EMERSON Enardo 2100 Emergency Pressure Relief Vent and Manhole Cover Instruction Manual
- June 4, 2024
- Emerson
Table of Contents
EMERSON Enardo 2100 Emergency Pressure Relief Vent and Manhole Cover
Failure to follow these instructions or to properly install and maintain this
equipment could result in an explosion, fire and/or chemical contamination
causing property damage and personal injury or death.
FisherTM emergency pressure relief vent must be installed, operated and
maintained in accordance with federal, state and local codes, rules and
regulations and Emerson Process Management Regulator Technologies Tulsa, LLC
instructions.
Failure to correct trouble could result in a hazardous condition. Call a
qualified service person to service the unit. Installation, operation and
maintenance procedures performed by unqualified person may result in improper
adjustment and unsafe operation. Either condition may result in equipment
damage or personal injury. Only a qualified person shall install or service
the emergency pressure relief vent.
Introduction
Scope of the Manual
This Instruction Manual provides instructions for installation, maintenance and parts ordering information for the Enardo 2100 Series Emergency Pressure Relief Vent.
Product Description
The Enardo 2100 Series Emergency Pressure Relief Vent is designed to provide simple, reliable operation as an emergency vent, while providing efficient access to your tank and maintaining the industry leading sealing standards (1 SCFH at 90% set point). It also provides trouble free operation with a minimum maintenance. There are two available configurations for Enardo 2100 Series: tethered and restrained (see Figure 3).
Specifications
The Specifications section lists the specifications for the Enardo 2100 Series. The following information are stamped on the nameplate attached to the relief vent: model number, connection size, date of manufacture, serial number, pressure setting and flow rate.
Connection Sizes Available
16, 20 and 24 in. / 387, 489 and 591 mm
Pressure Ranges(1)
0.7 to 8.0 oz./sq. in. and 1.2 to 14.0 in. w.c.
Construction Materials
Base: Carbon steel, 304 Stainless steel and 316 Stainless steel Lid and Seal
Support: Aluminum, 304 Stainless steel and 316 Stainless steel
Construction Materials (continued)
Seal: Buna-N, FEP Teflon® and Viton®
Certification
EN IEC 60079-0:2018
EN IEC 60079-11:2012
EN ISO 80079-36:2016
EN ISO 80079-37:2016
1, The pressure limits in this Instruction Manual and any applicable standard
or code limitation should not be exceeded.
Product Identification and Marking
Hazardous Locations
FisherTM Emergency Pressure Relief Vents are available with outer housings of
Carbon steel, stainless steel or aluminum, as indicated in Figure 5.
Tagging Information
The nameplate is located on the unit’s base, above the connection flange (see
Figure 5).
Nameplate Information
A nameplate is attached to the vent and contains the following information: ·
-
Model Number Ex. 2124-24T-1
-
Connection Flange Size 24 in. / 610 mm
-
Serial Number
-
Tag Number (Optional)
-
Notified Body Number Ex. 2460
-
Cat. No. (Category Number)
– Category 1 Stainless steel, Carbon steel or Coated Aluminum vents
– Category 2 Uncoated Aluminum vent -
Date Date of Manufacture
-
Certificate Ex. PRESAFE 17 ATEX 10273X
-
Pressure Setting and Flow Rate
– Setting Ex. Z4.0 – Flow Rate SCFH (Air) Ex. 00000
Wear protective gloves and clothing to prevent skin contact when handling lead weights. Wear eye protection. Avoid breathing dust, fumes, mist, vapors and spray. Do not eat, drink or smoke while using the product. Avoid release to the environment. Wash hands with soap and water after handling. Keep away from excessive heat and open flames.
Make sure line is free of hazardous vapors before installing or servicing the valve.
Principle of Operation
The Enardo 2100 Series maintains a tight seal until system pressure exceeds
the set pressure of the vent. To adjust the set pressure, a series of weights
may be stacked onto the lid assembly. When excessive overpressure occurs the
weighted lid assembly lifts, breaking the seal between the seat and seal
portion of the lid assembly. This allows vapors to pass through the vent
orifice and relieve pressure buildup. The vent reseals upon relief and remains
sealed; tethered lids may blow completely off in a catastrophic pressure event
(see Figure 4).
It is important to know that relieving vapors near the set pressure in a
continuous manner may cause the lid assembly to flutter or oscillate. This is
a common occurrence in products of this type in the industry. Operating the
vent with flutter or oscillation over time may cause premature vent damage or
wear. Please feel free to contact your local Sales Office with any questions
or for information on proper tank venting.
Installation
The Enardo 2100 Series is shipped with its lid held partially open. The lid
assembly has attached weights and is heavy. Use caution when removing the
shipping blocks and metal bands to avoid injury to fingers and hands.
Prior to installation, remove the unit from its crate and discard any
protective coverings. Follow the recommended instructions for the installation
of the Enardo 2100 Series.
- Carefully remove the Enardo 2100 Series from its crating.
Note
The seal portion of the vent can be damaged through improper handling, protect this surface with a padding material while transporting the unit if possible.
