SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
- June 9, 2024
- SMART TEMP
Table of Contents
- SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
- Introduction
- Thermostat operation
- On/Off (Mode)
- Set Temperature
- Fan
- Ventilation Mode
- “Make up Room” & “Do Not Disturb” Buttons
- Installation – HVAC Control
- System Design
- Opening Wall Controller
- Mounting wall Controller
- DIP Switch Settings
- Wiring – HVAC Control Terminal Designations
- 0-10v Outputs
- A1 – Cool
- A2 – Heat
- A3 – Fan
- Span
- Time Interval
- Direction
- Minimum Value
- Maximum Value (Fan A3) output only
- Belimo ™ 6 Way Valve
- 2 Pipe Mode
- Klixon Mode / 2 pipe
- Ancillary Functions
- Complete System Overview
- Occupancy Detection
- DO NOT APPLY EXTERNAL VOLTAGES TO THESE INPUTS
- Fault Indication
- Door Switch
- Entering or exiting the room.
- Door Left Open
- PIR input
- Latched Occupancy Detection Logic
- Using a PIR Only for occupancy Detection
- Manual Occupancy Input
- Doorbell
- Outside Door Station
- Automatic Day Set Temperature
- Modbus Wiring
- Remote Temperature sensors
- Installer Options Menu
- Navigating Through the Installer Mode Settings
- Option List Table
- Modbus Data – Addendum 1
- Data Format
- Specifications
- Read More About This Manual & Download PDF:
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SMART TEMP SMT-131 Hotel Touchscreen Thermostat User Manual
Introduction
The Smart Temp SMT-131 thermostat has been designed for use in hotel rooms,
guest accommodation and locations where the user will require a thermostat
that is simple to use. Further, given the nature of the hospitality industry
in general it is important that the thermostat be robust, flexible in function
and attractive. The SMT-131 thermostat has been designed with these important
goals is mind.
The SMT-131 also offers advanced energy conservation features such as set
point limit control, automatic un-occupied heating and cooling settings as
well as Modbus RTU communications for integration with the “Building
Automation System” (BAS) or “Hotel Check In” system. Additionally, the SMT-131
seamlessly interfaces with the Smart Temp OC-3D occupancy detection system and
HOT-242 “Door Station” system for added functionality.
Thermostat operation
The SMT-131 is an extremely simple thermostat to operate and has been designed
to not require a user manual.
The diagram to the left shows all LCD elements and the 7 buttons (Up / Down /
Make Up Room / Do Not Disturb / On – Off (mode) / Fan Mode / Deg C-F Select.
Depending on switch and installer menu settings not all LCD segments or
buttons maybe shown.
On/Off (Mode)
Tap the On/Off button to turn the thermostat On or Off and if permitted to
select heat only or cool only mode. (To ensure the simplest user operation
on/off only Mode is set as default).
Note – for simplicity – If the thermostat is OFF by simply touching the
thermostat display will turn it on.
Set Temperature
Adjust the target temperature with the Up or Down button. The range of temperature adjustment can be limited with the installer setting “heat and cool limit setting”. ( See page 16) __
Fan
Single fan speed mode (Sw1= Off) (See Dip switch settings page 5)
Tap the fan button to cycle between auto fan and continuous fan mode.
Three fan speed mode (Sw1= On) (See Dip switch settings page 5)
Tap the fan button to cycle between low, medium, high and auto fan speeds.
Press and hold the fan button to turn the fan on continuously.
Note. Option 16 in the installer menu (See page 16) permits you to
set the SMT-131 to automatically reset the indoor fan to Automatic Mode (cycle
on and off with heating and cooling) every time the thermostat is turned off
and then back on if desired.
If Auto Fan mode is selected, then when the heating and cooling stops, so
will the fan (after any purge periods have expired if set- see page 16)
If Fan On mode is selected, then the fan will continue to run after the
heating and cooling stops to maintain ventilation.
Ventilation Mode
If permitted by DIP Sw7, (See page 5) the user can run the indoor fan only (Ventilation Mode) when the SMT-131 is off by tapping the fan button. Each tap of the fan button will cycle between all available fan speeds.
“Make up Room” & “Do Not Disturb” Buttons
When enabled by DIP Sw8, (See page 5) pressing these buttons will activate
relevant LCD segments and backlight colour on the optional outside door
station as well as write data to Modbus for monitoring by a BAS system.
Note – you do not need the outside door stations to be fitted if you simply
wish this data to be presented to Modbus.
Installation – HVAC Control
System Design
Great effort has been taken to make the SMT-131 system intuitive, reliable and easy to install. Using a common-sense approach to the installation will ensure this product is installed easily and to the customer’s satisfaction. Please read and understand this instruction manual so that installation, testing and commissioning process is undertaken in an effective and efficient manner.
Opening Wall Controller
Open the SMT-131 wall controller by placing a flat blade screwdriver or coin
in the slot on the bottom of the thermostat case (1) and
gently twist (2) to release the case locking clip. Gently pry the two case
halves apart at the base taking care not to twist the case as this may crack
the LCD.
Mounting wall Controller
The SMT-131 should be mounted in a convenient location at approximately 1.2 to
1.5 meters from the ground. It should be in a “typical” location where it will
sense the accurate room temperature and not be affected by direct sunlight or
drafts.
It is highly recommended that any penetrations in the wall where wiring may
pass for example be sealed to prevent drafts from entering the rear of the
thermostat and effecting the room temperature sensor accuracy.
Take care to ensure excess wiring is not trapped between the cases half’s when closing – push excess wires into the wall cavity. Never press on the LCD when closing the SMT-131 as it may crack. Always press on the SMT-131 plastic case only
DIP Switch Settings
Switch | Function | On | Off |
---|---|---|---|
Sw1 | Indoor Fan Mode | 3 Fan Speed | 1 Fan Speed |
Sw2 | Equipment Type | Heat Pump | Heat Cool |
Sw3 | HP Mode (Sw2= ON) HC Mode (Sw2=OFF) | Rev Valve Heat (B) HE – Fan With | |
Heat | Rev Valve Cool (O) HG – No Fan In Heat | ||
Sw4 | 2 / 4 pipe mode | 2 pipe mode | 4 pipe Mode |
Sw5 | Comp Protection Delay | 5 Min Anti Cycle | Immediate Comp start |
Sw6 | Klixon Mode | On | Off |
Sw7 | Ventilation Mode | Permitted | Not Permitted |
Sw8 | Door Station (Optional) | Fitted | Door Station Not Used |
Note: The SMT-131 reads the switch settings on power up only. If you change
any DIP switch settings you must power cycle before these changes will take
effect.
