EMERSON Rosemount 644 Rail Mount Temperature Transmitter with RK Option
and HART 7 Protocol
About this guide
This guide provides basic guidelines for installing the Rosemount 644R Rail
Mount Temperature Transmitter. It does not provide instructions for detailed
configuration, diagnostics, maintenance, service, troubleshooting, or
installation. Refer to the Rosemount 644R Rail Mount Reference Manual for more
instruction. The manual and this guide are also available electronically on
Emerson.com/Rosemount.
Safety messages
WARNING
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-
qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local
Emerson Sales Representative.
Follow instructions
Failure to follow these installation guidelines could result in death or
serious injury.
Ensure only qualified personnel perform the installation.
Physical access
Unauthorized personnel may potentially cause significant damage to and/or
misconfiguration of end users’ equipment. This could be intentional or
unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental
to protecting your system. Restrict physical access by unauthorized personnel
to protect end users’ assets. This is true for all systems used within the
facility.
WARNING
Explosions
Explosions could result in death or serious injury.
Installation of the transmitters in a hazardous environment must be in
accordance with the appropriate local, national, and international standards,
codes, and practices. Please review the Product Certifications section for any
restrictions associated with a safe installation.
Do not remove the connection head cover in explosive atmospheres when the
circuit is live.
Before connecting a handheld communicator in an explosive atmosphere, ensure
the instruments are installed in accordance with intrinsically safe or non-
incendive field wiring practices.Verify the operating atmosphere of the
transmitter is consistent with the appropriate hazardous locations
certifications.
All connection head covers must be fully engaged to meet explosion-proof
requirements.
Process leaks
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock
Electrical shock could cause death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
CAUTION
Conduit/cable entries
Unless otherwise marked, the conduit/cable entries in the housing enclosure
use a ½–14 NPT form. Only use plugs, adapters, glands, or conduit with a
compatible thread form when closing these entries. Entries marked “M20” are
M20 x 1.5 thread form.
When installing in a hazardous location, use only appropriately listed or Ex
certified plugs, glands, or adapters in cable/conduit entries.
System readiness
Confirm HART revision capability
If using HART®-based control or asset management systems, confirm the HART
capability of those systems prior to transmitter installation. Not all systems
are capable of communicating with HART Revision 7 protocol. This transmitter
is a HART Revision 7 device.
Confirm the correct device driver
- Verify the latest Device Driver files are loaded on your systems to ensure proper communications.
- Download the latest Device Driver at Emerson.com/Rosemount.
Transmitter installation
Safety messages
Instructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol. Please
refer to the following safety messages before performing an operation preceded
by this symbol.
WARNING
Failure to follow these installation guidelines could result in death or
serious injury.
Ensure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the housing covers in explosive atmospheres when the circuit
is live.
Before connecting a handheld communicator in an explosive atmosphere, ensure
the instruments are installed in accordance with intrinsically safe or non-
incendive field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet explosion-proof
requirements.
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or serious injury.
Use extreme caution when making contact with the leads and terminals.
Connections
Single input
- When using thermocouple input, the transmitter can be configured for either constant, internal or external CJC via a Pt100 or Ni100 sensor. This must be selected during device configuration.
Dual inputs
- A. 2 w / 3 w / 4 w RTD or lin. R
- B. TC (internal CJC or external 2 w / 3 w / 4 w CJC)(1)
- C. mV
- D. 3 w / 4 w potentiometer
- E. 5 w potentiometer
- F. 3 w potentiometer
When using thermocouple input, the transmitter can be configured for either constant, internal or external CJC via a Pt100 or Ni100 sensor. This must be selected during device configuration.
Output
2-wire installation
Multidrop mode
The communication is either by means of a HART® communicator or a HART modem.
The HART communicator or a HART modem can be connected across BC or CD.
The outputs of maximum 63 transmitters can be connected in parallel for a
digital HART 2-wire communication.
Before it is connected, each transmitter must be configured with a unique
number from 1 to 63. If two transmitters are configured with the same number,
both will be excluded. The transmitters must be programmed for multidrop mode
(with a fixed output signal of 4 mA). Maximum current in the loop is therefore
252 mA.
