SMART TEMP SMT-710 Thermostat with Zone Control Instruction Manual
- June 13, 2024
- SMART TEMP
Table of Contents
SMT-710 Thermostat with Zone Control
Product Information: SMT-710 Manual Thermostat with Zone
Control
Thank you for purchasing the Smart Temp SMT-710 Zone Control
Thermostat. This thermostat offers several features to help you
control and maintain the temperature in your home or office.
Turning your Thermostat On and Off
The mode selection is located in the lower left corner of the
display. Depending on how your installer has set up your SMT-710,
you have the option to select On and Off with a single set point or
individual heating and cooling modes with separate set points. If
the text “Heat” or “Cool” is flashing, it means that your SMT-710
is requesting that function from your air conditioning system.
There may also be a maximum heating and cooling set point limit
imposed, and you will be notified when this limit is reached.
Controlling the Fan Speed and Mode
The SMT-710 can control a single or multi-speed fan system,
which will be set up by your installer to match your air
conditioning system’s capability. You can select between Fan On
Mode or Fan Auto Mode. In Fan On Mode, the fan will run
continuously regardless of heating or cooling. In Fan Auto Mode,
the fan will turn on and off with the heating and cooling. If you
have a multi-speed fan system, you can manually select between Low,
Medium, and High fan speeds, or let the SMT-710 automatically
choose the best fan speed based on the room temperature.
Setting your Desired Temperature
The display shows your current room temperature along with Up
and Down buttons. By tapping these buttons, you can adjust the set
temperature for the selected mode. In Heat only mode, you can
adjust the Heat set point; in Cool only mode, you can adjust the
Cool set point; and in Auto or On mode, you can adjust the single
set point. Please note that in single set point mode, there is a
Dead Band defined by your installer, where heating or cooling is
not needed.
Limit Control
Your installer may have set a temperature control limit, which
restricts the range of temperature adjustment. If the limit is
reached, the display will show a message and emit a few beeps to
notify you.
Zone Control
The SMT-710 has the capability to manage two independent zones:
Zone 1 (the location of the wall controller) and Zone 2. If a zone
is selected, conditioned air will be sent to that area, and the air
conditioning will turn on and off to maintain the temperature in
that zone. If the SMT-710 does not have the optional Zone 2
temperature sensor fitted, it will assume that both Zone 1 and Zone
2 have the same temperature as measured by the wall controller in
Zone 1.
For more detailed instructions and information, please refer to
the complete user manual.
SMT-710 Manual Thermostat with Zone Control
Thank you for the purchase of the Smart Temp SMT-710 Zone Control Thermostat.
Please take the time to read and understand this manual so that you may take
advantage of the many features this thermostat may offer
Turning your Thermostat On and OFF.
The lower left corner of the display controls the mode selection, depending
OFF ON AUTO HEAT COOL
on how your installer has set your SMT-710 up you will
be given the option of selecting On and Off with a single
set point (with a preset differential between the heating
and cooling) or selecting individual heating and cooling
modes, each with individual heating and cooling set
points.
If the text Heat or Cool is flashing then your SMT-710 is requesting that function from your air conditioning system.
If set for Heat and Cool mode, a maximum heating and cooling set point limit
may be imposed. Text and a chirp will be given when this limit is reached. Fan
ONVentilation
Low Medium High Auto
Controlling the Fan Speed and Mode. The SMT-710 can control a single or multi
speed fan system. This capability will be setup by your installer to match the
capability of the Air Conditioning system that it is controlling.
Fan Mode Press and hold the fan button to select Fan On Mode -in 3 fan speed mode or tap in single fan speed mode. In this mode the fan will run continuously regardless of the heating or cooling. Press and hold (or tap) again to return to Fan Auto mode where the fan will turn on and off with the heating and cooling.
Fan Speed The SMT-710 can also control multi-fan speed systems where you can either manually select between Low, Medium and High fan speed or let the SMT-710 automatically select the best fan speed based on how far the room temperature is from the set temperature. Simply tap the fan button to cycle through all available speeds if this function is enabled.