It is expected that only qualified people will make adjustment to these dip
switch settings. Knowledge of the HVAC system under the control of the SMT-131
is essential prior to making adjustment to these DIP switch settings.
Caution Incorrect adjustment of these DIP switch settings could cause HVAC equipment damage. This would NOT be covered by warranty.
Wiring – HVAC Control Terminal Designations
Terminal | Function |
---|---|
C | 24V Neutral |
R | 24V Active – This voltage is switched back through the relays |
Hi | Indoor Fan High Speed ( NOT Used in Single fan speed mode – Sw 1 = |
OFF)
Med| Indoor Fan Medium Speed ( NOT Used in Single fan speed mode – Sw 1 =
OFF)
Low| Indoor Fan Low Speed (Used in single & three fan speed mode)
Y| Compressor or Cool – (Based on Sw 2 setting)
W – O/B| Reversing Valve or Heat – (Based on Sw 2 setting)
A1 – Cool| 0-10V Output for Cooling (Typically used to control modulating
valves)
A2 – Heat| 0-10V Output for Heating (Typically used to control modulating
valves)
A3 – Fan| 0-10V Modulating Output for Indoor DC Fan
Com – 0V| 0V terminal – Used for 0-10V, sensor or digital inputs ground
reference
A| Modbus Data A
B| Modbus Data B
SI| Remote temperature sensor input (Remote / average / Modbus data use)
DI| Digital (Switched input) for forced un-occupied or initiate doorbell
function
WC| Window Contact – Forces SMT-131 OFF if window open > 5 min (Adjustable)
DS| Door Switch – Monitors room door status for occupancy detection (see
page 11)
PIR| PIR (Movement sensor) input for occupancy detection (see page 11)
The SMT-131 is powered by 24VAC and requires the 24VAC active and neutral to be connected to the “R” (active) and “C” (Neutral) terminals for the SMT-131 to function. The 24VAC applied to the SMT-131 “R” terminal is switch back through the 2A relays to the equipment. Note the drawing provided here
Caution – Although the SMT-131 is a robust device, wiring errors can potentially damage the thermostat. Warranty does NOT cover this damage. Take care when wiring 24V near sensor inputs or the Modbus communications terminals.
Note – When the SMT-131 calls heating or cooling the SMT-131 will drive both the relays and the 0-10V outputs simultaneously. This way the SMT-131 can call a circulating water pump via the relays as it controls room temperature with valves if needed.
0-10v Outputs
To permit the control of modulating heating and cooling valves as well as variable speed DC fan motors or variable capacity HVAC systems the SMT-131 has been fitted with 3 x 0-10V outputs.The 0-10V outputs in the SMT-131 are PI (Proportional Integral) controlled. This control method provides the most accurate and cost-effective way to control heating and cooling valves by ensuring set temperate are reached as quickly and efficiently as possible while reducing temperature overshoot.
As the SMT-131 is fitted with both relays as well as 0-10V outputs to control HVAC systems there may be some slight disparity between the thermostat display and the 0-10V outputs actions. The SMT-131 displays the relay actions more than the actions of the 0-10V outputs on the LCD. In most cases these are very closely matched however as the 0-10v outputs have the capability of providing finer control than do the ON/OFF relays the heating and cooling calls may have started slightly before indicated on the thermostat display. This is true of the fan also.
A1 – Cool
This output is used to control a cooling valve.
A2 – Heat
This output is used to control a heating valve.
A3 – Fan
This output is used to control a variable speed fan or a variable capacity AC
system. If the fan mode is set to
Auto speed the 0-10V output will vary between these two values based on
calculated demand. If the user selects LOW speed, the 0-10V output will be
fixed at 3.3VDC, when Medium speed is selected the 0-10V output will be fixed
at 6.6VDC. High speed is set to 10VDC
The installer menu provides the following settings for the control of the
three 0-10V outputs.
Span
This is the value where the output is at maximum value. It sets how aggressive the 0-10V will move for a given temperature change. Range is 0-5C
Time Interval
Time interval sets the running average calculation time. The smaller the number the faster the 0- 10V output will respond to room temperature changes. Range is 10 – 300 seconds.
Direction
Forward action 0V = 0% open and 10V = 100% open; reverse action sets 0V = 100% open and 10V = 0% open.
Minimum Value
Rather than start the output at 0V, when the output is called it will immediately jump to this value. It will then vary the output to maximum. When approaching set point the value will drop from the minimum value to 0v in 1 step. This setting is particularly useful for fan control as it will not permit the fan to run too slowly when close to set point.
Maximum Value (Fan A3) output only
When controlling 0-10V fans sometimes it is necessary to limit the fan speed
to reduce noise or to protect ducting. The fan output has a high voltage limit
setting so regardless of the user selected speed (High, Medium or Low) or
thermostat selected auto speed the 0-10V output will not exceed this pre-set
high limit.
These settings can be found in the installer menu (starting on page 16)
Belimo ™ 6 Way Valve
Belimo™ manufactures an actuator that is in full cooling at 2V, off at 6V and full heating at 10V. To use this type of actuator with the Smart Temp SMT-131 you must enter the installer menu and set valve type to “Belimo™ Mode”.
The heating 0-10v output only is used in this mode
Information on the installer menu can be found on page 15 of this manual.
As with normal valves, the 0-10V heating and cooling span settings in the
installer menu scale the heating and cooling outputs. Factory default is full
heating and full cooling 1°C from set point. The heating and cooling span can
be adjusted independently to a maximum of full heating and full cooling 3°C
from set point. The output is linear.
Note When using “Belimo” ™ mode, both the A1 “cool” and the A2 “Heat”
0-10 output are used. Both will provide the same output to the value. (The A3
“fan” output will remain unchanged and can be used to control a DC fan or
other devices).