- A. Power supply
- B. Connection
- C. Connection
- D. Connection
- E. 250 Ω < Rload < 1100 Ω
- F. Transmitter
Configuration
Safety messages
Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol. Please refer to the following safety messages before performing an operation preceded by this symbol.
WARNING
Failure to follow these installation guidelines could result in death or
serious injury.
Ensure only qualified personnel perform the installation.
Explosions could result in death or serious injury.
Do not remove the housing covers in explosive atmospheres when the circuit
is live.
Before connecting a handheld communicator in an explosive atmosphere, ensure
the instruments are installed in accordance with intrinsically safe or non-
incendive field wiring practices.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
All connection head covers must be fully engaged to meet explosion-proof
requirements.
Process leaks could result in death or serious injury.
Do not remove the thermowell while in operation.
Install and tighten thermowells and sensors before applying pressure.
Electrical shock could cause death or seriou s injury.
Use extreme caution when making contact with the leads and terminals.
Configuration methods
The device can be configured in the following ways:
- With a HART® communicator with Emerson’s DDL driver
- Via programming framework (e.g. AMS Device Manager, DCS, PACTware™)
HART communicator
To get access to product-specific commands, the HART communicator must be loaded with Emerson’s DDL driver. This can be ordered through either the FieldComm Group or Emerson.
- A. Rosemount transmitter
- B. Ex area
- C. Safe area
- D. 250 Ω < Rload < 1100 Ω
- E. Receiving equipment
- F. +V supply
- G. Input
Programming framework
Support for both EDD and FDT®/DTM™ technology, offering configuration and
monitoring via relevant DCS/Asset Management Systems and supported management
packages (e.g. PACTware).
- A. Rosemount transmitter
- B. 250 Ω < Rload < 1100 Ω
- C. Process computer
- D. DCS, etc.
Mount the transmitter
Rail mount transmitter with remote mount sensor
The least complicated assembly uses:
- a remote-mounted transmitter
- an integral mount sensor with terminal block
- an integral style connection head
- a standard extension
- a threaded thermowell
Refer to the Metric Sensor Product Data Sheet for complete sensor and mounting accessory information.
Assemble the device
To complete the assembly:
Procedure
- Attach the transmitter to a suitable rail or panel.
- Attach the thermowell to the pipe or process container wall. Install and tighten the thermowell before applying pressure.
- Attach the sensor to the connection head and mount the entire assembly to the thermowell.
- Attach sufficient lengths of sensor lead wire to the sensor terminal block.
- Attach and tighten the connection head cover. Enclosure covers must be fully engaged to meet explosion-proof requirements.
- Run sensor lead wires from the sensor assembly to the transmitter.
- Attach the sensor and power leads to the transmitter. Avoid contact with leads and terminals.
Rail mount transmitter with threaded sensor
The least complicated assembly uses:
- a threaded sensor with flying heads
- a threaded sensor connection head
- a union and nipple extension assembly
- a threaded thermowell
Refer to Rosemount Metric Sensor Product Data Sheet for complete sensor and mounting accessory information.Refer to Rosemount Metric Sensor Product Data Sheet for complete sensor and mounting accessory information.
Assemble the device
To complete the assembly:
Procedure
- Attach the transmitter to a suitable rail or panel.
- Attach the thermowell to the pipe or process container wall. Install and tighten the thermowell before applying pressure.
- Attach necessary extension nipples and adapters. Seal the nipple and adapter threads with silicone tape.
- Twist the sensor into the thermowell. Install drain seals if required for severe environments or to satisfy code requirements.
- Screw the connection head to the sensor.
- Attach the sensor lead wires to the connection head terminals.
- Attach additional sensor lead wires from the connection head to the transmitter.
- Attach and tighten the connection head cover. Enclosure covers must be fully engaged to meet explosion-proof requirements.
- Attach the sensor and power leads to the transmitter. Avoid contact with leads and terminals.
Safety instrumented systems
For Safety Certified installations, refer to the Rosemount 644R Reference Manual. The manual is available electronically at Emerson.com/Rosemount or by contacting an Emerson representative.
Product certifications
Rev: 1.1
European Directive information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
Ordinary location certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
Installing equipment in North America
The US National Electrical Code® (NEC) and the Canadian Electrical Code
(CEC) permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly
defined in the respective codes.
