hager TYA604A Output module 4-fold 4A User Manual
- June 5, 2024
- hager
Table of Contents
6LE008011A TYA604A
Output module 4-fold 4 A
TYA606 A
Output module 6-fold 4 A
TYA608A
Output module 8-fold 4 A
TYA610 A
Output module 10-fold 4 A
Safety instructions
Electrical equipment may only be installed and assembled by a qualified
electrician in accordance with the relevant installation standards,
guidelines, regulations, directives, safety and accident prevention
regulations of the country.
Failure to comply with these installation instructions may result in damage to
the device, fire or other hazards.
Hazard due to electric shock. Disconnect before working on the device or load.
Take into account all circuit breakers that supply dangerous voltages to the
device or load.
Hazard due to electric shock. The device is not suited for safe disconnection
of the main supply.
Hazard due to electric shock on the SELV/PELV installation. Not suitable for
switching SELV/ PELV voltages.
Connect one motor per output only. If several motors are connected, motors or
devices might be destroyed.
Use drives with mechanical or electrical final position switch only. Check
final position switches for correct adjustment. Observe motor manufacturer’s
data. The device could get damaged.
Do not connect any three-phase motors. The device could get damaged. Observe
the motor manufacturer’s data regarding change-over time and max. switch-on
time (ED).
These instructions are an integral component of the product and must be
retained by the end user.
Design and layout of the device
Fig. 1: example device variant 8/4gang
- Slide switch auto/
- KNX bus connection terminal
- Connections of loads
- Labeling field
- Illuminated programming button
- Operation button for manual operation per output with status LED
- Connections for switching voltage
- Mains power supply connections (only 8gang) With variants 4/2gang, 6/3gang and 10/5gang the basic design corresponds to the 8/4gang device variant.
Function
System information
This device is a product of KNX system and corresponds to the KNX guidelines.
Detailed specialized knowledge obtained from KNX training courses is required
for comprehension. The planning, installation, and commissioning of the device
is carried out with the help of KNX-certified software.
System link commissioning
The function of the device is software-dependent. The software is to be taken
from the product database.
You can find the latest version of the product database, technical
descriptions as well as conversion and additional support programs on our
website.
Functional description
The device receives telegrams from sensors or other controllers via the KNX
installation bus and switches electrical loads with its independent relay
contacts.
Correct use
– Switch electrical loads of 230 V AC with potential-free contacts.
– Switching electrically operated motors of 230 V AC for blinds, shutters,
awnings and similar hangings.
– Mounting on DIN rail according to DIN EN 60715 in the distribution box.
Product characteristics
- Manual activation of the outputs on the device possible, building site operation.
- Status display of the outputs on the device.
- Scene function
- Forced position by the higher-level controller.
- Connection of various external conductors is possible.
Functions in switch operation
-
Time switching functions.
Functions in roller shutter/blind operation -
The position can be started directly.
-
Slat position directly controllable.
-
Feedback of operating state, shutter position, and slat adjustment.
-
3 Alarms.
Operation
The manual operation switch on/off
With the 8/4gang variants, control of the outputs is possible even without bus
voltage when the mains voltage is connected e.g. for operation at building
sites.
Bus or mains power supply is present.
Push switch (1) to the position.
Manual operation is switched on, the outputs can be controlled using the
operation buttons
(6) independently of each other.
During manual operation, the controller is deactivated via the KNX bus.
System link commissioning:
depending on the programming, the manual operation is activated permanently or
for a time period configured via the application software.
If the manual operation is blocked via the application software, no activation
takes place. Or Move switch (1) to position auto.
The manual operation is switched off. The operation takes place solely via the
KNX bus. The output adopts the position predefined by the bus controller.
Operating outputs in manual operation
The operation takes place per output by briefly pressing the operation button
repeatedly (Table 1).
CAUTION! Risk of destruction due to the simultaneous pressing of the
buttons for UP and DOWN if a motor is connected when the motor is in an
unprogrammed state! Motors, hangings and the device may be destroyed! Always
only press one button in manual operation for unprogrammed devices.
