TRANE TPLFYP005FM140A 5000 BTU/H 4 Way Ceiling Cassette Owner’s Manual

June 17, 2024
Trane

TRANE TPLFYP005FM140A 5000 BTU/H 4 Way Ceiling Cassette

TRANE-TPLFYP005FM140A-5000-BTU-H-4-Way-Ceiling-Cassette-
PRODUCT

Product Information

Specifications

  • Unit Type: 4-Way Ceiling Cassette
  • Cooling Capacity (Nominal): 5,000 BTU/H
  • Heating Capacity (Nominal): 5,600 BTU/H
  • Power Source: 208/230V, 1-phase, 60 Hz
  • Power Consumption:
    • Cooling: 0.02 kW
    • Heating: 0.02 kW
  • Current:
    • Cooling: 0.19 A
    • Heating: 0.14 A
  • MCA (Minimum Circuit Ampacity):
    • Cooling: 0.24 A
    • Heating: 0.19 A
  • Maximum Overcurrent Protection (MOCP): 15 A
  • External Finish: Galvanized Steel Sheet
  • External Dimensions: 22-7/16 x 22-7/16 x 8-3/16 inches [570 x 570 x 208 mm]
  • Net Weight: 28.9 lbs [13.1 kg]
  • Heat Exchanger: Cross fin (Aluminum fin and copper tube)

FAQ

  • Q: What is the cooling capacity of the TPLFYP005FM140A ceiling cassette unit?
    • A: The cooling capacity is 5,000 BTU/H.
  • Q: What is the power source requirement for this unit?
    • A: The unit requires a voltage of 208/230V, 1-phase, 60 Hz.
  • Q: How do I control the temperature and mode of the unit?
    • A: You can use either the control interface or the provided remote controller to set the desired temperature and mode.
  • Q: How often should I clean or replace the air filter?
    • A: It is recommended to clean or replace the air filter every 3 to 6 months, depending on usage and air quality.

GENERAL FEATURES

  • Square edge, sleek design
  • 3D i-see Sensor™ available as an option
  • Improved installation features*
  • Occupancy detection*
  • Energy saving features*
  • Improved occupant comfort
  • Four fan speed settings including auto-fan
  • Individual vane settings
  • 2’ x 2’ size matches size of many ceiling tiles
  • Corner-pocket design for simplified installation
  • Built-in condensate lift mechanism designed to provide up to 33” of lift
  • Ventilation air intake supported

Requires a PAR-33MAA-J controller

Specifications

Specifications System
Unit Type TPLFYP005FM140A
Cooling capacity (Nominal)1 BTU/H
Heating capacity (Nominal)1 BTU/H
Power source Voltage, Phase, Hertz

Power Consumption

| Cooling| kW| 0.02
Heating| kW| 0.02

Current

| Cooling| A| 0.19
Heating| A| 0.14
MCA| A| 0.24
Maximum Overcurrent Protection (MOCP)| A| 15
External finish| Galvanized steel sheet
External Dimensions| In. [mm]| 22-7/16 x 22-7/16 x 8-3/16 [570 x 570 x 208]
Net weight| Lbs [kg]| 28.9 [13.1]
Heat exchanger| Cross fin (Aluminum fin and copper tube)

Fan

| Type x quantity| Turbo fan x 1
Airflow rate| CFM| 230–265–280
Motor type| DC motor
Motor Output| kW| 0.05
Motor FLA| A| 0.19
Sound pressure level (Measured in anechoic room)| dB(A)| 26–28–30
Air filter| PP honeycomb fabric (long life type)
Refrigerant| Type| R410A

Diameter of refrigerant pipe (O.D.)

| Liquid (High Pressure)| In. [mm]| 1/4 [6.35] Flare
Gas (Low Pressure)| In. [mm]| 1/2 [12.7] Flare
Diameter of drain pipe| In. [mm]| O.D. 1-1/4 [32]

NOTES

  1. Cooling / Heating capacity indicated at the maximum value at operation under the following conditions:
    • Cooling | Indoor: 80° F (26.7° C) DB / 67° F (19.4° C) WB; Outdoor 95° F (35° C) DB
    • Heating | Indoor: 70° F (21.1° C) DB; Outdoor 47° F (8.3° C) DB / 43° F (6.1° C) WB

INDOOR UNIT ACCESSORIES

INDOOR UNIT ACCESSORIES: TPLFYP005FM140A

Control Interface

| Connector cable for remote display| □ PAC-SA88HA-EP
---|---|---
IT Extender| □ PAC-WHS01IE-E
kumo station® for kumo cloud®| □ TAC-WHS01HC-E
Procon BACnet® and Modbus® Interface| □ PAC-UKPRC001-CN-1
Thermostat Interface| □ PAC-US444CN-1
Thermostat Interface| □ PAC-US445CN-1

Remote Sensor

| Flush Mount Remote Temperature Sensor| □ PAC-USSEN002-FM-1
Flush Mount Temperature Sensor| □ PAC-USSEN001-FM-1
Remote Temperature Sensor| □ PAC-SE41TS-E

Terminal Signal Adapter

| Terminal Signal Adapter| □ PAC-IT51AD-E
Terminal Signal Adapter| □ PAC-IT52AD-E

Wired Remote Controller

| Deluxe Wired MA Remote Controller†| □ TAR-40MAAU
Simple Ductless Wired Remote Controller| □ PAC-SDW01RC-1
Simple MA Remote Controller†| □ TAC-YT53CRAU-J
Smart ME Remote Controller – Backlit touchscreen| □ TAR-U01MEDU-K
Touch MA Controller†| □ TAR-CT01MAU-SB

Wireless Remote Controller

| kumo touch™ RedLINK™ Wireless Controller| □ MHK2
Wireless MA Receiver| □ PAR-SR32MA-E
Wireless MA Remote Controller| □ TAR-FL32MA-E
Wireless Receiver| □ PAR-WSC009FA-E
Wireless Remote Contoller| □ PAR-SL101A-E
Wireless Signal Receiver Panel| □ PAR-SR4LU-E

Condensate

| Blue Diamond (Advanced) Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended]| □ X87-721
Blue Diamond (MicroBlue) Mini Condensate Pump (110/208/230V) up to 18,000 BTU/H| □ X86-003
Refco Condensate Pump (100-240 VAC) up to 120,000 BTU/H| □ COMBI

Control Interface

| CN24 Relay Kit| □ CN24RELAY-KIT-CM3
Remote Operation Adapter‡| □ PAC-SF40RM-E
Grille| Grille| □ TLP-18FAU

i-see Sensor® Panel

| 3D i-see Sensor® Corner Panel| □ PAC-SF1ME-E
Grille with 3D i-see Sensor®| □ TLP-18FAEU

NOTES

  • High efficiency filter requires use of multi-function casement: PAC-SJ41TM-E

INDOOR UNIT DIMENSIONS

INDOOR UNIT DIMENSIONS: TPLFYP005FM140A

TRANE-TPLFYP005FM140A-5000-BTU-H-4-Way-Ceiling-Cassette-
FIG-1

More Information

  • Job Name: …………………..
  • System Reference: …………………..
  • Date: …………………..

Specifications are subject to change without notice.

© 2023 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.