2 Pipe Mode
The SMT-131 can measure water temperature via a sensor strapped to the water pipe and wired into the SMT-131 Sensor input terminals (SI and Com 0-10 input). Based on the pipe temperature, the room temperature and the set point the SMT-131 will control either the heating or the cooling outputs to maintain guest comfort. If the pipe temperature is above 30c, the 131 is in heating mode. If the pipe temperature is below 20c, cooling mode is used. Between 21 and 29 there are no calls. (Version V41.1 firmware and newer the heating and cooling thresholds are adjustable from within Installer Menu. Option 44 will adjust the heating mode threshold (default 30) and option 45 will adjust the cooling mode threshold (default 20).
When 2 pipe is mode is used, the SMT-131 will open the water valve for 30
seconds every 10 minutes to allow water to flow within the pipe so that the
SMT-131 can sample pipe temperature to determine / confirm operation mode.
(Version 41.0 or later firmware will open the valve 25% for 2 minutes every 10
minutes when heating or cooling is required to check if the water temp is
suitable)
If mode selection is permitted, the SMT-131 will only permit the appropriate
mode to be selected based on the pipe temperature.
To use the SMT-131 in 2 pipe mode set DIP 2 OFF and DIP 4 to the ON position.
Set Installer menu option 27 “Si & Com 0-V” to option “3” – 2 Pipe Mode.
(See page 17)
The pipe sensor needed for 2 pipe mode is the RS-1d sensor – available as an optional part from Smart Temp or an authorised distributor.
Klixon Mode / 2 pipe
The SMT-131 Heat and Cool mode can be changed by a remote manual mechanical switch or an automatic Klixon switch if required. ( A klixon switch is a mechanical temperature switch typically placed on a water pipe and use to detect water temperature, therefore selecting the correct thermostat mode based on the temperature of water in a fan coil).
To activate Klixon mode
- Place a Klixon switch (or mechanical switch) between the DI and Com
- Turn On DIP switch 4 (Two pipe Mode = ON).
- Turn On DIP switch 6 ( Klixon mode = ON).
- Enter the installer menu and select option 2 (Klixon Mode) in menu item 29.
The SMT-131 will automatically change Installer Option 1 to function 2 (manual
change over mode). The user will therefore only be permitted to turn the
thermostat On or Off, adjust set temperature and fan modes (if applicable)
By default, heating mode will be selected if the switch is closed, and cooling
mode will be selected if the switch is open. Should you wish to reverse this
input logic adjust Installer Option number 40.
Ancillary Functions
The SMT-131 has several additional capabilities such as communications with
Building Automation systems via its Modbus communications port. The SMT-131
will automatically control temperature set points based on occupancy of the
room when a suitable door switch and movement sensor is fitted. The SMT-131
can even automatically shut down the air conditioning system if balcony doors
or windows are left open when the optional door / window switch are fitted.
When you wish indication of the room status and an integrated doorbell from
the hall way outside the room, the SMT-131 can be fitted with the optional
“HOT-243” hall panel.
Complete System Overview
The SMT-131 is the hub of a compressive room comfort and energy control
system. As shown in the picture the SMT-131 accepts door, window and PIR
contact inputs to automatically control temperature set points. The HOT 243
wall controller mounted in the hallway outside of the room provides feedback
of the guests needs to housekeeping plus provides a convenient button to
activate the SMT-131 internal door bell.
Regardless of the need to control conferential HVAC systems, 2 or 4 pipe fan
coils with modulating valves the SMT-131 has the necessary outputs to achieve
your control needs.
Occupancy Detection
The SMT-131 has sophisticated logic that when connected to your choice of
movement sensors, door and window switches will automatically control the set
point and mode of the SMT-131.
Using part or all the functions described below are completely optional. The
SMT-131 will function
perfectly as a HVAC controller without the door, window or occupancy detection
logic enabled.
There are two types of occupancy detection modes provided by the SMT-131, see
latched occupancy detection on page 11 or PIR only occupancy detection on page
12 of this manual.
DO NOT APPLY EXTERNAL VOLTAGES TO THESE INPUTS
**Window Contact**
The window contact input (WC) is used to automatically disable the HVAC system
if a window is left open. This is done to prevent energy waste by trying to
heat or cool an open room.
The SMT-131 window input can be set for a Normally Open (switch open when
window is closed) or normally closed logic (switch closed when window is
closed). When the window is left open for longer than the pre-set time (0 to
300 seconds) the SMT-131 will automatically turn OFF. The text “OFF” will
flash in the LCD to indicate that the remote window (or door switch) is
holding the SMT-131 in off mode. The wall controller will prohibit all
changes.
The SMT-131 will automatically restart once the window is closed.
The Installer menu option 28 “Window Input Logic” and option 29 “Window Input
Delay” (page _17)_sets the window detection logic in the SMT-131.
Fault Indication
The SMT-131 can display the text “FLt” alternating with the temperature should
you wish to alert the user of an external fault with the heating or cooling
system.To enable this function, enter the installer menu and set the Window
contact input setting 31 to option 3. (See page 17 for this setting).
When the WC terminal and the Com-0V terminal are joined the SMT-131 will
alternate “FLt” with the current room temperature.
Register 32 will permit a time delay to be set after the fault signal is
received if necessary to reduce false trips.
The fault indication has NO effect on thermostat function
Door Switch
The Door switch input (DS) is used by the SMT-131 for 3 functions.
- To detect that the door has been opened and then closed to let somebody into or out of the
- To detect if the door has been left open.
- To use as an occupancy or Auto-Off timer in training rooms or
The SMT door switch input can be set for a Normally Open (switch open when door is closed) or normally closed logic (switch closed when door is closed) or OFF (input not used). The Installer menu 30 “Door Input Logic” and option 31“Door Input Delay” (page _17)_sets the door detection logic in the SMT-131.
Entering or exiting the room.
Once the door is opened and then closed the SMT-131 will begin its occupancy detection process using the PIR input described below. Based on the outcome of this process the SMT-131 will remain on and permit guest interaction with the SMT-131 (adjust mode and set point for example), or switch to “un-occupied” mode where the SMT-131 will substitute the guest set point and mode for the installer pre-set values.
Door Left Open
When the door is left open for longer than the pre-set time (0 to 300 seconds)
the SMT-131 will automatically turn OFF. The text “OFF” will flash in the
display to indicate that the remote door (or window switch) is holding the
SMT-131 in off mode. This is done to prevent energy waste by trying to heat or
cool an open room.