USA
I5 USA Intrinsically Safe (IS) and Division 2/Zone 2
- Certificate 80072530
- Standards UL Std No 913 Ed. 8, UL 60079-0 Ed. 5, UL 60079-11 Ed. 6, UL 60079-15 Ed. 4, UL 61010-1 Ed. 3
- Markings Class I, Division 1, Groups A, B, C, D
Class I, Zone 0: AEx ia IIC T6…T4
Class I, Zone 1: AEx ib [ia] IIC T6…T4
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2: AEx nA IIC T6…T4
Class I, Zone 2: AEx nA [ic] IIC T6…T4
when installed per Control Drawing 00644-8000
Table 7-1: IS Input Parameters vs Temperature Range
Input parameters (Terminals 11, 12)| Temperature range| Input parameters
(Terminals 11, 12)| Temperature range
---|---|---|---
Ui: 30 VDC| T4: -50 °C ≤ Ta ≤
+85 °C
| Ui: 30 VDC| T4: -50 °C ≤ Ta ≤
+85 °C
Table 7-1: IS Input Parameters vs Temperature Range (continued)
Input parameters (Terminals 11, 12)| Temperature range| Input parameters
(Terminals 11, 12)| Temperature range
---|---|---|---
Ii: 120 mA| T5: -50 °C ≤ Ta ≤
+70 °C
| Ii: 100 mA| T5: -50 °C ≤ Ta ≤
+75 °C
Pi: 900 mW| T6: -50 °C ≤ Ta ≤
+55 °C
| Pi: 750 mW| T6: -50 °C ≤ Ta ≤
+60 °C
Li: 0 uH| N/A| Li: 0 uH| N/A
Ci: 1.0 nF| N/A| Ci: 1.0 nF| N/A
Table 7-2: IS Output Parameters per Terminal Configuration
Parameters| One sensor using all output terminals (41-54)| Sensor using one set of output terminals (41-44
or 51-54)
---|---|---
Uo| 7.2 VDC| 7.2 VDC
Io| 12.9 mA| 7.3 mA
Po| 23.3 mW| 13.2 mW
Lo| 200 mH| 667 mH
Co| 13.5 uF| 13.5 uF
Table 7-3: Division 2/Zone 2 Input Parameters vs Temperature Range
Supply voltage | Temperature range |
---|---|
37 VDC max | T4: -50 °C ≤ Ta ≤ +85 °C T5: -50 °C ≤ Ta ≤ +70 °C T6: -50 °C ≤ Ta |
≤ +55 °C
30 VDC max| T4: -50 °C ≤ Ta ≤ +85 °C T5: -50 °C ≤ Ta ≤ +75 °C T6: -50 °C ≤ Ta
≤ +60 °C
NIFW
Vmax = 30 VDC, Ci = 1 nF, Li = 0
| T4: -50 °C ≤ Ta ≤ +85 °C T5: -50 °C ≤ Ta ≤ +75 °C T6: -50 °C ≤ Ta ≤ +60 °C
Special Conditions for Safe Use (X):
- Install per Installation Drawing 00644-8000 as appropriate.
- Install in accordance with the US National Electrical Code (NEC) for the US and in accordance with the Canadian Electrical Code (CEC) for Canada.
- The transmitter must be installed in suitable enclosure to meet installation codes stipulated in the Canadian Electrical Code (CEC) or for the US the National Electrical Code (NEC).
- If the enclosure is made of non-metallic materials or of painted metal, electrostatic charging shall be avoided.
- For Div 2/Zone 2 applications, the transmitter must be installed in an enclosure providing a degree of protection of at least IP54 according to IEC60529 that is suitable for the application and is correctly installed. Cable entry devices and blanking elements shall fulfil the same requirements.
- Use supply wires with a rating of at least 5 K above the ambient temperature.
- For Div 2/Zone 2 applications, the temperature transmitter requires connecting to Class 2 Power Supply with Transient protection. See installation drawing as appropriate.
Canada
I6 Canada Intrinsically Safe (IS) and Division 2/Zone 2
-
Certificate: 80072530
-
Standards: CSA C22.2 No. 157-92 (R2012), CAN/CSA C22.2 No.
