Danfoss VLT AutomationDrive FC 360 Frequency Inverter User Guide

June 13, 2024
Danfoss

Danfoss VLT AutomationDrive FC 360 Frequency Inverter

Danfoss VLT AutomationDrive FC 360 Frequency Inverter

Introduction

This operating guide provides necessary information for qualified personnel to install and commission the AC drive. Read and follow the instructions to use the drive safely and professionally.

Do not dispose of equipment containing electrical components together with domestic waste. Collect it separately in accordance with local and currently valid legislation.

Safety

Pay particular attention to the safety instructions and general warnings to avoid the risk of death, serious injury, and equipment or property damage.

Symbol

HIGH VOLTAGE

AC drives contain high voltage when connected to AC mains input.

UNINTENDED START

The motor may start from control panel, I/O inputs, or fieldbus at any time, when the drive is connected to the AC mains.

DISCHARGE TIME

The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are o .

  • Stop the motor, and disconnect AC mains, permanent magnet type motors.
  • Wait for the capacitors to discharge fully and measure it before performing any service or repair work.
  • The minimum waiting time is 20 minutes.

LEAKAGE CURRENT

Leakage currents of the drive exceed 3.5 mA. Make sure that the minimum size of the ground conductor complies with the local safety regulations for high touch current equipment.

Installation

Mechanical Dimensions
  • Illustration 1: Mechanical Dimensions, Enclosure Sizes J8–J9
    Illustration 1: Mechanical Dimensions, Enclosure Sizes
J8–J9

Table 1: Power Ratings, Dimensions, and Weights for Enclosure Sizes J8–J9

Enclosure size (IP20)| Power [kW (hp)]| Height [mm (in)]| Width [mm (in)]
---|---|---|---
3×380–480 V| A| A(1)| a| B| b| b1
J8| 110–160 (150–250)| 889 (35.0)| 909 (35.8)| 844 (33.2)| 250 (9.8)| 180 (7.1)| 200 (7.9)
J9| 200–315 (300–450)| 1096 (43.1)| 1122 (44.2)| 1051 (41.4)| 350 (13.8)| 280 (11.0)| 271 (10.7)
Enclosure size (IP20)| Depth [mm (in)]| Mounting hole [mm (in)]| Center of gravity [mm (in)]| Maximum weight [kg (lb)]
C| D| E| F| G
J8| 375 (14.8)| 11 (0.4)| 128 (5.0)| 495 (19.5)| 148 (5.8)| 98 (216)
J9| 375 (14.8)| 11 (0.4)| 176 (6.9)| 611 (24.1)| 148 (5.8)| 164 (362)

Note: (1) Including decoupling plate.

Removing the Front Cover

Procedure:

Step 1: Loosen and remove the 2 screws on the front cover.
Step 2: Disconnect the front cover from the hooks.

  • Illustration 2: Removing the Front Cover
    Removing the Front Cover
Connecting to Mains, Motor, Control Terminals, and Relays
  • Illustration 3: Connecting to Mains, Motor, Control Terminals, and Relays
    Illustration 3: Connecting to Mains, Motor, Control Terminals, and
Relays
Control Terminals
  • Illustration 4: Control Terminals
    Illustration 4: Control Terminals

Specifications

Table 2: Electrical Data for Normal Overload, Mains Supply 3×380–480 V AC

Drive Q110 Q132 Q160 Q200 Q250 Q315
Enclosure size J8 J8 J8 J9 J9 J9

Normal overload=110% current during 60 s
Typical shaft output at 400 V [kW]| 110| 132| 160| 200| 250| 315
Typical shaft output at 460 V [hp]| 150| 200| 250| 300| 350| 450
Output current (3-phase)
Continuous (at 400 V) [A]| 212| 260| 315| 395| 480| 588
Intermittent (60 s overload) (at 400 V) [A]| 233| 286| 347| 435| 528| 647
Continuous (at 460 V) [A]| 190| 240| 302| 361| 443| 535
Intermittent (60 s overload) (at 460 V) [A]| 209| 264| 332| 397| 487| 589
Continuous kVA (at 400 V) [kVA]| 147| 180| 218| 274| 333| 407
Continuous kVA (at 460 V) [kVA]| 151| 191| 241| 288| 353| 426
Maximum input current
Continuous (at 400 V) [A]| 204| 251| 304| 381| 463| 567
Continuous (at 460 V) [A]| 183| 231| 291| 348| 427| 516
Maximum number and size of cables per phase
Mains and motor [mm (AWG)]| 2×95 (2×3/0)| 2×185 (2×350 mcm)
Maximum external mains fuses [A]| 315| 350| 400| 550| 630| 800
Estimated power loss at 400 V [W]| 2559| 2954| 3770| 4116| 5137| 6674
Estimated power loss at 460 V [W]| 2261| 2724| 3628| 3569| 4566| 5714
Efficiency [%]| 98
Output frequency [Hz]| 0–590
Heat sink over temperature trip [°C (°F)]| 110 (230)
Control card over temperature trip [°C (°F)]| 75 (167)| 80 (176)