The SMT-131 will automatically restart once the door is closed.
PIR input
A PIR (passive infra-red) movement detector can be directly wired to the SMT-131 “PIR” input. As movement is detected by the PIR it will send multiple On/Off pulses to the SMT-131 every time it detects movement. The SMT-131 using this data (with or without a door switch) will determine the occupancy status of the room and behave accordingly. Note, the PIR must be separately powered, typically from a 12VDC supply. Consult the PIR manual for this information. Smart Temp do not provide a PIR sensor, and suitable alarm PIR sensor is suitable.
Latched Occupancy Detection Logic
(Typically used in Hotel applications) Latched occupancy detection requires
a door switch and PIR input to be wired and working.
When the door is first opened the SMT-131 instantly enters “Occupied Mode”
where the SMT-131 will permit the room occupant to set their desired
temperature and mode of operation. Once the door is closed the SMT-131 will
“look” for movement as detected by the PIR sensor wired to the PIR input. If
no movement is seen within the installer pre-set seek time (installer
adjustable 1 to 15 minutes) the SMT- 131 will return to “Un-occupied mode”
where the users temperature and mode will be replaced with installer pre-set
values. Should movement be detected within the installer pre-set seek time the
SMT-131 will Latch into “Occupied Mode” and no longer rely on continued
movement within
the room to remain in “Occupied Mode”. This ensures that the room remains a
conditioned space even if the occupant stops moving or sleeps for example.
Next time the door is opened and then closed again the SMT-131 will again
begin its occupancy detection process.
Note – even when the SMT-131 is in “un-occupied mode” it will continue to
use the PIR input to determine room occupancy. For example – in a hotel a
couple may be staying in the room and one leaves the room leaving the other
asleep in bed. As the door closes the SMT-131 will seek movement and when none
is found it will enter “un-occupied mode”. As the sleeper wakes and then moves
the SMT-131 will automatically re-enter “Occupied Mode” even though it may
have been some time since the door was closed.
Installer option “PIR Input Delay” (page 17 ) sets the PIR mode (On or
Off) and the seek time value (1 to 15 minutes).
Using a PIR Only for occupancy Detection
(Typically used in meeting or class room applications)
When you require the SMT-131 to turn the Heating and Cooling on when people
enter a room and off when people exit the room such as maybe the case in a
conference or class room.
Wire the PIR directly to the DS (door switch input) of the SMT-131. When
movement is detected by the PIR sensor the SMT-131 will turn the Air
conditioning on maintain the set point. After the last person has left the
room the SMT-131 will wait an installer defined time and then switch to “Un-
Occupied Mode”
Steps to use the SMT-131 in automatic occupancy detection mode.
- Wire the PIR movement detector into the DS (Door Switch)
- Set the PIR input delay period (See page 17 for information on setting the PIR input delay) to the number of minutes that you wish the Airconditioning to run after the last movement has detected in the space.
- Place a link permanently shorting the PIR input to Com
Manual Occupancy Input
The DI (Digital Input) & Com 0-10 terminals within the SMT-131 can be used to
instantly force the SMT-131 into “Un-occupied Mode”. This input can be wired
to a simple card reader or other 3rd party system that may be pre-installed
for room occupancy detection.
When the SMT-131 is in “Un-occupied Mode” the display will go completely blank
except for the words “Unoccupied” in the top left corner. If the optional
HOT-243 hall way panel is installed its display backlight will go out to let
housekeeping know the room is empty. Modbus register 40004 also indicates
occupancy status.
Doorbell
A built-in doorbell feature is included with the SMT-131 thermostat. This is normally activated by the optional outside door station as described above or via Modbus data link. In circumstances where this is not convenient the Digital Input (DI) terminals can be reassigned as a doorbell
activation switch with the digital input options detailed in the installer menu. (see page 17 ). Simply place a momentary volt free switch across “DI” and Com “0-V” terminals to activate the doorbell. Once pressed, the doorbell will chime for about 10 seconds.
Outside Door Station
When coupled with the optional Smart Temp door station the guest can set the
room as “Do Not Disturb”, call for housekeeping or be alerted to visiting
guests with a pleasant doorbell chime. Hotel staff are informed about the room
status or guest’s needs by text information displayed on the door station LCD
or the door station backlight colours.
Connection between the SMT-131 and the hotel door station is cable fitted with
RJ12 plugs. Cables can be provided at additional cost at up to 15 metres
maximum. Alternatively, custom cables can be produced. They are direct wired
(not cross over).
When fitting the door station, the SMT-131 DIP Sw8 must be ON. The outside
door station will flash all LCD segments if DIP Sw8 is in the wrong position.
Automatic Day Set Temperature
The SMT-131 can optionally reset the user set point and replace with an
installer defined set point after the SMT-131 has been off for more than 6
hours. This will typically happen after one guest has checked and before the
next guest checks in but will not generally affect a guest who may turn the
thermostat off for a few hours or so or who may go out for the afternoon.
Option 40 in the installer menu defines this Function. Off or a value between
15 and 30c or 59- 86F
Modbus Wiring
Modbus communications unlock many additional functions within the SMT-131 thermostat. It also permits all modes, functions and controls to be remotely supervised and adjusted from a central location if needed. Modbus object data can be found on page 15 of this manual.
The SMT-131 uses a high-powered Maxim chipset that will “theoretically” permit the connection of up to 255 devices on a single Modbus node. RF noises and other interferences will reduce the real world permitted connections to a maximum of 150 ~ 200 in most cases.
Modbus and other communication protocol rely on the quality of cable and good
installation practises to ensure reliable communications. Modbus requires the
use of screen cable with the drain grounded in a single location.
When using a common power supply or when using a modbus master that also
powers the SMT- 131, ensure the R (24v active), C (24v common) Data A & B
wires are not crossed.
Hint! When the SMT-131 is connected to a working Modbus Network and
receiving valid data, the decimal point in the temperature display will blink.
If there is no communication or the SMT-131 is receiving corrupted data, this
decimal point will remain on steady.
The Modbus data is provided in Addendum 1 at the back of this manual. (page
18 ).