Setting your desired Temperature. The display will show you your current room
temperature along with some Up/Down buttons. When you tap either of the up
down button the display will change and show you the set temperature for the
currently selected mode, being the Heat set point in Heat only mode and the
Cool set point in Cool only mode or the single set point in Auto or On mode.
(Note, In single set point mode your installer will have defined a “Dead Band”
of a few degree either side of the internal heat and cool set points where the
heating or cooling is not needed.
Limit Control Your installer many have set a temperature control limit, where the range of temperature adjustment may be restricted. Text showing the limit has been reached will be shown on the display accompanied by a few beeps.
Zone Control One of the strengths of the SMT-710 is
Zone 1 SELECTED
its ability to manage two independent zones. These
zones are identified as either Zone 1 (The location of
the wall Controller) and Zone 2. If the zone is shown as
“selected” then conditioned air will be sent to this area
and the air conditioning will turn on and off to maintain
this zones temperature.
Single Sensor Zone Control If the SMT-710 does not have the optional Zone 2 temperature sensor fitted, then it will assume both Zone 1 temperature and Zone 2 temperature is the same – as measured by the wall controller in Zone 1. The air conditioning will turn on and off to maintain the current set point.
Twin Sensor Zone Control When the SMT-710 detects the Zone 2 sensor has been installed, it will control both Zone 1 and Zone 2 to ensure both zones temperature is maintained to the desired value. This may mean that conditioned air may automatically be sent to Zone 2 only (for example) if zone 2 needs additional heating or cooling to reach the desired set point. The Air Conditioning system will treat both zones Independently.
Room Temperature Display – Twin sensor The SMT-710 will display the Zone 1
temperature when ever Zone 1 only is selected or if Zone 1 and Zone 2 is
selected. If Zone 2 only is selected the SMT-710 will display Zone 2
temperature.
Note, If at anytime you wish to see the Zone 2 temperature, press and hold the
Zone 2 button for 2 seconds and the display will go blank except for the Zone
2 button and the room temperature as measured in Zone 2. The display will
return to normal after 4 seconds.
Ver 2.2
Smart Temp
Unit 20 / 1488 Ferntree Gully Rd Knoxfield Vic Aust 3180
www.smarttemp.com.au www.thermostat.com.au +61 3 97630094
info@smarttemp.com.au
Installation Wiring the wall controller to the unit control card requires 4
wires, 24V Active, 24V common Data A and Data B. The wall controller and the
unit control card are labelled identically, being R C A B. 4 wires need be
used of 0.2mm diameter ideally screened but not essential for short runs. An
external 24VAC power supply should be used and connected to either the wall
controller or Unit Control Card (12V DC can also be used, +12 to R and -12 to
C).
The SZ-PS power supply is suitable.
