CITEL M50 Series AC Surge Protector Instruction Manual
- June 4, 2024
 - CITEL
 
Table of Contents
M50 Series AC Surge Protector
Instruction Manual
AC surge protector – Parafoudre Basse Tension Protectiones Baja Tension
M50 Series

Technical Data
Note:
A: For the side nipple
B: for the nipple in the back
* M50F : contains a condenser.
Installation (Fig. 1)
Fusing is not required but only recommended when SPD is installed according to UL 1449.

Installation
- Turn off all power supplying this equipment before working on or inside the equipment.
 - See Installation – Figure 1.
 - Confirm M50 device is rated for your system by comparing voltage measurements to the Line Voltage on the product label.
 - Install in accordance with article 285 of the National Electric Code.
 - Confirm that the electrical terminals used to attach this device are identified for these conductors.
 - Twist conductors 1/2 turn or more for every 12 inches of length.
 - Keep conductor length as short as possible with no sharp bends.
 - Do not loop or coil wires.
 - Ensure a high-quality ground is in place.
 
Diagnostic Operation
- LED ON = Normal operation
 - LED OFF (one or more) = Fault, check phase voltage and connections. If OK, replace the unit.
 - Audible Alarm ON = Fault, check phase
 

Maintenance

**** ATTENTION!
- Installation must be performed only by an electrically skilled operator.
 - National electrical installation rules must be followed.
 - The unit must be used only as a surge protector and according to the conditions described in this document.
 - Surge protectors must be selected in relation to a dedicated AC network (see Table)
 - Dedicated fuses must be installed in the surge protector branch.
 - In the case of the red indicator, the surge protector must be replaced.
 
SAFETY INSTRUCTIONS ** This document could be modified without
notice.
Updated Information on Website.
www.citel2cp.com  
N121002a
**
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>