Modbus relies on a series connection and will normally not tolerate “Star”
wiring or “T” branches.
Remote Temperature sensors
Occasionally the room thermostat cannot be installed in the ideal location to
measure the room temperature accurately. In these circumstances the SMT-131
can use optional remote temperature sensors. These are a two- wire resistive
device,(10K Type II NTC) not polarity dependent and simply wired into the
SMT-131 sensor inputs terminals (“SI” and “Com 0-V”). Depending on installer
menu sensor settings, (shown on page 17) , remote sensor(s) will either
override the SMT-131 onboard sensor or average with the onboard sensor.
Multiple sensors can be used for averaging over larger areas if necessary.
Wireless (RF) remote sensors are also available if fixed wiring cannot be
installed economically. (P/N RS-W).
Installer Options Menu
The SMT-131 has an impressive list of options that can be installer selected.
These options tune the thermostat’s performance as well as set energy
conservation settings. This menu is deliberately hidden and difficult to enter
to discourage unauthorised tampering.
The information card provided in the SMT-131 box provides details on how to
enter the SMT-131 menu. If this is lost, please contact Smart Temp or an
authorised distributor for support.
Navigating Through the Installer Mode Settings
The bottom right button steps forward through the menu options, the bottom
left button steps you backwards.
Adjust your options with the up/down buttons.
Exit the menu saving changes by pressing and holding the bottom right or wait
3 minutes and the SMT-131 will automatically exit the installer menu.
The current menu option is shown between the left and right buttons. The
example to the right shows option 3, select deg C (option 0) or F display
(option 1).
Note. Option 3 in the installer menu described below sets the SMT-131
native temperature display format as deg C or Deg F modes. Temperature options
in the installer options use the native temperature format.
Option List Table
| Option| Setting
---|---|---
0| Buttons Shown| 0: Both mode and fan buttons show (default)
1: Show mode but fan button hidden 2: Show fan but mode button hidden 3: Both mode and fan buttons Hidden
Note: If the mode button is hidden, the service and maintenance staff can turn the SMT-131 on or off by pressing and holding the lower left of the LCD for 15 seconds. 2 chirps indicate the SMT-131 has turned ON. 1 chirp indicates the
SMT-131 has turned off (ver 3.03+)
1| Permitted Modes| 0: Off / Auto
1: Off / Auto / Heat / Cool 2: Off / Heat /Cool
3: Off / Heat 4 Off / Cool
5: Off / Auto (Display current heating or cooling mode)
2| Room / Set display| 0: Show room and set temp (default)
1: Show set temp only
3| Native display format| 0: C (default)
1: F
4| C/F button shown on LCD| 0: Off(default)
1: On
5 | High temp set limit | 5C-30C or 41F-86F (Ver41.0+ 5-50c or 41-122F) |
---|---|---|
6 | Low temp set limit | 5C-30C or 41F-86F |
7 | Dead band | 0C-5.0C or 0F-10.0F in 0.1C/0.1F steps. |
Depending on Option 3 above.
Data format: Dead band * 10
8| Fan Purge / Run On Period| 0: OFF
1: Fan purge – 1 min
2: Fan purge – 3 min
3: Fan purge – 5 min
4: Fan purge – 10 min
5: Heat only fan purge – 1 min 6: Heat only fan purge – 3 min 7: Heat only fan purge – 5 min 8: Heat only fan purge – 10 min 9: Cool only fan purge – 1 min 10: Cool only fan purge – 3 min 11: Cool only fan purge – 5 min
12: Cool only fan purge – 10 min
9| Fan span| 0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
10| 0-10V Fan Interval (PI)| 10-300 seconds 10 seconds’ steps (60 seconds
default)
11| 0-10V Fan direction| 0: 0 – 10V – slow to fast (Forward Acting)
1: 10 to 0V – slow to fast (Reverse Acting)
12| 0-10V Fan minimum value (Starting fan voltage when
running)
| 0 -10V
Data format: 0-10V Fan minimum value * 10
13| 0-10V Fan Maximum value (Maximum fan voltage
when running)
| 0 -10V
Data format: 0-10V Fan minimum value * 10
14| Heat span| 0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
15| 0-10V Heat interval (PI)| 10-300 seconds 10 seconds’ steps (60 seconds
default)
16| 0-10V Heat direction| 0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
17| 0-10V Heat minimum
Voltage
| 0 -10V
Data format: 0-10V Heat minimum value * 10
18| Cool span| 0.5C-3.0C/1.0F-6.0F 0.1C/0.1F steps
Data format: Fan span * 10
19| 0-10V Cool interval (PI)| 10-300 seconds 10 seconds’ steps (60 seconds
default)
20| 0-10V Cool direction| 0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
21| 0-10V Cool minimum
Voltage
| 0 -10V
Data format: 0-10V Cool minimum value * 10
22| Auto Off Timer| 0: No auto off timer
1-10hours 0.5 hour increments.
Data format: hour * 10
23| Un-occupied heat
Set point
| 0: OFF
5C-30C/41F-86F 0.5C/1F steps
24| Un-occupied cool
Set point
| 0: OFF
5C-30C/41F-86F 0.5C/1F steps
25| Un –Occupied fan mode| Fan 3 Speed mode
1: Low (Auto) (default) 2: Med (Auto)
3: High (Auto)
4: Low (ON)
5: Med (ON)
6: High (ON)
---|---|---
26| Backlight| 0: On with button press Only (Default > ver 3.1) 1: Always On
high
2: Low when standby / high when active (Default < ver 3.1)
27| TT sensor (SI & Com)| 0: Remote – Use this sensor in place of the fitted sensor.
1: Average – Use both remote and fitted sensor and control to the average temperature of both sensors.
2: Data – Sensor value used for Modbus only.
3: Duct – Used for 2 pipe mode.
28| Temperature Calibration| +/- 10 deg (C or F)
Adjust to show correct room temp.
