CITEL N151001c Surge Protection Installation Guide

June 5, 2024
CITEL

N151001c
INSTALLATION INSTRUCTIONS
AC surge protector DS130R SERIES

Technical Data

2000 m max.
6500 ft max. ** -40/+85°C max.
-40/+185°F max. ** IP20
indoor use only ** Humidity range
5% to 95%| 05131R(5)-120| DS132R(5)-280/G| P/N**
---|---|---|---
05132R(5)-120| O513411(5)-280/G
05133R(5)-120| DS131R(5)-320
D51341(5)-120| O513211(5)-320
05132R(5)-120/0| 05133R(5)-320
DS133R(5)-120/0| O513411(5)-320
DS134R(5)-120/0| 051328(5)-320/G
05131R(5)-230| DS134R(5)-320/0
05132R(5)-230| 051318(5)-400
05133R(5)-230| 051328(5)-400
05134R(5)-230| 051338(5)-400
05132R(5)-230/0| O513411(5)-400
DS134R(5)-230/0| DS132R(5)-400/G
05131R(5)-280| DS134R(5)-400/G
DS132R(5)-280| 051338(5)-800/Y
05133R(5)-280| DS133R(5)-1200/Y2(/R)
05134R(5)-280|

AC Network

120 Vac L+N| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
208 Vac 3L| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
120 Vac 2L+N| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
120/208 Vac 3L+N| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
230 Vac L+N| | | | | | | | | | | | | | | | | | | | | | | | | | IT| IT| | | | | |
320 Vac L+N| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
400 Vac 3L| | | | | | | | | | | | | | | | | | | | | | | | | | | | IT| | | | |
230/400 Vac 3L+N| | | | | | | | | | | | | | | | | | | | | | | | | | | | | IT| | | |
800 Vac 3L| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | IT| IT

Characteristics

KPE* < 1 mA / ( = 0 mA for G version )
Isccr* 25 kA
Imax* 50 kA
Iimp* 12,5 kA

Table 1

*values per pole
Remote signal option: S: e.g DS131RS-230

Installation

min-max ∅

| 2.5 – 35 mm²| 13 – 2 AWG
| 2.5 – 25 mm²| 13 – 4 AWG

Wiring

Standard wiring

* depending on national rules: Solution 1 or 2
Specific Disconnector for SPD provided by CITEL. For more details, consult the CITEL website.
**

Remote contact wiring

| Remote signal for disconnection information
11-12 Closed = SPD OK
11-14 Open = SPD OK
11-12 Open = SPD disconnect
11-14 Closed = SPD disconnect
---|---

Table 3

Maintenance

|
---|---

ATTENTION!

  • Installation must be performed only by an electrically skilled operator.
  • National electrical installation rules must be followed.
  • The unit must be used only as a surge protector and according to the conditions described in this document.
  • Surge protectors must be selected in relation to a dedicated AC network (see Table 1)
  • Dedicated fuses must be installed in the surge protector branch (see Table 2 column 1).
  • In the case of a red indicator, the surge protector must be replaced.

This document could be modified without notice. Updated Information on Website.

2, rue Troyon 92316
Sèvres CEDEX France
www.citel.fr
www.citel.de
www.citel.us
www.citel.com.cn
www.citel.ru
www.citel.in

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals