avoid damaging the fins. Alternatively, vacuum clean the coils.
WARNING:
DO NOT STEAM CLEAN REFRIGERATION COILS -
Check that the fan is firmly secured to the motor shaft and that the fan rotates freely. The fan motor is sealed for life and therefore does not need oiling.
-
To check the refrigerant charge, run the unit for 15 minutes and briefly remove the evaporator filter cover. The evaporator coil should be evenly frost coated across its surface. At temperatures above 80°F, the coil may be covered with droplets of water rather than frost. Partial frosting accompanied by a frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge.
-
Check all wiring connections.
-
To check the operation of the defrost system, switch the machine on and leave it running for approximately 55 minutes. The machine will then enter “Hot Gas” defrost mode for approximately 5 minutes before returning to normal operation. If the unit will not defrost, the printed circuit timer board may be defective or the by-pass valve may be inoperable.
IF ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC SERVICE CENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE.
REPAIRS
-
Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part.
If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action -
Any competent refrigeration technician will be able to service the equipment. The following procedure must be used:
a. The source of the leak must be determined and corrected.
b. The machine should be thoroughly evacuated before recharging.
c. The unit must be recharged with refrigerant measured accurately by weight.
d. For evacuation and recharging of the machine, use the crimped and brazed charging stub attached to the side of the refrigerant compressor.
The charging stub should be crimped and brazed after servicing. NEVER allow permanent service valves to be fitted to any part of the circuit. Service valves may leak causing further loss of refrigerant gas. -
The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service. Compressor failure can result from the machine losing its refrigerant gas. The compressor can be replaced by a competent refrigeration technician. Failure of the compressor can be confirmed by the following procedure:
a. Establish that power is present at the compressor terminals using a voltmeter.
b. With the power disconnected, check the continuity of the internal winding by using a meter across the compressor terminals. An open circuit indicates that the compressor should be replaced.
c. Check that the compressor is not grounded by establishing that a circuit does not exist between the compressor terminals and the shell of the compressor.
TROUBLESHOOTING
S YMPTOM | C AUSE **R EMEDY** |
---|---|
Unit inoperative | 1. No power to the unit |
power supply panel
Little or no airflow| 1. Fan motor burnt out
2. Dirty refrigeration coils
3. Loose electrical wiring| 1. Replace the fan motor
2. See Routine Maintenance Section
3. Check the wiring diagram to find faults and repair
Little or no water extraction| 1. Insufficient airflow
2. Compressor fault
3. Loss of refrigerant gas| 1. Check all of the above
2. Contact the Factory Service Center
3. Contact the Factory Service Center
Little or no defrost when required| 1. Faulty timer
2. Faulty by-pass valve| 1. Contact the Factory Service Center
2. Contact the Factory Service Center
Unit vibrates excessively| 1. Loose compressor
2. Damaged fan| 1. Tighten the nuts on the compressor mounts
2. Replace fan
Water flooding inside the machine| 1. Drain pipe blocked/frozen
2. Drain pipe too high
3. Crimped or blocked tubing| 1. Clear the obstruction
2. Ensure that no section of the drain hose is 1M max. above the level of the
water outlet
3. Straighten, clear, or replace tubing
ECO85
SPARE PARTS LIST
NUMBER | DESCRIPTION | PART NUMBER | QUANTITY |
---|---|---|---|
1 | Defrost Timer | 1619508 | 1 |
2 | Terminal Block | 3031460 | 1 |
3 | Capillary Tube | 3014254 | 2 x 24” |
4 | Solenoid Valve | 3020837 | 1 |
5 | Filter Dryer | 3020909 | 1 |
6 | Compressor | 3944918 | 1 |
7 | Solenoid Coil | 3030452 | 1 |
8 | Capacitor | 3037513 | 1 |
9 | Filter | 2029826 | 1 |
10 | Mains Lead | 2029217 | 1 |
11 | Fan Motor | 3040253 | 1 |
12 | Fan Motor Inlet Ring | 3040254 | 1 |
13 | Fan Motor Capacitor | 3030841 | 1 |
14 | Relay | 3036188 | 1 |
15 | Rubber Foot | 3088553 | 2 |
16 | Condensate Pump | 3160151 | 1 |
17 | Condenser Coil | 2029322 | 1 |
18 | Evaporator Coil | 2029323 | 1 |
Spare parts are available online
www.EIPLDIRECT.com
WARNINGS
This appliance can be used by children from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning the
use of the application in a safe way and understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without
supervision.
If the SUPPLY CORD is damaged, it must be replaced by the manufacturer, its
service agent, or a similarly qualified person in order to avoid hazards.
This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol. The refrigeration system is hermetically sealed.
The Global Warming Potential (GWP) of refrigerants used in products
manufactured by Ebac Industrial Products Ltd is as follows
R134a – 1300
R407c – 1610
For the type and weight of refrigerant contained in this unit, please refer to
the product data label
Due to the high pressures within the refrigeration circuit, under no
circumstances must direct heat be applied to the evaporator coil in an attempt
to remove the build-up of ice.
No attempt should be made to cut open any part of the refrigeration circuit
due to the high pressures and gas involved.
If the unit is switched off at the mains power supply for any reason, the unit
must be allowed to stand at rest for at least three minutes before restarting.
For correct installation and operation, the unit inlet and outlet must have a
clearance of 0.5M from all adjacent surfaces and or structures.
Drawing : – TPC374
Issue : – 6
Date: – 24/11/16
UK Head Office
Ebac Industrial Products Ltd
St Helens Trading Estate
Bishop Auckland
County Durham
DL14 9AD
Tel: +44 (0) 1388 664400
Fax: +44 (0) 1388 662590
www.eipl.co.uk
sales@eipl.co.uk| Page 12 of 12
American Sales Office
Ebac Industrial Products Inc
700 Thimble Shoals Blvd.
Suite 109, Newport News
Virginia, 23606-2575
USA
Tel: +01 757 873 6800
Fax: +01 757 873 3632
www.ebacusa.com
sales@ebacusa.com| German Sales Office
Ebac Industrial Products Ltd.
Gartenfelder Str. 29-37
Gebäude 35
D-13599, Berlin
Germany
Tel: +49 3043 557241
Fax: +49 3043 557240
www.eip-ltd.de
sales@eip-ltd.de
---|---|---
Get In Touch
Call: 0845 6880112
Email: info@adremit.co.uk
Our Address
Prevent, Adremit Limited, Unit 5a, Commercial Yard,
Settle, North Yorkshire, BD24 9RH
References
- EIP Group - Industrial Dehumidifiers
- EIP Group - Industrial Dehumidifiers
- EIPL - Industrial Dehumidifiers
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>