Danfoss PT1000 Ally Programmable Wireless Control System User Guide
- June 13, 2024
- Danfoss
Table of Contents
Danfoss PT1000 Ally Programmable Wireless Control System
Introduction
Segment
This application guide covers the use Danfoss Ally™.
Overview of the units in a Danfoss Ally™ system
Danfoss Ally™ Gateway
The Danfoss Ally™ Gateway is a programmable, wireless control system that
connects all the Danfoss Ally™ devices to the internet and intelligently
controls your heating via a free app downloadable from Google Play and App
Store.
Danfoss Ally™ Radiator Thermostat
Danfoss Ally™ Radiator Thermostat is a connected radiator thermostat for
residential use.
It is a Zigbee 3.0 certified product, compatible with Danfoss Ally™ Gateway
and with third party systems using Zigbee protocol.
Danfoss Ally™ Room Sensor
Danfoss Ally™ Room Sensor measures the temperature and humidity in the room
and makes sure each radiator delivers the exact amount of heat needed for
temperature perfection.
Danfoss Ally™ Zigbee repeater
Is used for extending the wireless transmission range between Danfoss Ally™
Gateway and other units in a system.
Danfoss Icon™/Icon2™
Advanced room controls for hydronic floor heating and other applications with
actuators.
Designed like a light switch to complement the interior.
Number of units in a Danfoss Ally™ system
When building a Danfoss Ally™ system it is important to remember that the total number of units for the one Danfoss Ally™ Gateway must not exceed 128 mains and 32 battery powered devices.
Danfoss Ally™ Radiator Thermostat | 32 units |
---|
Danfoss Ally™ Room Sensor
Danfoss Ally™ Zigbee Repeater| 128 units
Danfoss Icon™ Zigbee Module| 20 units
Danfoss Icon™ Master Controller (floor Heating)| 20 units
Danfoss Icon™ Room Thermostat| 128 units
Devices per room| 128 units
Devices per one gateway| 128 units
Rooms per one gateway| Unlimited
Homes/Families| Unlimited
Best practices
Danfoss Ally™ Radiator Thermostats are masters in temperature regulation, but
if your radiator is hidden behind a curtain or a piece of furniture, it is
recommended to install Danfoss Ally™ Room Sensor to your set-up. Doing this
you will achieve a perfect indoor climate. The small and discrete room sensor
measures both temperature and humidity, and communicates back to the Danfoss
Ally™ Gateway.
Do not install Danfoss Ally™ Room Sensor on outer walls or where it will be
subject to direct sunlight.
The installation height should be 1,5 m minimum from the floor surface. The room sensor needs to be at least 0,5m away from doors and windows.
In wet rooms Danfoss Ally™ Room Sensor RS shall be installed according to
local building regulations.
Danfoss Ally™ Radiator Thermostat
The batteries on the Danfoss Ally™ Radiator Thermostat last up to two years. A
month before the battery is completely discharged, a low battery symbol
appears on the thermostat’s display and PUSH notifications inform you that it
is time to replace the batteries. A good tip is to set a calendar reminder for
2 years in the future, where you change all the batteries at once – even if
they have not necessarily run out yet.
If you do not change the batteries before they run completely dry, the
thermostat will open slightly and thus ensure that heat constantly flows
through the radiator. This is a safety mode to ensure that frost damage does
not occur if the thermostat is placed in an otherwise cold room.
General Guidelines
Heat supply
If the heating system has been optimized for constant set temperature around
the clock, you may need to adjust the settings when working with setback
periods. When changing the temperature from a low economy setting to a comfort
temperature, the system must be able to supply enough heat to raise the room
temperature at least 1 °C per hour to perform well. Compared to a steady
temperature the heating system must typically be able to supply 25% more heat,
but only for a short period of time during heat up.
How to achieve 25% extra capacity in a system that should run boost:
Limitations | Action |
---|---|
Max.ΔP and temperature reached: | Increase valve presetting |
Max. temperature and preset reached: | Increase pump pressure |
Max. preset and ΔP reached: | Increase water temperature |
NOTE: Maximum acceptable presetting, water temperature and pump
differential pressure settings are different from system to system and depend
on the application.
For radiator valves with pre-setting, balance the system to allow for enough
flow.
The supply line temperature at the radiator valves should be above 40 °C to
ensure optimal control.
Make sure that the supply water temperature and flow is adequate to provide
enough energy.