29| Digital Input| 0: Force Room to Unoccupied Mode 1: Chime Door Bell
2: Klixon Mode Enable
30| Digital Input Logic| 0: Normally Open
1: Normally Closed
31| Window Input Logic| 0: Normally Open
1: Normally closed
2: OFF (Input function disabled)
3: Ver 3.3+ Show FLt (Fault) on LCD (Toggles between
temperature display and “FLt”)
32| Window Input Delay| 0 – 300 seconds 30 seconds steps (30 seconds default)
33| Door Input Logic| 0: Off (default)
1: Normally open
2: Normally close
34| Door Input Delay| 0 – 300 seconds 30 seconds steps (180 seconds default)
35| PIR Input Delay| 0: Off (default)
1 – 15 minutes 1 minute steps (ver 3.3 changed 0-60min)
36| Reset Fan| 0: Off
1: On
(resets indoor fan to auto every time mode is set to off)
37| Belimo Mode| 0: Off 1: On
38| Modbus Address| 1-255
39| Baud rate| 1: 4800bps
2: 9600bps (default)
3:19200bps
40| Default Start Temp
Version Ver 3.3+
| 0=OFF (default) 15~35C or 59~86F
41| Beeper
Version Ver 3.9+
| 0: Off
1: On (default)
42| Fan Relay Lock (Version 40.1+)| 0:Off (default) 1: On
(This function locks the Fan relay logic to 0-10V outputs – if
enabled depending on other settings it may cause fan to start
and run before heat or cool calls from the W & Y relays. | ||
---|---|---|
43 | Thermostat response to changes in room Temperature Ver 4.04+ | 0: Very Fast |
1: Fast
2: Normal
3: Slow (Default)
4: Very Slow
44| Firmware Ver 41.1 +
2 Pipe heating threshold
| Range 5 to 50 (default 30c)
45| Firmware Ver 41.1 +
2 Pipe cooling threshold
| Range 5 to 50 (default 20c)
t| Temperature calibration Offset Ver 4.04+| -9.9c to +10c 0.0 (Default)
This permits you to apply a correction offset factor to the
room (or remote) temperature sensor used by the SMT-131.
r| Factory Reset| 0: NO
1:Yes (Exit to initiate)
Modbus Data – Addendum 1
The SMT-131 has integrated Modbus RTU communications. Using a Modbus master
controller such as the Smart Temp 770-HMI many of the SMT-131 thermostat
features can be centrally controlled and monitored.
Modbus is a simple protocol that is extremely popular due to its robustness
and simple implementation. It is also a “forgiving” protocol and will tolerate
many installation errors. This being stated however; correct wiring practices
should be used to achieve maximum reliability. See page 10 for details on
wiring Modbus networks.
The SMT-131 Modbus data is within the “40XXX” range, this being holding
registers. Depending on your choice of Modbus Master you may need to enter the
address using the full address – such as “40012” or by selecting “Holding
Registers” and entering the address simply as “12”.
These modbus registers are shown as Base “1” (PLC addressing) format.
Depending on your modbus master addressing format you may need to subtract 1
from these values to convert to base “0” (protocol addressing) format.
Note – The Modbus data layout may seem unorganised in this document, for
example 0-10v for heat and cool is at register 40040 & 40041 while the 0-10V
output for the fan is at register 40068. This is done to maintain backwards
compatibility with the SMT-131 version 1 ModBus registers. All the new
functions added to version 2 of the SMT-131 have their Modbus registers at the
end of the version 1 SMT-131 Modbus register list.
Data Format
Protocol Modbus RTU (Slave)
Byte Format 1 Start Bit, 8 Data Bits, 1 Stop Bit, No
Parity Address 1 to 255
Baud 4800 / 9600 / 19200 BPS
Holding
Register
| Type| Value| Comments
---|---|---|---
40001| Read Only| Device ID| Always Returns “131”
Use as A Sentinel Point
40002| Read Only| Firmware Version| Divide By 100 (e.g. Version 2.36 = 236)
40003| Read Only| DIP Switch State| Binary Count
Sw 1 = 1, Sw2 = 2, Sw3 = 4, Sw 4 = 8 etc
40004| Read /
Write
| Occupancy Status| 0 = Room is Unoccupied 1 = Room is Occupied
Note – Modbus can write “0” holding the room unoccupied regardless of the occupancy input.
Modbus cannot override the occupancy input
and hold the SMT-131 in occupied mode.
40005| Read Only| Bell Status| 0 = Bell Is Silent
1 = Bell Is Chiming
40006| Read /
Write
| Door Station Status| 0 = Normal – No Activity
1 = “Make Up Room” Active
2 = “Do Not Disturb” Active
40007| Read /
Write
| HVAC Status| 0 = Air Conditioning Off (1 or 3 Fan Speed)
1 = Low Speed Ventilation (1 or 3 Fan Speed) 2 = Med Speed Ventilation (3 Fan Speed Only) 3 = High Speed Ventilation (3 Fan Speed only)
4 = Air Conditioning ON (1 or 3 Fan Speed)
40008| Read /
Write
| Fan Status| 3 Fan Speed Mode 0 = Low (Fan Auto) 1 = Med (Fan Auto) 2= High (Fan Auto)
3 = Auto Fan Speed (Fan Auto) 4 = Low (Fan On)
5 = Med (Fan On) 6 = High (Fan On)
7 = Auto Fan Speed (Fan On)
1 Fan Speed Mode
0 = Fan Auto
4 = Fan On
40009| Read /
Write
| User Set Point| Deg C = 0.5°C Steps Deg F = 1°F Steps
Value / 10 ( e.g. 23.5°C = 235)
40010| Read /
Write
| Contact Reception Notification| 0 = Off
1 = Show Contact Reception on LCD
SMT-131 LCD will flash “Contact Reception”
on LCD and sound chime. User may accept
alert by touching any button on SMT-131
40011| Read /Write (Read only
ver +4.04)
| Room Temperature| Value / 10 (e.g. 21.7c = 217)
(Writing to the room temp register to
calibrate this value.)
---|---|---|---
40012| Read /
Write
| Temperature
Display
| 0 = Show Room and Set Temperature
1 = Show Set Temperature Only
40013| Read /
Write
| Native C/F Display| 0 = Deg C format
1 = Deg F format
40014| Read /
Write
| User Set Point High
Limit
| 5°C to 30°C Range (41°F-86°F) in 1°C/F Steps
1:1
40015| Read /
Write
| User Set Point Low
Limit
| 5°C to 30°C Range (41°f-86°F) in 1°C/F Steps
1:1
40016| Read /
Write
| Dead Band| 0.5°C to 5.0°C in 0.5°C Steps 1.0°F to 10.0°F in 1°F Steps
Value / 10 (e.g. 1.5°C Dead Band = 15)
40017| Read /
Write
| Relay Span| 0.5°C to 3.0°C in 0.5°C Steps 1°F to 10°F in 1°F Steps
Value / 10 (e.g. 1.0°C Span = 10)
Version 3 code has this function Inactive. Modbus will return valid data however this function is internally disabled. Register
provided for backwards compatibility only.