Table 3: Electrical Data for High Overload, Mains Supply 3×380–480 V AC

Drive H90K H110 H132 H160 H200 H250
Enclosure size J8 J8 J8 J9 J9 J9

High overload=150% current during 60 s
Typical shaft output at 400 V [kW]| 90| 110| 132| 160| 200| 250
Typical shaft output at 460 V [hp]| 125| 150| 200| 250| 300| 350
Output current (3-phase)
Continuous (at 400 V) [A]| 177| 212| 260| 315| 395| 480
Intermittent (60 s overload) (at 400 V) [A]| 266| 318| 390| 473| 593| 720
Continuous (at 460 V) [A]| 160| 190| 240| 302| 361| 443
Intermittent (60 s overload) (at 460 V) [A]| 240| 285| 360| 453| 542| 665
Continuous kVA (at 400 V) [kVA]| 123| 147| 180| 218| 274| 333
Continuous kVA (at 460 V) [kVA]| 127| 151| 191| 241| 288| 353
Maximum input current
Continuous (at 400 V) [A]| 171| 204| 251| 304| 381| 463
Continuous (at 460 V) [A]| 154| 183| 231| 291| 348| 427
Maximum number and size of cables per phase
Mains and motor [mm (AWG)]| 2×95 (2×3/0)| 2×185 (2×350 mcm)
Maximum external mains fuses [A]| 315| 350| 400| 550| 630| 800
Estimated power loss at 400 V [W]| 2031| 2289| 2923| 3093| 4039| 5004
Estimated power loss at 460 V [W]| 1828| 2051| 2089| 2872| 3575| 4458
Efficiency [%]| 98
Output frequency [Hz]| 0–590
Heat sink over temperature trip [°C (°F)]| 110 (230)
Control card over temperature trip [°C (°F)]| 75 (167)| 80 (176)

Ambient Conditions

J8–J9 enclosure size IP20/Chassis
Vibration test (standard) 0.7 g
Relative humidity 5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during

operation)
Aggressive environment (IEC 60068-2-43) H2S test| Class Kd
Aggressive gases (IEC 60721-3-3)| Class 3C3
Test method according to IEC 60068-2-43| H2S (10 days)
Ambient temperature (at SFAVM switching mode)

  • with derating
  • with full output power of typical EFF2 motors (up to 90% output current)
  • at full continuous FC output current

|

Maximum 55 °C (131 °F)
Maximum 50 °C (122 °F)
Maximum 45 °C (113 °F)

Minimum ambient temperature during full-scale operation| -15 °C (5 °F)
Minimum ambient temperature at reduced speed performance| -20 °C (-4 °F)
Temperature during storage/transport| -25 to +65/70 °C (-13 to +149/158 °F)
Maximum altitude above sea level without derating| 1000 m (3281 ft)
Maximum altitude above sea level with derating| 3000 m (9842 ft)
Energy efficiency class| IE2

Mounting Clearance

Enclosure size| Minimum mounting clearance [Maximum temperature 50 °C (122 °F)]
---|---
J8 and J9| Above and below: 225 mm (9 in)

EMC Compatibility and Motor Cable Length

EMC standard, Emission/Immunity Category C3/EN/IEC 61800-3
Maximum motor cable length, shielded Category C3/ 150 m (492 ft)
Maximum motor cable length, unshielded 300 m (984 ft)
Maximum cross-section to control terminals, rigid wire 1.5 mm2/16 AWG (2×0.75

mm2)
Maximum cross-section to control terminals, flexible cable| 1 mm2/18 AWG
Maximum cross-section to control terminals, cable with enclosed core| 0.5 mm2/20 AWG
Minimum cross-section to control terminals| 0.25 mm2/23 AWG

Programming

Local Control Panel (LCP)
  • Illustration 5: Local Control Panel (LCP 21 and LCP 23)
    Illustration 5: Local Control Panel \(LCP 21 and LCP
23\)

Functional Section A: Display

Table 4: Display Function

Number Function
1 The setup number shows the active setup and the edit setup.
  • For LCP 21: The setup number shows the active setup and the edit setup. If the same setup acts as both active and edit setup, only that setup number is shown (factory setting).
  • For LCP 23, the setup number shows on the upper right corner in the status mode. For example, “1(2)” means the active setup is “1” and the editing setup is “2”.