Increase the temperature or the pump level, if necessary.;
Functions
Danfoss Ally™ Radiator Thermostat has a built in function that senses if a window has been opened. It will automatically shut off the heat for 30 minutes, after which the heating in the room will automatically be restarted. If you have more than one radiator in the same room, only one of the thermostats has to register an open window, after which all the radiators in the same room will shut off.
Please note:
-
The radiator must be located in the immediate vicinity of the window (which it most often will). If the radiator is located e.g. 10 meters from the window, it may be difficult for the thermostat to sense a clear drop in temperature, which is needed for it to turn off the heat.
-
Between the finish of the “open window” period and the start of a new one there must be at least 45 minutes.
-
The first activation of the “open window” feature is 75 minutes after the battery insert.
-
If you live in a home without a ventilation system, we recommend that you ventilate the entire house twice daily for a minimum of 5 minutes by opening windows in opposite ends of the house.
-
If you have a Danfoss Ally™ Room Sensor installed, the open window function will be disabled. The Room Sensor cannot detect that a window is open and the system will continue the heating process
The pre-heat function ensures that the comfort temperature is reached at set time. The warm up time is continuously adjusted according to seasonal temperature changes.
-
Pre-heat function ensures that the wanted temperature is reached at the wanted time (here 20 °C at 07:00).
-
Pre-heat uses data from the previous 7 days to be able to reach the correct temperature at the right time.
-
Pre-heat is sensitive to large, rapid temperature changes.
Rooms
Covering the radiator – e.g. with furniture, curtains or a radiator cover – might cause heat to be accumulated around the thermostat.
Light curtain/furniture: You can use Radiator Thermostat, but function is
improved by using a Danfoss Ally™ Room Sensor.
Medium curtain/furniture: Use with Danfoss Ally™ Room Sensor.
Radiator cover: Use with Danfoss Ally™ Room Sensor.
If two radiators are placed within 40 cm of each other, the heat emission from
one radiator can affect the thermostat on the other radiator. In such cases it
is recommended to install Danfoss Ally™ Room Sensor.
Direct heat radiation from large radiators may disturb the Radiator
Thermostats ability to measure the room temperature correctly
To avoid this, mount the thermostat pointing away from the radiator. The
optimal solution is a Radiator Thermostat with a Danfoss Ally™ Room Sensor.
Danfoss do not recommend to use an angle adapter, instead the valve should be turned or replaced.
A fireplace in the room can affect the pre heat function of the Radiator
Thermostat and disturb the heating control. If you use your fireplace
regularly it is recommended to deactivate the Pre-Heat function. By
deactivating this function, Radiator Thermostat will work as a traditional
thermostat, but with a delay in heating up the room after the fire has burned
out.
NOTE: If the valve has been closed for a longer period there may be a delay in
heating up the room.
Sunlight from large windows in the room can affect the Pre-Heat function of
the Radiator Thermostat and disturb the heating control. Then it is
recommended to deactivate this function. By deactivating it, Danfoss Ally™
Radiator Thermostat will work as a traditional thermostat, but with a delay in
heating up the room after the heating from the sunlight has stopped.
Applications
Heating System with Central Boiler
A large gas, oil or pallet boiler which provides hot water to several households.
Recommendations:
- min. 40 °C supply temperature at the valve.
- sufficient heating capacity to increase the room temperature with 1 °C per hour.
- only radiator valves approved for Danfoss adapters.
Boiler turned off at night
If the boiler is turned off or has reduced temperature during the night, then
make sure that it is active when the Radiator Thermostat is programmed to
warm.
Weather compensation
If the boiler’s heating curve is set to have the Radiator Thernostats on
comfort temperature constantly, the curve must be increased in order to be
able to raise the room temperature after a setback period.
- If the setback periods are long, further increase might be necessary.
- If the economy periods are short, less increase can be sufficient.
Heating System with Boiler
A boiler with build-in or external domestic hot water tank can provide instant heat for the heating system, as well as for the domestic hot water.
Recommendations:
- min. 40 °C supply temperature at the valve.
- sufficient heating capacity to increase the room temperature with 1 °C per hour.
- only radiator valves approved for Danfoss adapters.
Boiler turned off at night
If the boiler is turned off or has reduced temperature during the night, then
make sure that it is active when the Radiator Thermostat is programmed to
warm.
Weather compensation
If the boiler’s heating curve is set to have the radiator thernostats on
comfort temperature
constantly, the curve must be increased in order to be able to raise the room
temperature after a setback period.
- If the setback periods are long, further increase might be necessary.
- If the economy periods are short, less increase can be sufficient
District Heating
District heating is generated in a centralized location and distributed to residential and commercial use.
Recommendations:
- min. 40 °C supply temperature at the valve.