40018| Read /
Write
| Fan Purge Period| 0 = Off
1 = Fan Purge – 1 Min 2 = Fan Purge – 3 Min 3 = Fan Purge – 5 Min 4 = Fan Purge – 10 Min
5 = Heat Only Fan Purge – 1 Min 6 = Heat Only Fan Purge – 3 Min 7 = Heat Only Fan Purge – 5 Min 8 = Heat Only Fan Purge – 10 Min 9 = Cool Only Fan Purge – 1 Min 10 = Cool Only Fan Purge – 3 Min 11 = Cool Only Fan Purge – 5 Min
12 = Cool Only Fan Purge – 10 Min
40019| Read /
Write
| 0-10V Heat Span| 0.5°C to 10°C in 0.5°C Steps 1°F to 20°F in 1°F Steps
Value / 10 (e.g. Heat Span of 1°C= 10)
40020| Read /
Write
| 0-10V Cool Span| 0.5°C to 10°C in 0.5°C Steps 1°F to 20°F in 1°F Steps
Value / 10 (e.g. Cool Span of 1°C = 10)
40021| Read /
Write
| Auto Off Timer| 0 = 0ff
1 to 10 Hours. (0.5 hour steps)
Value / 10 (e.g. 3 Hour Auto Off Timer = 30)
40022| Read /Write| Unoccupied Heat Set Point| 0 = Off
5°C to 30°C in 1.0°C Steps
41°F to 86°F in 1°F Steps
40023| Read / write| Unoccupied Cool Set Point| 0 = Off
5°C to 30°C in 1.0°C Steps
41°F to 86°F in 1°F Steps
40024| Read /
Write
| Unoccupied Fan Mode| 3 Fan Speed Mode 1 = Low (Fan Auto) 2 = Med (Fan Auto) 3 = High (Fan Auto) 4 = Low (Fan On)
5 = Med (Fan On) 6 = High (Fan On) 1 Fan Speed Mode 0 = Fan Auto
4 = Fan On
---|---|---|---
40025| Read /
Write
| Backlight| 0 = On with Button Press only 1 = Always On (High)
2 = Always On Low – High With Button Press
40026| Read /
Write
| Remote “SI & Com 0-V Temperature Input Function| 0 = Replace On Board Sensor with Remote 1 = Average On board Sensor with Remote
2 = Modbus Use Only (e.g. Coil Temp Monitor)
3: 2 pipe monitor
40027| Read /
Write
| Digital Input Function| 0 = Occupancy Initiate 1 = Chime Door Bell
2 = Input Disabled (Ver 3.09+)
40028| Read /
Write
| Reset Fan Mode| 0 = Leave fan mode unchanged
1 = Reset fan to Auto at switch off
40029| Read /
Write
| Belimo Mode| 0 = Standard 0-10V Valve Logic
1 = Belimo 6V = Off 3 Way Valve Logic
40030| Read /
Write
| Modbus Address| 1 to 255
40031| Read /
Write
| Baud Rate| 1 = 4.8Kbs
2 = 9.6kbs
3 = 19.2Kbs
40032| Read Only| Digital Input Status| 0 = Open
1 = Closed
40033| Read Only| Internal Sensor
Value
| Value / 10 (e.g. 23.3°C = 233)
40034| Read Only| Remote Sensor
Value
| Value / 10 (e.g. 21.8°C = 218)
Version 3.09+ firmware provides the ability for Modbus to override all the
SMT-131 outputs. (5 x relays & 3 x 0-10v).
Note – To protect equipment functions the following rules apply.
To override register 40035 (W relay).
The anticycle timer must be OFF. (SW 5=Off).
To override register 40036 (Y relay)
The mode must be Heat Cool (Sw2=OFF) and the anticycle timer must be OFF. (SW 5 = Off)
To override register 40037 (High fan relay)
Single fan speed (Sw1=OFF) must be selected and the mode must be Heat Cool (Sw2=OFF)
To override register 40038 (Med fan relay)
Single fan speed (Sw1=OFF) must be selected and the mode must be Heat Cool (Sw2=OFF)
To override register 40039 (Low fan relay)
The mode must be Heat Cool (Sw2=OFF)
The 3 x 0-10V ( 40040 (Heat) , 40041 (Cool) & 40068 (Fan)) , outputs can be controlled by Modbus at any time without restriction.
To permit Modbus to control the output first enter 1000 in the register you wish to override, it is then unlocked from SMT-131 control and you are then permitted to enter the value you wish the selected output to be; such as 0=relay OFF and 1 1=relay ON or 63 should you wish the 0-10v to output 6.3v.
To return the output to SMT-131 control simply enter 1001 into the register.
Please Note – Writing to the relays or 0-10V output via Modbus bypasses the SMT-131 internal memory protection logic. Changing these values regularly via Modbus may reduce the thermostats memory life to only a few years. Using this function will void the SMT-131
warranty for the memory chip within the thermostat.
