TIME MARK B258B 3-Phase Monitor Instruction Manual
- June 5, 2024
- TIME MARK
Table of Contents
TIME MARK B258B 3-Phase Monitor
Specifications
Model| Nominal AC Voltage (Phase to Phase)| Case Color| Adjustment Range|
Frequency| Power Consumption| Transient Protection| Repeat Accuracy| Response
Time| Dead Band| Output Contacts| Expected Relay Life| Operating Temp.|
Humidity Tolerance| Enclosure Material| Mounting| Weight| Agency Approvals
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
258B| 120VAC| Gray| 85-120VAC| 60Hz| 1.4W| 2500VAC for 10ms| –| 50ms drop out|
Approx. 2%| SPDT 10A at 240VAC resistive| Mechanical: 10 million operations,
Electrical: 100,000
operations at rated load| –| 0 – 97% w/o condensation| ABS plastic cover|
8-pin socket (sold separately)| 5 oz.| UL Recognized and CSA Certified
Product Usage Instructions
Description:
The Model 258 3-Phase Monitor is designed to continuously monitor 3-phase power lines for abnormal conditions such as phase loss, low voltage, and phase reversal. It features solid-state voltage and phase-angle sensing circuits driving an electromechanical relay.
Installation Instructions:
WARNING: Potentially hazardous voltages arepresent at the terminals of the Model 258. All electrical power should be removed when connecting or disconnecting wiring. This device should be installed and serviced by qualified personnel.
Installation:
Mount the 8-pin socket in a suitable enclosure. A NEMA-1 rated enclosure designed for socket-mounted relays is available from Time Mark Corporation.
Troubleshooting and Maintenance:
If the monitor detects a fault condition, it will de-energize the relay. Correct the fault, and the monitor will automatically reset. For manual reset versions, follow the manual reset procedure provided in the user manual.
Frequently Asked Questions
Q: What is the warranty period for the Model 258 3-Phase Monitor?
A: The Model 258 comes with a five-year unconditional warranty.
Q: Can the Model 258 be used with both Wye and Delta systems?
A: Yes, the Model 258 does not require a neutral connection and can be used with both Wye and Delta systems.
3-Phase Monitor
- Detects phase loss, low voltage, phase reversal
- 50Hz, 60Hz and 400Hz models
- Automatic or manual reset
- Five year unconditional warranty
DESCRIPTION
The Model 258 continuously monitors 3- phase power lines for abnormal conditions. When properly adjusted, the Model 258 Monitor will detect phase loss on a loaded motor even when regenerated voltage is present. This device consists of a solid-state voltage and phase-angle sensing circuit, driving an electromechanical relay. When correct voltage and phase rotation are applied, the internal relay will energize. A fault condition will de-energize the relay. When the fault is corrected, the monitor will automatically reset (a manual reset version is also available). The Model 258 3-Phase Monitor does not require a neutral connection and can be used with Wye or Delta systems. Voltage ranges are sufficiently wide to allow for proper adjustment to existing conditions. Both “TRIP” and “NORM” condition indicators are provided to aid in adjustment and system troubleshooting.
SPECIFICATIONS
DIMENSIONS
TYPICAL APPLICATION
READ ALL INSTRUCTIONS BEFORE INSTALLING, OPERATING OR SERVICING THIS DEVICE. KEEP THIS DATA SHEET FOR FUTURE REFERENCE.
GENERAL SAFETY
POTENTIALLY HAZARDOUS VOLTAGES ARE PRESENT AT THE TERMINALS OF THE MODEL 258. ALL ELECTRICAL POWER SHOULD BE REMOVED WHEN CONNECTING OR DISCONNECTING WIRING. THIS DEVICE SHOULD BE INSTALLED AND SERVICED BY QUALIFIED PERSONNEL.
Installation Instructions
WARNING
IN APPLICATIONS WHERE VOLTAGES IN EXCESS OF 300VAC ARE TO BE MONITORED, BE CERTAIN TO USE THE TIME MARK MODEL 51X120 8-PIN SOCKET, OR AN EQUIVALENT UL APPROVED 600VAC RATED SOCKET.
INSTALLATION
Mount the 8-pin socket in a suitable enclosure. A NEMA-1 rated enclosure,
designed for socket-mounted relays is available from Time Mark Corporation.
Connect 3-phase power to terminals 3, 4, and 5 on the socket. Phase rotation
should be verified using a Time Mark Model 108A or 108B Phase Sequence
Detector. Connect the load control wiring to the appropriate terminals on the
socket: For motor control applications; use terminals 1 and 8. For phase loss
alarm applications; use terminals 1 and 2. Insert the Model 258 into the
socket and apply power. If the contact does not transfer (green light ON),
check that all phases are present, and of the correct voltage. If power is
correct, rotate the level adjustment counter-clockwise. If the contact still
does not transfer, remove power and reverse any two of the three phase wires
at the socket (phase rotation is reversed). Re-apply power. The contact should
transfer to provide a signal path between pins 1 and 8.
NOTE: When installing the Model 258 monitor in areas of high humidity or
contamination, it is recommended that the base area and all exposed metal
parts of the socket be coated liberally with a good quality silicone grease,
such as Dow Corning DC-4 or DC- 4X. Insert the unit into the socket and wipe
off excess grease around the base. This will prevent the entrance of moisture
and other contaminates into the base and socket areas.
ADJUSTMENT SETTINGS
The following procedure will allow the Model 258 to be adjusted to achieve a trip point just below the nominal phaseto- phase voltage, where the unit is applied. Rotate the adjustment control fully clockwise, or until the red (TRIP) indicator illuminates. Slowly rotate the adjustment control in a counter-clockwise direction, just until the green (NORM) indicator illuminates. At this point, the Model 258 is the most sensitive to irregular power line conditions. If nuisance tripping occurs, turn the control slightly farther counter-clockwise. A more accurate setting will require the use of a 3-phase variac to lower the voltage to an exact measurable setting. Time Mark also offers a factory set version of all models and voltage ranges, for only a small additional charge.
TROUBLESHOOTING
Should the Model 258 Monitor fail to operate properly, check that all three voltages are present, and are of the correct voltage level and phase rotation (a Model 108A or 108B Phase Sequence Detector should be used to verify phase rotation). Check all fuses and verify that all wiring connections are correct. If problems persist, contact your local Time Mark Distributor, or the factory for assistance (Monday-Friday, 8 a.m. to 5 p.m. CST).
MANUAL RESET VERSIONS
IF YOU DO NOT WISH TO USE A NORMALLY CLOSED EXTERNAL RESET SWITCH ON THE MANUAL RESET VERSION, YOU MUST JUMPER PINS 6 AND 7. Refer to the Manual Reset 8-pin diagram.
WARRANTY
This product is warranted to be free from defects in materials and workmanship and is covered by our exclusive 5-year Unconditional Warranty. Should this device fail to operate for any reason, we will repair it for five years from the date of manufacture. For complete warranty details, see the Terms and Conditions of Sales page in the front section of the Time Mark catalog or contact Time Mark at 1-800-862-2875.
Contact
- Telephone: Main – 918-438-1220
- Sales – 800-862-2875
- Fax: 918-437-7584
- E-mail: sales@time-mark.com
- Internet: http://www.time-mark.com
- 11440 East Pine St reet
- Tulsa, Oklahoma 74116
- 2012 TIME MARK CORPORATION
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>