Failure to use spreader bar in lifting the unit may result in personal
injury, damage to the unit and damage to the equipment.
There should be no tension on the lanyards if the unit is to be hoisted in
position, failure to do so may result in damage to the unit.
- Use an appropriate spreader bar when lifting the unit by the installed eyebolts. If the complete unit is to be hoisted into position using installed eyebolts, first secure the base to the lid so that there is no tension on the lanyards. Lanyards are load-rated to 350 lbs / 160 kg each; damage to other components may occur.
- Install the Enardo 2100 Series on flange bolt patterns that match that of the vent itself. If a matching pattern is not available, please contact your local Sales Office for an adapter. The attachment flange base must be a level surface. Use an appropriate gasket placed between the Enardo 2100 Series flange and the attachment flange, center the vent into place.
- Insert the appropriate number of bolts and make sure the vent is fastened securely. Installed bolts should be clear of the lid assembly when it is in the full open position. Remove any spacer or seal protection and inspect the now installed unit for items that would keep it from working properly. The sealing area should be free of any debris or damage that would cause leakage.
Startup
Ensure the tank is at atmospheric pressure before opening. A pressure
buildup inside the tank can cause a spray to be emitted from the vent if
opened under pressure.
Tethered Configuration
-
Grip lid firmly and lift straight up until the bottom of guide assembly clears the base.
Note
Be careful to keep the guide from denting or scratching the sealing surface as this can cause leaks.
-
Move the lid away from the opening and set it down on the guide assembly. The guide assembly is designed to hold the cover assembly even at the maximum 8 oz./sq. in. setting.b
Restrained Configuration
-
Remove the nylock nut and outer fender washer. The loop slides off the lanyard attachment assembly.
-
Grip lid firmly and lift straight up until the bottom of guide assembly clears the base or attach shackles to the eyebolts and use a crane or hoist to lift.
Note
Be careful to keep the guide from denting or scratching the sealing surface as this can cause leaks.
-
Move the lid away from the opening set it down.
The guide assembly is designed to hold the cover assembly even at the maximum 8 oz./sq. in. setting.
Maintenance
Sealing Surface Protector
The sealing surface protector must be removed before the Enardo 2100 Series is returned to service. The vent will not seal with the protector in place.
The following instructions are applicable only if the sealing surface
protector was also purchased for your unit. This guard is available to prevent
damage to the sealing surface when the Enardo 2100 Series is being used for
tank access or for running air or weld leads into the tank. Figure 10. Surface
Protector Installation Figure 11. Surface Protector Cross Section
Remove the sealing surface protector from its bag.
Place one end of the protector over the machined surface with the legs
pointing down and the flat side up. Firmly press the protector over the
sealing surface. Move around the sealing surface making sure the protector is
snugly attached.
Seal Replacement Procedure
Tools and Supplies Needed:
- 2 standard 7/16 in. wrenches
- Torque wrench (recommended)
- 1 screwdriver, any type (for eyebolt units only)
- Adhesive tape (recommended for eyebolt units)
- Enardo 2100 Series seal
- 4-1/4 in. stat-o-seals (recommended)
Replacement Procedure:
Ensure the tank is at atmospheric pressure before opening. A pressure buildup inside the tank can cause a spray to be emitted from the vent if opened under pressure.
-
Remove the Nylock nut and outer fender washer.
The loop slides off the lanyard attachment assembly. Remove the lid assembly from the base and place on a level surface.
-
Loosen the 4 hex nuts on the bottom of the lid assembly. If the unit is equipped with eyebolts, insert the screwdriver through the eye to provide leverage.
-
If the unit is equipped with eyebolts, place a piece of adhesive tape over the hex bolt heads to prevent them from falling out. This is not required, but makes seal replacement much easier.
-
Flip the lid assembly over so that the guide assembly is facing up.
-
Remove the hex nuts, washers, guide assembly, stat-o-seals, seal support and seal. Take note of the order in which the components are removed.
-
Discard seal. If replacement stat-o-seals were ordered, discard old stat-o-seals.
-
Reassemble the lower lid components in the reverse order of disassembly.
-
Before tightening hex nuts, ensure that the eyelet on the lanyard(s) is pointing away from the center of the lid. Failure to do this may result in damage to the tank by preventing the unit from opening fully in a pressure event. Tighten each nut to 1 turn after snug.
-
Flip the lid assembly over so that the guide assembly is facing down. Reinsert the lid into the base and reattach the lanyard(s). Do not tighten the hex nut and the nylock nut greater than 12 ft•lbf.
Parts Ordering
When corresponding with your local Sales Office about this equipment, always reference the equipment serial number stamped on the nameplate.
When ordering replacement parts, specify the complete 11-character part number found in Table 1.