- sufficient heating capacity to increase the room temperature with 1 °C per hour.
- only radiator valves approved for Danfoss adapters.
Weather compensation / ECL
If the boiler’s heating curve is set to have the radiator thermostats on
comfort temperature constantly, the curve must be increased in order to be
able to raise the room temperature after a setback period.
- If the setback periods are long, further increase might be necessary.
- If the economy periods are short, less increase can be sufficient.
Heat Pump
A heat pump is generating heating by transferring heat from a relatively low-
temperature reservoir, such as air or ground, to one at a higher temperature.
Recommendations:
- min. 40 °C supply temperature at the valve.
- sufficient heating capacity to increase the room temperature with 1 °C per hour.
- only radiator valves approved for Danfoss adapters.
Weather compensation
If the heat pump’s heating curve is set to have the radiator thermostats on comfort temperature constantly, the curve must be increased in order to be able to raise the room temperature after a setback period.
- If the setback periods are long, further increase might be necessary.
- If the economy periods are short, less increase can be sufficient.
NOTE: If system is installed during period with outside temperature > 10° C opening point will not be found until temperature drops below 7-8° C.0
Danfoss Icon™/Icon 2™ – room thermostats for floor heating
Danfoss Icon™ comes in 3 modular concepts to cover every application –
Wireless, 24V and 230V
| Wireless| 24V| 230V
---|---|---|---
| | | **
Thermostat models| Display + Display infrared + Dial| Display|
Programmable + Display + Dial
Thermostat versions| On-wall| On-wall + In-wall| On-wall + In-wall
Exchangeable frame| **| In-wall| In-wall
Icon App| | | **
Cooling options| Automatic + Manual| Automatic + Manual| Manual
Automatic balancing| **| |
Supply temp. control| | | **
Commissioning test| **| |
Communication| Wireless 2-way| Star / daisy chain bus| Wired 230V
Zones| Up to 3x 15 = 45| Up to 3x 15 = 45| Up to 1x 8 = 8
Danfoss Icon™ E-error codes description
Alarm code | Problem | Solution |
---|---|---|
Er03 | You have set-up a cooling application that requires a reference | |
room thermostat to be appointed. | Please go to the thermostat in the desired |
reference room and enter the thermostat installer menu. Set thermostat to
ON in ME.6 “reference room thermostat”.
Er05| Communication lost to Radio Module.| Please check that the cable
is properly connected in the Radio Module and Danfoss Icon™ Master Controller
24V.
Er06| Communication lost to room thermostat.| Identify the room
thermostat by looking at the flashing outputs on the Danfoss Icon™ Master
Controller 24V, or look at the thermostats. Wake up thermostat, then press on
the thermostat. Faling thermostat will say “NET ERR”.
In some cases it is necessary to add a repeater to establish a better wireless
communication between the Master Controller and Thermostat. Replace batteries
on room thermostat and per- form a network test (activate NET TEST in menu
ME.3 on room thermostat).
Er07| Communication lost to Slave Controller.| If wireless, check Radio
Module connection to Danfoss Icon™ Master Controller 24V. If wired system,
check the wire connecting the controllers.
Er08| Communication lost from Slave to Master Controller.| If wireless,
check Radio Module connection to Danfoss Icon™ Master Controller 24V. If wired
system, check the wire connecting the controllers.
Er10| Communication lost to Repeater.| Check that the repeater is
plugged into outlet / has not been removed and outlet is ON.
Er11| Communication lost to Expansion Module.| Check that Expansion
Module is slidded fully into place.
_ Note! The Master controller must be turn off and on _again in order to
register the expansion module.
Er12| Actuator defective. The defective actuator output is flashing.|
Replace actuator.
Er14| A Danfoss Icon™ Master Controller cannot be included as (become)
a Slave Controller because one or more room thermostats, repeaters or Danfoss
Icon™ Master Controller 24V have all ready been included.| This Danfoss Icon™
Master Controller 24V has to be factory reset to become a Slave Controller.
(See description in chapter ”Reset or replace a Danfoss Icon™ Master
Controller”).
Er16| This application requires a specific actuator output to be
available.| You have already assigned this output to a room thermostat, or the
output has not yet had an actuator fitted. Please uninstall RT from TWA, it
must be available to the application chosen (or fit actuator – if this was not
yet done).
Er17| External PT1000 sensor not fitted, or defective.| Check sensor and
replace if necessary
Note! Remember to ensure that the Master Control- ler is connected due to risk of electric shock.
