EIPL RM85-H Industrial Dehumidifier Owner’s Manual
- June 5, 2024
- EIPL
Table of Contents
EIPL RM85-H Industrial Dehumidifier
INTRODUCTION
Designed for a wide range of applications, the RM85H is a rugged, industrial
unit, which utilizes an energy-efficient compressor and a compact portable
design to provide easy efficient drying.
The RM85H has a number of special features:
- High-efficiency rotary compressor
- EIPL’s “Hot Gas” defrost system
- Hours run meter
- Integral pump-out system
- Provision for permanent drainage
- xtra long power cord
- Robust rotational molded polyethylene housing
- Separate outlets allowing dry air to be ducted
The fan draws the moist air through the cold evaporator coil, which cools the
air below its dew point. Moisture forms on the evaporator coil and is
collected in the condensate tray, which is equipped with a permanent drain.
The cooled air then passes through the hot condenser coil where it is reheated
using the same energy removed during the cooling phase, plus the additional
heat generated by the compressor. The air is, therefore, discharged from the
dehumidifier at a slightly higher temperature with lower absolute humidity
than that which entered. Continuous circulation of air through the
dehumidifier gradually reduces the relative humidity within the area. The
RM85H dehumidifier is a rugged, reliable drying unit designed to operate
effectively over a broad range of temperature and humidity conditions. An
active hot gas defrosts system, controlled by an electronic timer, guarantees
positive de-icing, thereby optimizing operation at low temperatures.
A digital Humidistat is included which allows for precise humidity control. A
programmable display lets you set a specific desired humidity level.
The unit incorporates a rotationally molded polyethylene shell resilient to
damage caused by rough handling.
SPECIFICATIONS
- MODEL: 10560RH-GB
- HEIGHT: 945 mm
- WIDTH: 545 mm
- DEPTH: 492 mm
- WEIGHT: 45 kg
- AIRFLOW: 390 M3/Hr
- POWER SUPPLY: 230V/ 50Hz/ 1 ph
- FINISH: Rotational Moulded polyethylene
- OPERATING RANGE: 3°C – 35°C
- REFRIGERANT: R407c (500g)
“This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. The refrigeration system is hermetically sealed. The Global Warming Potential (GWP) of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a – 1300 R407c – 1610 For the type and weight of refrigerant contained in this unit, please refer to the product data label”
OPERATION
The following procedures should be followed to test the RM85 for correct operation:
-
After unpacking, examine all external features to confirm damage-free shipment. Report all defects and damage at once. Connect the power cable to a grounded 13 Amp electrical outlet. Connect the drainage outlet to a suitably sized hose and run the hose to a permanent drain
-
Setting the Digital Humidistat The Digital Humidistat is factory preset to give the optimum level of control. Only adjustment of the desired set point is required.During normal operation, the display shows the current % Relative Humidity within the space being conditioned.
The required humidity level can be set as follows:- Press the “S” button once to access the set point
- Press the or button to change the display to the desired Humidity level
- Press the “S” button again to save the set point – The control returns to displaying the current % Relative Humidity
-
Check the dehumidification process as follows:
CAUTION:
DO NOT REMOVE COVERS WHEN THE UNIT IS IN OPERATION- Place unit on a level surface.
- Start-up unit by switching to “I”.
- Check that the compressor is running.
- Leave the machine running for 15 minutes.
- Observe the evaporator coils through the front grille, to confirm frost formation or weeping.
- If the air temperature is below 25°C, an even coating of frost should cover the entire evaporator coil.
- If the air temperature is above 25°C, frost and/or droplets of condensed water should cover the entire evaporator coil.
- When the unit has operated an ambient of less than 15°C, a defrost cycle should occur approximately every hour. The exact time is impossible to predict as the unit is fitted with a temperature-sensitive defrost control. During this defrost cycle the fan will switch off.
When the unit is defrosting, the % Relative Humidity displayed on the digital controller may increase as a result of the ice/frost melting. This is quite normal and the display will return to its normal reading when the unit returns to dehumidifying mode. (Fan running)If, after carrying out the above procedures, the unit does not appear to function properly, refer to the Trouble Shooting section, which follows, or contact the Factory Service Center.
CAUTION:
ONCE THE UNIT HAS BEEN SWITCHED OFF, WAIT AT LEAST FIVE MINUTES BEFORE
RESTARTING.
After using the RM85H, turn it off for five minutes to allow the condensate on the coils to drain into the pump reservoir, then turn it back on and press the momentary purge switch for twenty to thirty seconds to evacuate the water from the pump reservoir.
ROUTINE SERVICE
WARNING:
ENSURE THAT THE POWER CORD TO THE MACHINE HAS BEEN DISCONNECTED BEFORE
CARRYING OUT ROUTINE SERVICE. THE SERVICING AND REPAIR OF THIS UNIT SHOULD
ONLY BE CARRIED OUT BY A SUITABLY QUALIFIED PERSON.
To ensure continued full efficiency of the dehumidifier, maintenance procedures should be performed as follows:
- Clean the surface of the evaporator and condenser coils by blowing the dirt out from behind the fins with compressed air. Hold the nozzle of the air hose away from the coil to avoid damaging the fins. Alternatively, vacuum clean the coils.
- Check that the fan rotates freely. The fan motor is sealed for life and therefore does not need oiling.
- To check the refrigerant charge, run the unit for 15 minutes and observe the evaporator coil. It should be evenly coated with frost across its surface. At temperatures above 25°C, the coil may be covered with droplets of water rather than frost. Partial frosting accompanied by frosting of the thin capillary tubes, indicates loss of refrigerant gas or low charge.