60079-0:11, CAN/CSA C22.2 No. 60079-11:11, CAN/CSA C22.2 No. 60079-15:12, CSA 61010-1-12 -
Markings: Class I, Division 1, Groups A, B, C, DEx ia IIC T6…T4
Ex ib [ia] IIC T6…T4
Class I, Division 2, Groups A, B, C, D
Ex nA IIC T6…T4
Ex nA [ic] IIC T6…T4
when installed per Control Drawing 00644-8000
Table 7-4: IS Input Parameters vs Temperature Range
Input parameters (Terminals 11, 12)| Temperature range| Input parameters
(Terminals 11, 12)| Temperature range
---|---|---|---
Ui: 30 VDC| T4: -50 °C ≤ Ta ≤
+85 °C
| Ui: 30 VDC| T4: -50 °C ≤ Ta ≤
+85 °C
Ii: 120 mA| T5: -50 °C ≤ Ta ≤
+70 °C
| Ii: 100 mA| T5: -50 °C ≤ Ta ≤
+75 °C
Pi: 900 mW| T6: -50 °C ≤ Ta ≤
+55 °C
| Pi: 750 mW| T6: -50 °C ≤ Ta ≤
+60 °C
Input parameters (Terminals 11, 12)| Temperature range| Input parameters
(Terminals 11, 12)| Temperature range
---|---|---|---
Li: 0 uH| N/A| Li: 0 uH| N/A
Ci: 1.0 nF| N/A| Ci: 1.0 nF| N/A
Table 7-5: IS Output Parameters per Terminal Configuration
Parameters| One sensor using all output terminals (41-54)| Sensor using one set of output terminals (41-44
or 51-54)
---|---|---
Uo| 7.2 VDC| 7.2 VDC
Io| 12.9 mA| 7.3 mA
Po| 23.3 mW| 13.2 mW
Lo| 200 mH| 667 mH
Co| 13.5 uF| 13.5 uF
Table 7-6: Division 2/Zone 2 Input Parameters vs Temperature Range
Supply voltage | Temperature range |
---|---|
37 VDC max | T4: -50 °C ≤ Ta ≤ +85 °C T5: -50 °C ≤ Ta ≤ +70 °C T6: -50 °C ≤ Ta |
≤ +55 °C
30 VDC max| T4: -50 °C ≤ Ta ≤ +85 °C T5: -50 °C ≤ Ta ≤ +75 °C T6: -50 °C ≤ Ta
≤ +60 °C
NIFW
Vmax = 30 VDC, Ci = 1 nF, Li = 0
| T4: -50 °C ≤ Ta ≤ +85 °C T5: -50 °C ≤ Ta ≤ +75 °C T6: -50 °C ≤ Ta ≤ +60 °C
Special Conditions for Safe Use (X):
- Install per Installation Drawing 00644-8000 as appropriate.
- Install in accordance with the US National Electrical Code (NEC) for the US and in accordance with the Canadian Electrical Code (CEC) for Canada.
- The transmitter must be installed in suitable enclosure to meet installation codes stipulated in the Canadian Electrical Code (CEC) or for the US the National Electrical Code (NEC).
- If the enclosure is made of non-metallic materials or of painted metal, electrostatic charging shall be avoided.
- For Div 2/Zone 2 applications, the transmitter must be installed in an enclosure providing a degree of protection of at least IP54 according to IEC60529 that is suitable for the application and is correctly installed. Cable entry devices and blanking elements shall fulfil the same requirements.
- Use supply wires with a rating of at least 5 K above the ambient temperature.
- For Div 2/Zone 2 applications, the temperature transmitter requires connecting to Class 2 Power Supply with Transient protection. See installation drawing as appropriate.