SMT-710 Wall Controller
Aux In Data Power
TT BA
SZ-PS
24VAC CR
Typical 2 Stage Heat Pump – 3 Fan Speeds
Relay Common
Rly Com
Low Fan
G1
Fan
Medium Fan
G2
HighFan
G3
Comp / Cool Normally Closed
Y1 NC
Comp / Cool Normally Open
Y1
Cool
Comp
Heat / R-Valve Normally Closed
WNC1
Heat / R-Valve Normally Open
W1 Heat
R/Valve
Assignable Relay
Ass Rly
Zone 1 Damper Close
Z1 NC
Zone 1 Damper Open
Z1 NO
Zone Common
Zone Com
Zone 2 Damper Close
Z2 NC
Zone 2 Damper Open
Z2 NO
Control Active Low Fan Medium Fan High Fan Comp 1 Comp 2 Reversing Valve
DIP 1 On (3 Fan Speeds) DIP 2 On (Heat Pump) DIP 3 Off for RV in cool (O) DIP
3 On for RV in Heat (B) DIP 4 to 8 Installer Choice Set Installer Option 13 =
1
Flash with Data
Zone 2 Sensor
Heat
R C A B 0 H C F 0 T T Power
Ass Ass In+ In-
Cool Fan
Z1 Z2
0-10V Heat Cool Fan
Power Data
Unit Control Card
Zone Common Z2 Sensor Zone 2 Damper
Zone 1 Damper Aux Input
Comp / Cool Heat / R-Valve Assignable Relay
Relay Common Fan
G1G2 G3 Y1 W1 Rly
Com Fan
Y1
W1
Ass Zone 1 Zone Zone 2
NC NC Rly Cool Comp
Heat R/Valve
NC
NO
Com
NC
NO
Fan
O-10V Outputs
Terminal Designation
R 24 VAC Active (12V+) C 24 VAC Common (12v-) A Data A B Data B
0 0V / Common
H 0-10V Heat
C 0-10V Cool
F 0-10V Fan
0 0V / Common
Ass In+
Assignable Input
Ass In-
0V / Common
T Zone 2 Temp Sensor
T Zone 2 Temp Sensor
Rly Com
Relay Common
G1 Low Fan (or single fan)
G2 Medium Fan
G3 HighFan
Y1 NC
Comp / Cool Normally Closed
Y1
Cool
Comp / Cool Normally Open
Comp
W1 NC
Heat / R-Valve Normally Closed
W1 Heat
Heat / R-Valve Normally Open
R/Valve
Ass Rly
Assignable Relay
Z1 NC
Zone 1 Damper Close
Z1 NO
Zone 1 Damper Open
Zone Com
Zone Common
Z2 NC
Zone 2 Damper Close
Z2 NO
Zone 2 Damper Open
Dip Switch Settings (Sw 1, 2,3 &5 on by Default)
Switch Function
1
Fan Speeds
2 Equipment Type
3
HP/HC Mode
4
Not Used
5
Comp Delay
6
Not Used
7 Ventilation Mode
8
Zone Enable
Off
On
Single Speed 3 Speed
Heat Cool
Heat Pump
Gas Heat / O Electric Heat / B
Off
On – 5 Min
Off
On
Off
On
Typical 2 Heat 1 Cool 1 Fan Speed
Relay Common
Rly Com
Low Fan
G1
Fan
Medium Fan
G2
HighFan
G3
Comp / Cool Normally Closed
Y1 NC
Comp / Cool Normally Open
Y1
Cool
Comp
Heat / R-Valve Normally Closed
WNC1
Heat / R-Valve Normally Open
W1 Heat
R/Valve
Assignable Relay
Ass Rly
Zone 1 Damper Close
Z1 NC
Zone 1 Damper Open
Z1 NO
Zone Common
Zone Com
Zone 2 Damper Close
Z2 NC
Zone 2 Damper Open
Z2 NO
Control Active Fan Cool Heat Stage 1 Heat stage 2
DIP 1 Off (1 Fan Speed) DIP 2 OFF (Heat Cool DIP 3 Off for Gas Heat DIP 3 On
for Electric Heat DIP 4 to 8 Installer Choice Set Installer Option 13 = 2
Typical Heat / Cool Valve Wiring
24V Power Supply
R 24 VAC Active C 24 VAC Common
A Data A B Data B
0V / Common 0
O-10V Outputs
0-10V Heat H
0-10V Cool C
0-10V Fan F
0V / Common 0
Assignable Input
Ass In+
0V / Common
Ass In-
T Zone 2 Temp Sensor
T Zone 2 Temp Sensor
1
2
Heat Valve
3
1
2
Cool Valve
3
(typical Belimo LMU-24SR motor)
Note. Switch 3 function is based on the position of switch 2. Dip 2 OFF (Heat
– Cool Mode) DIP 3 controls the fan mode (Electric or Gas Heat Fan). DIP 2 ON
(Heat Pump Mode) Dip 3 controls the reversing valve logic (Energise Cool O or
Heat B)
Please contact Smart Temp or an authorised agent for additional support
information if required support@smarttemp.com.au
Installer Options Menu
The SMT-710 has a comprehensive list of options that can be adjusted by the
installer to better tune the performance of the SMT-710 to the needs of the
client.