- Check all wiring connections, including mains cable for damage or loose connections.
- In order to check the defrost operation, the unit needs to be operated in an ambient temperature of less than 15°C for at least 1 hour. When operated In this condition the unit should defrost at least once every hour. The defrost mode can be monitored by observing the ice melting on the coil face, prior to defrost the face will show a white coating of frost, which should clear during defrost
IF ANY OF THE PRECEDING PROBLEMS OCCUR, CONTACT THE EBAC SERVICE CENTER PRIOR TO CONTINUED OPERATION OF THE UNIT TO PREVENT PERMANENT DAMAGE.
REPAIRS
-
Should an electrical component fail, consult the Factory Service Center to obtain the proper replacement part.
-
If refrigerant gas is lost from the machine, it will be necessary to use a refrigeration technician to correct the fault. Contact the Factory Service Center prior to initiating this action.
Any competent refrigeration technician will be able to service the equipment. The following procedure must be used:- The source of the leak must be determined and corrected.
- The machine should be thoroughly evacuated before recharging.
- The unit must be recharged with refrigerant measured accurately by weight.
d. For evacuation and recharging of the machine, use the crimped and brazed charging stub attached to the side of the refrigerant compressor.
The charging stub should be crimped and rebrazed after servicing. NEVER allow permanent service valves to be fitted to any part of the circuit. Service valves may leak causing further loss of refrigerant gas.
-
The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service. Compressor failure can result from the machine losing its refrigerant gas. The compressor can be replaced by a competent refrigeration technician.
Failure of the compressor can be confirmed by the following procedure:- Establish that power is present at the compressor terminals using a voltmeter.
- With the power disconnected, check the continuity of the internal winding by using meter across the compressor terminals. An open circuit indicates that the compressor should be replaced.
- Check that the compressor is not grounded by establishing that a circuit does not exist between the compressor terminals and the shell of the compressor.
TROUBLESHOOTING
S YMPTOM | C AUSE **R EMEDY** |
---|
Unit inoperative
| ****
1. No power to unit
2. Mains cable damaged.
| 1. Check the power from power supply panel.
2. Contact the Factory Service Center
Little or no airflow
| ****
1. Fan motor burnt out
2. Dirty refrigeration coils
3. Loose electrical wiring
| 1. Replace the fan motor
2. See Routine Maintenance
Section
3. Check the wiring diagram to find fault and repair
Little or no water extraction
| 1. Insufficient air flow
2. Compressor fault
3. Loss of refrigerant gas
| 1. Check all of the above
2. Contact the Factory Service Center
3. Contact the Factory Service Center
Little or no defrost when required
| ****
1. Faulty timer
2. Faulty by-pass valve
| 1. Contact the Factory Service Center
2. Contact the Factory Service Center
Unit vibrates excessively| 1. Loose compressor
2. Damaged fan
| 1. Tighten the nuts on the compressor mounts
2. Replace fan
Water flooding inside the machine
| ****
1. Drain pipe blocked/frozen
2. Drain pipe too high
3. Crimped or blocked tubing
| 1. Clear the obstruction
2. Ensure that no section of the drain hose is above the level of the water outlet
3. Straighten, clear, or replace tubing
RM85
SPARE PARTS LIST
N UMBER| DESCRIPTION| P ART
N UMBER
| Q UANTITY
---|---|---|---
1| Timer| 1619508| 1
2| Condenser coil| 2029322| 1
3| Evaporator coil| 2029323| 1
4| Cable & Tube wrap| 2056002| 2
5| Drain tray| 2056003| 1
6| Filter| 2056004| 1
7| Capillary| 3014254| 2 X 2ft
8| Solenoid valve| 3020837| 1
9| Filter dryer| 3020909| 1
10| Defrost Relay| 3030270| 1
11| Solenoid coil| 3030452| 1
12| Humidity Controller| 3031526| 1
13| On/Off switch| 3035914| 1
14| Power Relay| 3036188| 1
15| Run capacitor| 3036337| 1
16| Pump purge switch| 3036779| 1
17| Fan| 3040278| 1
18| Fan inlet ring| 3040283| 1
19| Wheel| 3050124| 2
20| Rubber foot| 3101436| 2
21| Condensate pump| 3160151| 1
22| Compressor| 3944933| 1
WARNINGS
This appliance can be used by children from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge if they have been given supervision or instruction concerning use of
the application in a safe way and understand the hazards involved. Children
shall not play with the appliance. Cleaning and user maintenance shall not be
made by children without supervision. If the SUPPLY CORD is damaged, it must
be replaced by the manufacturer, its service agent or a similarly qualified
person in order to avoid hazards. This product contains fluorinated greenhouse
gases covered by the Kyoto Protocol. The refrigeration system is hermetically
sealed. The Global Warming Potential (GWP) of refrigerants used in products
manufactured by Ebac Industrial Products Ltd is as follows
R134a – 1300
R407c – 1610
For the type and weight of refrigerant contained in this unit, please refer to
the product data label Due to the high pressures within the refrigeration
circuit, under no circumstances must direct heat be applied to the evaporator
coil in an attempt to remove the build-up of ice. No attempt should be made to
cut open any part of the refrigeration circuit due to high pressures and gas
involved. If the unit is switched off at the mains power supply for any
reason, the unit must be allowed to stand at rest for at least three minutes
before restarting. For correct installation and operation the unit inlet and
or structure.
References
- EIP Group - Industrial Dehumidifiers
- EIP Group - Industrial Dehumidifiers
- EIPL - Industrial Dehumidifiers
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>