Europe
I1 ATEX Intrinsic Safety
- Certificate: DEKRA 21ATEX0003X
- Standards: EN60079-0:2012+A11:2013, EN60079-11: 2012
- Markings: II 1 G Ex ia IIC T6…T4 Ga
II 2(1) G Ex ib [ia Ga] IIC T6…T4 Gb
II 1 D Ex ia IIIC Da
I 1 M Ex ia I Ma
when installed per Control Drawing 00644-8001
Input parameters (Power terminals) | Output parameters (Sensor terminals) |
---|---|
Ui: 30 Vdc | Uo: 7.2 Vdc |
Ii: 120 mA | Io: 7.3 mA |
Pi: See table below | Po: 13.2 mW |
Li: 0 uH | Lo: 667 mH |
Ci: 1.0 nF | Co: 13.5 uF |
Pi per Channel | Temperature class |
--- | --- |
900 mW | T6 |
T5 | +65 °C |
T4 | +85 °C |
750 mW | T6 |
Pi per Channel | Temperature class |
--- | --- |
T5 | |
T4 | +85 °C |
610 mW | T6 |
T5 | +75 °C |
T4 | +85 °C |
Special Conditions for Safe Use (X):
- For all potentially explosive atmospheres, if the enclosure is made of non-metallic materials, or if it is made of metal having a paint layer thicker than 0.2 mm (group IIC), or 2 mm (group IIB, IIA, I), or any thickness (group III), electrostatic charges shall be avoided.
- For EPL Ga, if the enclosure is made of aluminum, it must be installed such that ignition sources due to impact and friction sparks are excluded.
- For EPL Da, the surface temperature “T” of the enclosure, for a dust layer with a maximum thickness of 5 mm, is the ambient temperature +20 K.
N1 ATEX Zone 2
-
Certificate: DEKRA 21ATEX0004X
-
Standards: EN60079-0:2012+A11:2013, EN60079-7:2015+A1:2018,
EN60079-11:2012, EN60079-15:2010 -
Markings: II 3 G Ex nA IIC T6…T4 Gc
II 3 G Ex ec IIC T6…T4 Gc
II 3 G Ex ic IIC T6…T4 Gc
II 3 D Ex ic IIIC Dc
when installed per Control Drawing 00644-8001
Supply/input to transmitter | Temperature class | Maximum ambient temperature |
---|---|---|
Ex nA & Ex ec | Ex ic |
Li = 0 µH Ci = 1.0 nF
| Ex ic
Ui = 48 VDC
Li = 0 µH Ci = 1.0 nF
| Single and dual input
Vmax = 37 VDC| Ui = 37 VDC| Pi = 851 mW
per channel
| T4| +85 °C
T5| +70 °C
T6| +55 °C
Vmax = 30 VDC| Ui = 30 VDC| Pi = 700 mW
per channel
| T4| +85 °C
T5| +75 °C
T6| +60 °C
Table 7-7: Maximum Output of Transmitter
Ex nA & Ex ec | Ex ic |
---|---|
Vmax = 7.2 VDC | Uo = 7.2 VDC Io = 7.3 mA Po = 13.2 mW Lo = 667 mH Co = 13.5 |
µF
Special Conditions for Safe Use (X):
- For all potentially explosive atmospheres, if the enclosure is made of non-metallic materials, or if it is made of metal having a paint layer thicker than 0.2mm (group IIC), or 2mm (group IIB, IIA, I), or any thickness (group III), electrostatic charges shall be avoided.
- The transmitter shall be installed in an enclosure providing a degree of protection of not less than IP54 in accordance with EN 60079-0, which is suitable for the application and correctly installed, e.g. in an enclosure that is in type of protection Ex n or Ex e.
- Additional, for Ex nA or Ex ec, the area inside the enclosure shall be pollution degree 2 or better, as defined in EN 60664-1.
- For EPL Dc, the surface temperature “T” of the enclosure, for a dust layer with a maximum thickness of 5mm, is the ambient temperature + 20K.
International
I7 IECEx Intrinsic Safety
- Certificate IECEx DEK 21.0002X
- Standards IEC 60079-0:2011, IEC 60079-11:2011
- Markings Ex ia IIC T6…T4 Ga
Ex ib [ia Ga] IIC T6…T4 Gb
Ex ia IIIC Da
Ex ia I Ma
when installed per Control Drawing 00644-8002
Input parameters (Power terminals) | Output parameters (Sensor terminals) |
---|---|
Ui: 30 VDC | Uo: 7.2 VDC |
Ii: 120 mA | Io: 7.3 mA |
Pi: See table below | Po: 13.2 mW |
Li: 0 uH | Lo: 667 mH |
Ci: 1.0 nF | Co: 13.5 uF |
Pi per channel | Temperature class |
--- | --- |
900 mW | T6 |
T5 | +65 °C |
T4 | +85 °C |
750 mW | T6 |
T5 | +70 °C |
T4 | +85 °C |
610 mW | T6 |
T5 | +75 °C |
T4 | +85 °C |
Special Conditions for Safe Use (X):
- For all potentially explosive atmospheres, if the enclosure is made of non-metallic materials, or if it is made of metal having a paint layer thicker than 0.2 mm (group IIC), or 2 mm (group IIB, IIA, I), or any thickness (group III), electrostatic charges shall be avoided.