To Enter the Installer Menu, with the mode OFF, Press and Hold the centre of
the LCD. After some seconds it will show the digits “15” Use the up (or down)
button to adjust this to “21” or the new PIN if changed from default.
Navigate forward or backwards through the installer menu with the lower left
and right buttons, adjust the current value with the up / down button.
To exit the installer menu press and hold the lower right button for 3
seconds. (Do not remove power for 30 seconds to save changes.)
Option 0 Installer entry PIN 0-99 (Default 21) Option 1 Buttons shown 0 – Both
Mode and Fan button shown (Default) 1 – Show mode but hide fan 2 – Show fan
but hide mode* 3 – Both mode and fan buttons hidden. Option 2 Permitted User
Modes 0 – Off / Auto 1 – Off / Auto / Heat / Cool 2 – Off / Heat / Cool
(Default) 3 – Off / Heat 4 – Off /Cool 5 – Off / Auto (display current heat or
cool mode) Option 3 Room / Set Display 0 – Show room and set temp (Default) 1
– Show set temp only Option 4 Display Format 0 – Deg C (Default) 1 – Deg F
Option 5 C/F button shown on the LCD 0 – Off (Default) 1 – Show swap C/F
button on LCD Option 6 Heat Temp High Set Limit 5 to 50 C (Default 35) Option
7 Cool Temp Low Set Limit 5 to 50 C (Default 15) Option 8 Dead Band 0 to 5.0C
(Default 0.5c) Option 9 Heat Relay Span 0.5 to 10.0c (Default 1.0c) Option 10
Cool Relay Span 0.5 to 10.0c (Default 1.0c) Option 11 Fan Relay Span 0.5 to
10.0c (Default 1.0c) Option 12 Fan Purge 0 – Off (Default) 1 -Purge 1 minute 2
– Purge 3 minutes 3 – Purge 5 minutes 4 – Purge 10 minutes 5 – Purge Heat mode
1 minute 6 – Purge Heat mode 3 minute 7 – Purge Heat mode 5 minute 8 – Purge
Heat mode 10 minute 9 – Purge Cool mode 1 minute 10 – Purge Cool mode 3 minute
11 – Purge Cool mode 5 minute 12 – Purge Cool mode 10 minute Option 13 Aux
Relay Function 0 – Close on fault (Default) 1 – Y2 (in HP or HC mode) 2 – W2
(In Heat cool mode) 3 – Spill – Opens when all zones are closed (when option
38 = 0) Option 14 0-10V Heat Relay Span 0.5 to 10.0c (Default 1.0c) Option 15
0-10V Heat Interval PI 10 – 300 Seconds (60 Seconds default) Option 16 0-10V
Heat Direction 0 – 0-10V (valve opens as more heat required – Forward Acting)
(Default) 1 – 10-0V (valve closes as more heat required – Reverse Acting)
Option 17 0-10V Heat Minimum Voltage 0-10v 0.1 steps (Default 0v) Option 18
0-10V Cool Relay Span 0.5 to 10.0c (Default 1.0c) Option 19 0-10V Cool
Interval PI 10 – 300 Seconds (60 Seconds default) Option 20 0-10V Cool
Direction 0 – 0-10V (valve opens as more heat required – Forward Acting)
(Default) 1 – 10-0V (valve closes as more heat required – Reverse Acting)
Option 21 0-10V Cool Minimum Voltage 0-10v 0.1 steps (Default 0v) Option 22
0-10Fan Span 0.5 to 10.0c (Default 3.0c)
Option 23 0-10V Fan Interval PI
10 – 300 Seconds (60 Seconds default)
Option 24 0-10V Fan Direction
0 – 0-10V (valve opens as more heat required – Forward Acting)
(Default)
1 – 10-0V (valve closes as more heat required – Reverse Acting)
Option 25 0-10V Fan Minimum Voltage
0-10v 0.1 steps (Default 0v)
Option 26 0-10V Fan Maximum Voltage
0-10v 0.1 steps (Default 10v)
Option 27 Auto Off Timer
0 – Auto Off Timer disabled (Default)
1 to 10 hours.