Status | Behavior when button pressed briefly |
---|
Switching operation
Load is switched off, status LED of button (6) is off.| Switch ON the
connected load. Status LED of a button (6) lights up.
Load is switched on, status LED of the button (6) lights up.| Switch OFF the
connected load. The LED goes out.
Roller shutter/blind operation
Output is in stand- by, status LED
of the button (6) is off.| Movement operation starts. Status LED of button (6)
lights up1).
When the roller shutter/ blind is in the final position, the button opposite
must be pressed to move the shutter/blind.
Output active, status LED of the button (6) lights up’).| Movement operation
stops, LED goes out.
- LED lights up red with TYA6.. devices. LED lights up red while moving up and green while moving down with TXA6.. devices.
Table 1: manual operation
Information for electricians
Installation and electrical connection
DANGER! Touching live parts can result in an electric shock!
An electric shock can be lethal! Disconnect the connecting cables before
working on the device and cover all live parts in the area!
CAUTION! Impermissible heating if the load of the device is too high! The
device and the connected cables may get damaged in the connection area!
Do not exceed the maximum current carrying capacity!
CAUTION! Risk of destruction if the parallel connection of several motors
on one output! Final position switches could fuse together. Motors, hangings
and the device may be destroyed! Only connect one motor per output!
Installing the appliance
Observe temperature range. Provide sufficient cooling.
Mount devise onto DIN rail in accordance with DIN EN 60715.
Connect device
|
---|---
Connect bus cable via connecting terminal (2).
Mains voltage can be connected optionally for device variants 8/4gang (8).
Reduction of the power supply load is possible (see Technical data).
Connecting loads to be switched
The output is configured as switching output.
- Connect switching voltage on the upper terminal strip (7) of the device.
- Connect load on the lower terminal strip (3) of the device.
Connecting blind drives
The two adjacent relay outputs C1/C2, C3/C4, C5/ C6, C7/C8 each form one blind
output for blind operations. Each left relay output C1, C3, C5, C7is intended
for the direction UP, and each right relay output C2, C4, C6, C8 is intended
for the direction DOWN. In manual operation, the blind is moved UP and DOWN
using the corresponding operation buttons.
Two outputs are configured as a blind outputs.
Connect supply voltage of the drives on the upper terminal strip (7). While
doing so, use the same phase (external conductors).
Connect drives on the lower terminal strip (3).
Start-up
System link: loading physical address and application software
- The switch (1) is in position auto.
- Switch on bus voltage.
- Press the programming button (5). The button lights up.
If the button does not light up, no bus voltage is present.
- Load the physical address into the device.
- The status LED of the button goes out.
- Load application software.
- Note down the physical address on the labeling field (4).
Start up the device
- Switch on mains voltage on the outputs.
- Switch on main power supply (8gang variant).
Determine operation time and slat adjusting time
In blind/roller shutter operation, the operation time for positioning the
sunshade is important. The position is calculated based on the operation time.
The slat adjusting time for slat blinds, determined by the design, is part of
the total operation time.
The opening angle of the slats is therefore set as operation time between
opened and closed positions.
The operation time for UP is normally longer than the operation time for DOWN
and must be measured separately if necessary.
- Measure UP and DOWN operation time of the hanging.
- Measure slat adjusting time between OPEN and CLOSED.
- Enter measured values into the parameter setting – running time… or slat step time.
Functional test
The functionality of the outputs is displayed via the status LED of the
operation button (6).