- For EPL Ga, if the enclosure is made of aluminum, it must be installed such that ignition sources due to impact and friction sparks are excluded.
- For EPL Da, the surface temperature “T” of the enclosure, for a dust layer with a maximum thickness of 5 mm, is the ambient temperature +20 K.
N7 IECEx Zone 2
-
Certificate: IECEx DEK 21.0002X
-
Standards: IEC 60079-0:2011, IEC 60079-7:2017, IEC 60079-11:2011,
IEC 60079-15:2010 -
Markings: Ex nA IIC T6…T4 Gc
Ex ec IIC T6…T4 Gc
Ex ic IIC T6…T4 Gc
Ex ic IIIC Dc
when installed per Control Drawing 00644-8002
Supply/input to transmitter | Temperature class | Maximum ambient temperature |
---|---|---|
Ex nA & Ex ec | Ex ic |
Li = 0 µH Ci = 1.0 nF
| Ex ic
Ui = 48 VDC
Li = 0 µH Ci = 1.0 nF
| Single and dual input
Vmax = 37 VDC| Ui = 37 VDC| Pi = 851 mW
per channel
| T4| +85 °C
T5| +70 °C
T6| +55 °C
Vmax = 30 VDC| Ui = 30 VDC| Pi = 700 mW
per channel
| T4| +85 °C
T5| +75 °C
T6| +60 °C
Table 7-8: Maximum Output of Transmitter
Ex nA & Ex ec | Ex ic |
---|---|
Vmax = 7.2 VDC | Uo = 7.2 VDC Io = 7.3 mA Po = 13.2 mW Lo = 667 mH Co = 13.5 |
µF
Special Conditions for Safe Use (X):
- For all potentially explosive atmospheres, if the enclosure is made of non-metallic materials, or if it is made of metal having a paint layer thicker than 0.2mm (group IIC), or 2mm (group IIB, IIA, I), or any thickness (group III), electrostatic charges shall be avoided.
- The transmitter shall be installed in an enclosure providing a degree of protection of not less than IP54 in accordance with EN 60079-0, which is suitable for the application and correctly installed, e.g. in an enclosure that is in type of protection Ex n or Ex e.
- Additional, for Ex nA or Ex ec, the area inside the enclosure shall be pollution degree 2 or better, as defined in EN 60664-1.
- For EPL Dc, the surface temperature “T” of the enclosure, for a dust layer with a maximum thickness of 5mm, is the ambient temperature + 20K.
China
I3 China (NEPSI) Intrinsic Safety
-
Certificate GYJ21.1036X
-
Standards GB3836.1-2010, GB3836.4-2010, GB3836.20-2010,
GB12476.1-2013, GB12476.4-2010 -
Markings Ex ia IIC T4/T5/T6 Ga
Ex ib [ia Ga] IIC T4/T5/T6 Gb
Ex iaD 20 T80 °C/T95 °C/T130 °C
Ex ibD [iaD 20]21 T80 °C/T95 °C/T130 °C
Special Condition for Safe Use (X):
See certificate for special conditions.
N3 China (NEPSI) Zone 2
Certificate GYJ21.1036X
- Standards GB3836.1-2010, GB3836.4-2010, GB3836.8-2014, GB3836.20-2010
- Markings Ex nA [ic Gc] IIC T6…T4 Gc Ex ic IIC T6…T4 Gc
Special Condition for Safe Use (X):
See certificate for special conditions.
For more information: Emerson.com
©2022 Emerson. All rights reserved.
Emerson Terms and Conditions of Sale are available upon request. The Emerson
logo is a trademark and service mark of Emerson Electric Co. Rosemount is a
mark of one of the Emerson family of companies. All other marks are the
property of their respective owners.
References
- Emerson Global | Emerson
- Rosemount | Emerson US
- Rosemount | Emerson US
- Rosemount | Emerson US
- Software & Drivers Page | Emerson US
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>