Option 28 Un=Occupied Heat Set point
0 – Off (Default 15)
5-35C
Option 29 Un=Occupied Cool Set point
0 – Off (Default 27)
5-35C
Option 30 Un=Occupied Fan Speed / Mode (1 or 3 speed)
1 – Low (Auto) (Default)
1 – Auto 1 speed fan (Default)
2 – Medium (Auto)
3 – High(Auto)
4 – Low (On)
4 – On 1 speed fan
5 – Medium (On)
6 – High(On)
Option 31 Back light
0 – On with button press (Default)
1 – Always high
2 – Low in standby & high when touched
Option 32 TT Terminal Functions
0 – Remote sensor (replaces on board sensor) (Default)
1 – Average remote sensor with onboard sensor
2 – Force un-occupied
3 – Fault
Option 33 Assignable Input Function
0 – Remote sensor (replaces on board sensor) (Default)
1 – Average remote sensor with onboard sensor
2 – Force un-occupied
3 – Fault
4 – Force Off
5 – Warm Start (HP mode only – delays indoor fan till 25c or 30 seconds)
Option 34 Temperature Sensors Sensor speed of response
0 – Very fast
1 – Fast
2 – Normal
3 – Slow (Default)
4 – Very Slow
Option 35 TT Temperature Calibration
+/- 10c (Default 0.0c)
Option 36 Wall controller Temperature Calibration
+/- 10c (Default 0.0c)
Option 37 Zone 2 Temperature Calibration
+/- 10c (Default 0.0c) Option 38 Zone Management (see Zone Logic – next page)
0 – NO default zone. Both zones can be closed
1 – Zone 1 default. (zone 1 will auto turn on to keep a zone open)
2 – Zone 2 default (zone 2 will auto turn on to keep a zone open)
3 – No default – just cant turn off last zone (Default)
Option 39 Fault Input action
0 – Only display Fault on LCD – no action required
1 – Shut down HVAC – No display on LCD
2 – Shut down HVAC and display on LCD (Default)
3 – Shut down HVAC after 15 seconds – no display on LCD
4 – Shut down HVAC after 15 seconds – display on LCD
Option 40 Modbus Mode
0 – SP7 communication (Inc temperzone & BMS )(Default)
1 -Intesis Module
2 – SMT-UI
Option 41 Modbus Address (only if Option 34 = 3)
1 – 255 (Default 7)
Option 42 Modbus Baud (only if Option 34 = 3)
0 – 4800
1 – 9600
2 – 19200 (Default )
Option 43 Modbus Parity (only if Option 34 = 3)
0 – None
1 – Odd
2 – Even (Default)
Option 44 Dec x 10 for Intensis or SMT-UI-DK Module
0 – Disable
1 – Enable
R Factory reset
Set to value to 1 (one) and exit to initiate
Specifications subject to change without notice
Zone Logic
The SMT-710 can control 2 zones in several ways depending on the needs of the
project and whether the second zone (Zone 2 has a temperature sensor fitted.
You must enable Zone control by turning DIP 8 to the on position while the
unit Control card is NOT powered.
The Zone 2 temperature sensor is automatically detected by the SMT-710 system.
The Zone 2 temperature sensor is wired to the Z2 temperature sensor input on
the Unit Card.
Option 1 – Zone 2 sensor is NOT installed Zone 1 and zone 2 is assumed to be
the same temperature and the heating and cooling is controlled based on the
set temperature and the temperature measured by the wall controller ( Zone 1
temperature). The zone selection switches simply open and close the various
zone dampers. This sends conditioned air to whatever zone (s) are selected.