Parts List
Key Description
- Base, Carbon steel, 304 Stainless steel and 316 Stainless steel
- Cover, Aluminum, Zinc-plated Carbon steel, 304 Stainless steel and 316 Stainless steel
- Seal Support, Aluminum, Zinc-plated Carbon steel, 304 Stainless steel and 316 Stainless steel
- Shield, Aluminum, Zinc-plated Carbon steel, 304 Stainless steel and 316 Stainless steel
- Guide, Aluminum, Zinc-plated Carbon steel, 304 Stainless steel and 316 Stainless steel
- Seal, Buna-N, Teflon® and Viton®
- Stat-O-Seal, 1/4 in. Fluorocarbon, Stainless steel and Viton®
- Flat Washer, 1/4 in., 316 Stainless steel
- Fender Washer, 1/4 x 1 in. O.D., 316 Stainless steel
- Lock Washer, 1/4 in., 316 Stainless steel
- Hex Bolt, 1/4 in. – 20 x 3 in., 316 Stainless steel
- Hex Bolt, 1/4 in. – 20 x 2 in., 316 Stainless steel
- Hex Nut, 1/4 in. – 20, 316 Stainless steel
- Eyebolt, 1/4 in. – 20 x 3 in., 316 Stainless steel
- Nylock Hex Nut, 1/4 in. – 20, 316 Stainless steel and Nylon
- Roller, Zinc-plated Carbon steel, 316 Stainless steel
- Weight, “Makes”, Zinc-plated Carbon steel
- Weight, oz./sq. in. or in. w.c., Zinc-plated Carbon steel and 316 Stainless steel
- Lanyard, Tether or Restraint, 316 Stainless steel
Table 1. Enardo 2100 Series Seal Options
MATERIAL
| GASKET AND SEAL OPTIONS
---|---
Part Number
16 in.| 20 in.| 24 in.
Buna-N| NE3043037A0| NE3043040A0| NE3043043A0
Teflon®| NE3043038A0| NE3043041A0| NE3043044A0
Viton®| NE3043039A0| NE3043042A0| NE3043045A0
_ Table 2. _Torque Specifications – Raised Face Flange, Steel Only
NOMINAL PIPE DIAMETER
| NUMBER OF BOLTS| BOLT DIAMETER|
TORQUE
---|---|---|---
in.| mm| ft-lbs| N•m
16| 16| 1.00| 25.4| 159| 216
20| 20| 1.13| 28.7| 214| 290
24| 24| 1.25| 31.8| 253| 343
Assumptions:
Use of SAE grade 5 bolts or studs or stronger. No lubricant.
Compressed mineral fiber material or similar
Notes:
If lubricant is used on bolts, apply torque reduction factor listed in
Lubricant Table.
For best results hardened steel washers should be used on all cast flange
bolted connections.
Teflon® and Viton® are marks owned by E. I. du Pont de Nemours and Co.
Table 3. Torque Specifications – Flat Face Flange, Steel or Aluminum
NOMINAL PIPE DIAMETER
| NUMBER OF BOLTS| BOLT DIAMETER|
TORQUE
---|---|---|---
in.
| mm| ft-lbs| N•m
16| 16| 1.00| 25.4| 125|
170
20
| 20| 1.13| 28.7| 135| 183
24| 24| 1.25| 31.8| 156|
212
20 API
| 16| 0.63| 16.0| 75| 102
24 API| 20| 0.63| 16.0| 75|
102
Assumptions:
Use of SAE grade 5 bolts or studs or stronger. No lubricant.
Elastomer <70 Durometer Shore A.
Notes:
Flat faced flanges should never be mated to a raised face flange for
installation.
If lubricant is used on bolts, apply torque reduction factor listed in
Lubricant Table.
For best results hardened steel washers should be used on all cast flange
bolted connections.
Table 4. Torque Reduction Factor per Lubricant
DESCRIPTION
| COEFFICIENT OF FRICTION| MULTIPLY TORQUE VALUE IN TABLE BY
---|---|---
Machine Oil| f = 0.15|
0.75
API SA2 Grease
| f = 0.12| 0.60
Nickel-based Lubricant| f = 0.11|
0.55
Copper-based Lubricant
| f = 0.10| 0.50
Heavy-duty Lubricating Past| f = 0.06|
0.30
| Webadmin.Regulators@emerson.com
---|---
| Enardo.com
|
Facebook.com/EmersonAutomationSolutions
| LinkedIn.com/company/emerson-automation-
solutions
| Twitter.com/emr_automation
Emerson Automation Solutions
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853 +1 972 548 3574
Tulsa, OK 74146 USA
T +1 918 662 6161
Europe
Bologna 40013, Italy
T +39 051 419 0611
Asia Pacific
Singapore 128461, Singapore
T +65 6770 8337
Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
D103824X012 © 2015, 2021 Emerson Process Management Regulator Technologies,
Inc. All rights reserved. 12/21.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. All other marks are the property of their prospective owners.
Fisher™ is a mark owned by Fisher Controls International LLC, a business of
Emerson Automation Solutions.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Process Management Regulator Technologies Tulsa, LLC does not assume responsibility for the selection, use or maintenance ofany product. Responsibility for proper selection, use and maintenance of any Emerson Process Management Regulator Technologies Tulsa, LLC product remains solely with the purchaser.