How to install Danfoss Icon™
Danfoss Icon™ Display is a room thermostat especially designed for floor heating systems. It comes in four different designs to suit markets worldwide. Danfoss Icon™ Display is very intuitive and easy to use. Just set your desired comfort temperature, and the thermostat will control the room temperature in accordance with your setting.
Wake up the thermostat
Touch the screen to wake up Danfoss Icon™ Display.
The actual room temperature is displayed. Touch to return to the previous
screen. The screen turns off after 10 seconds without any action.
Set the temperature
Touch to set the desired room temperature.
The temperature flashes to indicate setting is in progress. Confirm your
setting by touching
Reset to default factory settings
Press simultaneously for at least 3 seconds to reset Danfoss Icon™ Display to
the default factory settings. The display toggles between and . Confirm by
touching
Menus
Wake up the thermostat. Press for 3 seconds to open the User menus and .
Toggle the menus with . Choose menu with . (To open the Installer menus and ,
press again for 3 seconds)
Temperature limitation
and toggles with the temperature on the screen. Set highest temperature with
or .
and toggles with the temperature on the screen. Set lowest temperature with or
.
Confirm your choice with .
Default temperature range: 5 to 35° C.
Product ID
Production code.
Menu 3 and 4 are only relevant for the installer
Set actuator type
Choose between Normally Closed or Normally Open with .
Confirm with .
Set heat emission characteristics of the floor
Choose Fast Medium or Slow heat emission characteristics with . Confirm with
.
Danfoss Icon2™ specifications
Danfoss Icon2™ comes in 3 modular concepts to cover every application –
Wireless, common and wired solution.
With Danfoss Icon2™ you can chose between 3 different Wireless Thermostats.
Danfoss Icon2™ Sensor
Danfoss Icon2™ RT Display
Danfoss Icon2™ RT Featured
Code number| Version| Display| Humidity sensor| Floor
sensor| Tool-free mounting| Open Zigbee
---|---|---|---|---|---|---
088U2120| Danfoss Icon2™ Sensor|
÷
|
+
|
÷
|
+
|
+
088U2121| Danfoss Icon2™ RT|
+
|
+
|
÷
|
+
|
+
088U2122| Danfoss Icon2™ Featured RT|
+
|
+
|
+c
|
+
|
+
Available +
Optional (+)
Not available ÷
For the Danfoss Icon2™ Wired Thermostat you can chose between 4 different versions.
Icon™ 24V RT
Code number| Version| Display| Humidity sensor| Floor
sensor| In-wall mounting| Switchable frames
---|---|---|---|---|---|---
088U2125| Danfoss Icon2™ 24V RT, In-wall 80×80|
+
|
÷
| (+)|
+
|
+
088U2126| Danfoss Icon2™ 24V RT, In-wall 86×86|
+
|
÷
|
(+)
|
+
|
+
088U2127| Danfoss Icon2™ 24V RT, In-wall (Feller)|
+
|
÷
|
(+)
|
+
|
+
088U2128| Danfoss Icon2™ 24V RT, On-wall|
+
|
÷
|
(+)
|
÷
|
÷
Available +
Optional (+)
Not available ÷
Danfoss Icon2™ Main Controller Basic and Advanced features
Feature | Icon2™ MC Basic | Icon2™ MC Advanced |
---|---|---|
“Ease of installation” features |
+
|
+
Wireless and Wired thermostats|
+
|
+
Floor temperature control|
+c
|
+
Multiple heat emitter control|
+
|
+
Zigbee compatibility to Ally and 3rd parties|
+
|
+
Setup and commissioning via Commissioning App|
+
|
+
Handover report via commissioning app|
+
|
+
Multiple Main Controllers connected|
+
|
+
Automatic Hydronic Balancing|
+
|
+
HP optimizer function|
+
|
+
Manual floor cooling|
+
|
+
Advanced floor cooling applications|
÷
|
+
Flow temperature control applications|
÷
|
+
NOTE: To get more information about how to install Danfoss Icon2™ MC and powerline diagrams please, use the installer app as a guideline for installation. Please find “Installer app“ from Danfoss on Google Play and App store.
DanfossA/S
Climate Solutions• danfoss.com
• +45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material.
Danfoss reserves the right to alter its products without notice. This also
applies to products ordered but not delivered provided that such alterations
can be made without changes to form, tit or function of the product.
All trademarks in this material are property of Danfoss A/5 or Danfoss group
companies.
Danfoss and the Danfoss logo are trademarks of Danfoss A/5. All rights
reserved.
AB440847594423en-000101
© Danfoss I FEC I 2023.07 I 19
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>