40035| Read Only Read Write (3.09+)| W relay status| 0 = Off (under thermostat control)
1 = Energised (under thermostat control) 1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40036| Read Only Read Write (3.09+)| Y Relay Status| 0 = Off (under thermostat control)
1 = Energised (under thermostat control) 1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40037| Read Only Read Write (3.09+)| High Fan Relay Status| 0 = Off (under thermostat control)
1 = Energised (under thermostat control) 1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40038| Read Only Read Write (3.09+)| Medium Fan Relay Status| 0 = Off (under thermostat control)
1 = Energised (under thermostat control) 1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40039| Read Only Read Write (3.09+)| Low Fan Relay Status| 0 = Off (under thermostat control)
1 = Energised (under thermostat control) 1000 = Held OFF by Modbus
1001 = Held ON by Modbus
40040| Read Only Read Write
(3.09+)
| 0-10V Heat Value| Value / 10 (e.g. 7.3V = 73)
(To write add 10 e.g. – to write 7.3v send
1073
40041| Read Only Read Write
(3.09+)
| 0-10V Cool Value| Value / 10 (e.g. 2.1V = 21)
(To write add 10 e.g. – to write2.1v send 1021
40042| Read Only| Permitted Modes (ver 2.1+ only)| 0 = Auto (Heating and cooling called) 1 = Heat Only Mode
2 = Cool Only Mode
Values below only apply to version 2 hardware only, Firmware version 3+
40043| Read /
Write
| 2 pipe mode
changeover
| 0 = Heat
1 = Cool
40044| Read /
Write
| Thermostat
Displaying
| 0 = Deg C
1 = Deg F
40045| Read /
Write
| Buttons shown on display| 0: Both mode and fan buttons show (default) 1: Show mode but hide fan button
2: Show fan but hide mode button
40046| Read Write| /| Permitted Modes| 0: Off / Auto
1: Off / Heat / Cool / Auto 2: Off / Heat / Cool
3: Off / Heat 4: Off / Cool
5: Off / Auto – (display current mode in LCD)
---|---|---|---|---
40047| Read
Write
| /| Swap C/F display
shown on display
| 0: C/F Button hidden
1: C/F button shown
40048| Read
Write
| /| Fan Span| 0.5C-10 C 0.5C step 1.0F-20 F 1F steps
Data format: Fan span * 10
40049| Read
Write
| /| 0-10 Fan Interval| 10-300 seconds in 10 second steps
seconds default.
| (60
40050| Read
Write
| /| 0-10 Fan Direction| 0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40051| Read
Write
| /| 0-10 Fan Minimum
Voltage.
| 0-10v (Fan value x 10)
40052| Read
Write
| /| 0-10 Heat Interval| 10-300 seconds in 10 second steps
seconds default.
| (60
40053| Read
Write
| /| 0-10 Heat Direction| 0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40054| Read
Write
| /| 0-10 Heat
Minimum Voltage
| 0-10v (Heat value x 10)
40055| Read
Write
| /| 0-10 Cool Interval| 10-300 seconds in 10 second steps
seconds default.
| (60
40056| Read
Write
| /| 0-10 Cool Direction| 0: 10V is 100% open (forward acting)
1: 0V is 100% open (reverse acting)
40057| Read
Write
| /| 0-10 Cool Minimum
Voltage
| 0-10v (Cool value x 10)
40058| Read Write| /| Window input logic| 0: Normally Open
1: Normally closed
2: Off (input disabled)
3: Shows FLT (FAULT) shown on alternating with temperature display.
|
LCD
40059| Read
Write
| /| Window input
Delay
| 0-300 seconds in 30 second steps
40060| Read Write| /| Door input logic| 0: Off
1: Normally Open
2: Normally closed
40061| Read
Write
| /| Door input Delay| 0-300 seconds in 30 second steps
40062| Read
Write
| /| PIR input Delay
(Seek Time)
| 0: Off
1-60 minutes in 1-minute steps
40063
40064
| Read
Write
| /| Unit run time log| 0-9999.9 hours
Register 40063 & 40064 are to be used together to determine the total Heat &
Cool run time in
0.1 hours.
For example, for a total run time of 15643.4 hours register 40064 will show 434 and register
40063 will show 156
40065| Read Only| Window Input
Status
| 0: Open
1: Closed
40066| Read Only| Door Input Status| 0: Open
1: Closed
---|---|---|---
40067| Read Only| PIR Status| 0: No Movement detected
1: Movement detected
40068| Read Only Read Write
(3.09+)
| 0-10V Fan Value| Value / 10 (e.g. 2.1V = 21)
(To write add 10 e.g. – to write2.1v send 1021
40069| Read Only| 0-10V Fan Max
Value
| 0-10v (@*10)
40070| Read /
Write
| Digital Input logic| 0: Normally Open
1: Normally Closed
40071| Read /
Write
| Default Start Temp
Ver 3.3 firmware +
| 0: Off
15-35c or 59-86F
40072| Read /
Write
| Beeper| 0: Beeper OFF
1: Beeper On (Default)
40073| Read /
Write
| Fan Relay Lock (Version 40.1+)| 0: Off (default)
1: On
This function locks the Fan relay logic to 0-10V outputs – if enabled depending on other settings it may cause fan to start and run before heat or cool calls from the W & Y
relays.
40074| Read /
Write
| Temperature calibration offset (Version 40.4+)| -9.9 to +10c
This register permits the room temperature to be offset to correct for perceived room temperature sensor inaccuracies.
40075| Read /
Write
| Temperature sensor speed of response.
(Version 40.4+)
| 0: Very Fast
1: Fast
2: Normal
3: Slow (Default)
4: Very Slow
Specifications
Input Voltage 24VAC 50/60 Htz +/- 15%
Operating Temperature= 0°C to 50°C (32°F to 122°F) Operating
RH 0-95% (Non-Condensing)
Storage Temperature =0°Cto 65°C (32°F to 150°F) Size =113 x 103 x 25mm.
Display Size 69.5 x 46.3mm.
Backlight White LED (Other Colours
Available Upon Request)
Display Type STN Touch Panel
Relay Rating 30V @ 1Amp Max
0-10V Output Load 10mA Max
Control Range 5°C to 30°C (41°F to 86°F)
Memory Type Non-Volatile – Settings Do Not
Require Battery Backup
Communications Modbus RTU 4 .8K / 9.6K / 19.2 K
1 Stop Bit, 8 Data Bits, 1 Start Bit. No Parity.
Plastic ABS / Poly Blend – UV
Stabilised and Fire Rated
Warranty 3 Year RTB
Great care has been taken in the preparation of this manual. Smart Temp
Australia P/L takes no responsibility for errors or omissions contained in
this document. It is the responsibility of the user to ensure this controller
or equipment connected to it, is operating to their respective specifications
and in a safe manner.
Due to ongoing product improvement Smart Temp Australia P/L reserves the right
to change the specifications of the SMT-131 thermostat (or its components)
without notice.
All rights reserved. © Smart Temp Australia P/L 2011 Intellectual rights
apply.
Read More About This Manual & Download PDF:
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>