Appendix
Technical data
Supply voltage KNX | 21-32V SELV |
---|---|
Breaking capacity | µ 10A AC1 230V~ |
Incandescent lamps | 800 W |
HV halogen lamps | 800 W |
Conventional transformers | 800 W |
electronic transformers | 800 W |
Fluorescent lamps:
– without ballast
– with electronic ballast (mono/duo)| 800 W
12 x 36 W
Energy-saving/LED lamps | 12 x 23 W |
---|---|
Switching current at cos Φ = 0.6 | max. 2,5 A |
Upstream protection: circuit breaker | 10:00 AM |
Minimum switching current | 100 mA |
Interlock time for
changing direction of travel | software-dependent |
---|---|
Operating altitude | max. 2000 m |
Degree of contamination | 12:00 AM |
Surge voltage | 4 kV |
Degree of protection of housing | IP20 |
Degree of protection of housing under front panel | IP30 |
Impact protection | IK 04 |
--- | --- |
Overvoltage class | III |
Operating temperature | -5° … +45°C |
Storage/transport temperature | -20 … +70 °C |
Maximum switching cycle rate
at full load | 6 switching cycle/minute |
---|---|
Connection capacity | 0.75 mm²…2.5 mm² |
Communication media KNX | TP 1 |
Configuration mode | S-Mode |
Variants 4/2gang
Energy dissipation | 1 W |
---|---|
Permissible highest current strength per device | max. 16 A |
Own consumption on the KNX bus: – typical | 4 mA (TYA..) |
– in standby | 3,3 mA (TYA..) |
Dimension | 4 TE, 4 x 17.5 mm |
Variants 6/3gang
Energy dissipation | 1 W |
---|---|
Permissible highest current strength per device | max. 24 A |
Own consumption on the KNX bus: – typical | 4,3 mA (TYA..) |
– in standby | 3,3 mA (TYA..) |
Dimension | 4 TE, 4 x 17.5 mm |
Variants 8/4gang
Auxiliary voltage | 230V~ +10/-15%240V~ +/-6% |
---|---|
Energy dissipation | 2 W |
Permissible highest current strength per device | max. 32 A |
Own consumption on the KNX bus: – typical | 15,2 mA (TYA..) |
– in standby | 8,6 mA (TYA..) |
Own consumption on the KNX bus with mains connection: – typical – in standby |
2 mA (TXA.., TYA..)
2 mA (TXA.., TYA..)
Dimension| 6 TE, 6 x 17.5 mm
---|---
Variants 10/5gang
Energy dissipation| 3 W
Permissible highest current strength per device| max. 40 A
Own consumption on the KNX bus: – typical| 15,9 mA (TYA..)
– in standby| 7,5 mA (TYA..)
Dimension| 6 TE, 6 x 17.5 mm
Troubleshooting
Manual operation not possible
Cause 1: switch (1) not moved to .
Move the switch to .
Cause 2: manual operation has not been enabled (System link).
Enable manual operation via the application software.
Bus operation is not possible
Cause 1: bus voltage is not present.
Check bus connection terminals for correct polarity.
Check bus voltage by briefly pressing the programming button (5), a red LED
lights up if bus voltage is present.
8gang: If mains voltage without bus voltage is present – the red LED of
programming button (5) flashes.
Cause 2: manual operation is active. Switch (1) is in position. Move switch
(1) to position auto.
Shutters/blinds do not move to the final position Cause: operation time for
the shutters/blinds set incorrectly.
Check operation times. Measure again and reprogram if necessary.
WARNING!
The supply voltages of the electric circuits connected to the product must
always all fall within the same voltage range (LV (low voltage), VLV (very-low
voltage) or SELV (safety extra-low voltage)). Connecting voltages of different
ranges is strictly prohibited.
Correct Disposal of This product (Waste Electrical & Electronic Equipment).
(Applicable in the European Union and other European countries with separate
collection systems).
This marking shown on the product or its literature indicates that it should
not be disposed of with other households’ waste at the end of its working
life. To prevent possible harm to the environment or human health from
uncontrolled waste disposal, please separate this from other types of waste
and recycle it responsibly to promote the sustainable reuse of material
resources. Household users should contact either the retailer where they
purchased this product, or their local government office, for details of where
and how they can take this item for environmentally safe recycling. Business
users should contact their suppliers and check the terms and conditions of the
purchase contract.
This product should not be mixed with other commercial wastes of disposal.
Usable in all Europe and in Switzerland
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>