Option 2 – Zone 2 sensor is installed Zone 1 and Zone 2 temperature are
individually measured by the SMT-710 and the Zone temperatures will be
individually maintained to the temperature as set on the wall controller.
The Zone 1 and 2 damper(s) will automatically open or close and the Air
Conditioning will be controlled to ensure both zone temperatures are
maintained.
Zone Limit Control The SMT-710 can be set to ensure that at least one zone is
open at all times or permit both zones to be closed if a common zone is
available for example. Zone control management has several options as shown in
the installer option menu, option 38.
Temperature Display The SMT-710 will, by default display Zone 1 temperature.
If you have the zone 2 temperature sensor fitted and only zone 2 selected,
then the wall controller will display the zone 2 temperature.
If at any time you wish to see zone 2 temperature press and hold the zone 2
select button for 2 seconds and the Zone 2 temperature will be displayed for 4
seconds. If the zone 2 sensor is not fitted the SMT-710 wall controller will
display Dash Dash.
Assignable Input
The SMT-710 has a universal input that can be assigned one of several
functions. See Installer option 33 over.
This input will accept a VOLT FREE dry contact input a standard Smart Temp 10K
NTC thermistor input. There are several options available to the assignable
Input as detailed in the installer menu option number 33.
Remote Input (Wall Controller T T Terminals) The SMT-710 Wall Controller has a
remote Aux input with options defined in the Installer menu option 32. This
input will accept a VOLT FREE dry contact or a standard Smart Temp 10K NTC
sensor
Indicator LEDS The SMT-710 UCC (Unit Control Card) has several LEDS that show
Power is available (blinking when receiving data), whether the card is calling
for heating, cooling or fan and what Zone is open. These indicator LEDS should
be the first thing considered when diagnosing any faults.
Typical Zone Sensor Wiring Zone 2 Sensor
RS1-02
R C A B T T Power
0 H C F 0 Ass Ass
In+ In- O-10V Outputs
Heat Cool Fan
Z1 Z2
Power Data
0-10V Heat Cool Fan
Aux Input Z2 Sensor
SMT-710 Control Card
Typical Zone Damper Wiring
Zone 1 Damper Close Zone 1 Damper Open
Zone Common Zone 2 Damper Close Zone 2 Damper Open
Power Supply
Z1 NC Z1 NO Zone Com Z2 NC Z2 NO
Belimo Damper
1 2 3
1 2 3
Typical Auxiliary Inputs
R 24 VAC Active C 24 VAC Common
A Data A B Data B
0V / Common 0
0-10V Heat H
0-10V Cool C
0-10V Fan F
0V / Common 0
Assignable Input
Ass In+
0V / Common
Ass In-
T Zone 2 Temp Sensor
T Zone 2 Temp Sensor
O-10V Outputs O-10V Outputs
Volt Free Switch
R 24 VAC Active C 24 VAC Common
A Data A B Data B
0V / Common 0
0-10V Heat H
0-10V Cool C
0-10V Fan F
0V / Common 0
Assignable Input
Ass In+
0V / Common
Ass In-
T Zone 2 Temp Sensor
T Zone 2 Temp Sensor
Temp Sensor
Condensed Specifications
Power Requirement
12 AC or DC to 28V AC / DC
Recommended Transformer
SZ-PS 24V 48VA
Relay Rating
6A at 240V max (15A Total fused)
Temperature Sensor type
10K NTC Type II (RS-01/2)
Maximum Z2 sensor run
10M Un-screened (30M Max)
Backlight
White LED
Wall Controller Size
110 x 105 x 38 mm
Relay Box Size
145 x 112 x 66
Storage Conditions (max)
-5 to 80c @ 90% RH (Non Condensing)
Operating Conditions (Max)
0 t0 45c @ 90% RH (Non Condensing)
Warranty
2 Years – RTB
All rights reserved – Specifications subject to change without notice
References
- Smart Temp Thermostats and Zoning Solutions | Australia
- Smart Temp Thermostats and Zoning Solutions | Australia
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>