2|

  • LCP 21 shows only parameter number.
  • LCP 23 shows both parmenter number and name.

3| Parameter value.
4| Motor direction indicated by a small arrow pointing either clockwise or counterclockwise. For LCP 23, it only shows in status menu on the upper right corner of the screen.
5| The triangle indicates if the LCP is in Status, Quick Menu, or Main Menu.

Functional Section B: Menu Key

Press [Menu] to select among Status, Quick Menu, or Main Menu.

Functional Section C: Indicator Lights (LEDs) and Navigation Keys

Table 5: Indicator Lights (LEDs)

Number Indicator Light Function
6 On Green Turns on when the drive receives power from the mains voltage, a

DC bus terminal, or a 24 V external supply.
7| Warn.| Yellow| Turns on when warning conditions are met. Text is shown in the display area identifying the warning.
8| Alarm| Red| Flashes when a fault condition occurs. Text is shown in the display area identifying the alarm.

Table 6: Navigation Keys

Number Key Function
9/13 Up/Down (1) Switches among parameter groups, parameters, and within

parameters. (2) Increases or decreases parameter values. (3) Sets local reference.
10| [Back]| Moves to the previous step or layer in the navigation structure.
11| Right| Moves from left to right within the parameter value to change each digit individually.
12| [OK]| Selects a parameter and accepts changes to parameter settings.

Functional Section D: Operation Keys and Indicator Lights (LEDs)

Table 7: Operation Keys and Indicator Lights (LEDs)

Number Key Function
14 [Hand On] (1) Starts the drive in local control. (2) An external stop

signal via control input or serial communi- cation overrides the local hand on command.
15| [O /Reset]| (1) Stops the motor but does not remove power to the drive. (2) Resets the drive manually after a fault has been cleared. (3) In alarm mode, the alarm is reset when the alarm condition is removed.
16| [Auto On]| Puts the system in remote operational mode, in which the drive only respond to an external start command via control terminals or bus communication.
Symbol

[2] Coast inverse is the default option for parameter 5-12 Terminal 27 Digital Input. If there is no 24 V supply to terminal 27, [Hand On] does not start the motor. Connect terminal 12 to terminal 27.

Automatic Motor Adaptation (AMA)
  • Via running AMA in VVC+ mode, the drive builds a mathematical model of the motor to optimize compatibility between drive and motor, and thus enhances the motor control performance.
  • Some motors may be unable to run the complete version of the test. In that case, select [2] Enable Reduced AMA in parameter 1-29 Automatic Motor Adaptation (AMA).
  • For best results, run the following procedure on a cold motor.

Procedure:

  1. Set motor data in parameter group 1-** Load and Motor according to the motor nameplate.
  2. Connect terminal 27 to terminal 12 (24 V voltage) or choose [0] No operation in parameter 5-12 Terminal 27 Digital Input.
  3. Set [1] Enable Complete AMA or [2] Enable Reduced AMA for parameter 1-29 Automatic Motor Adaptation (AMA).
  4. Press the [Hand On] key, the test runs automatically and the main display indicates when it is completed.

Troubleshooting

Table 8: Warning and Alarm Code List

Number| Description| Warning| Alarm| Trip lock| Cause
---|---|---|---|---|---
2| Live zero error| X| X| –| Signal on terminal 53 or 54 is less than 50% of the values set in parameter 6-10 Terminal 53 Low Voltage , parameter 6-12 Terminal 53 Low Current , parameter 6-20 Terminal 54 Low Voltage , and parameter 6-22 Terminal 54 Low Current.
3| No motor| X| –| –| No motor has been connected to the output of the drive, or 1 motor phase is missing.
4| Mains phase loss(1)| X| X| X| Missing phase on the supply side, or the voltage imbalance is too high. Check the supply voltage.
7| DC overvoltage(1)| X| X| –| DC-link voltage exceeds the limit.
8| DC undervoltage(1)| X| X| –| DC-link voltage drops below the voltage warning low limit.
9| Inverter overloaded| X| X| –| More than 100% load for too long.
10| Motor ETR over temperature| X| X| –| Motor is too hot due to more than 100% load for too long.
11| Motor thermistor over temperature| X| X| –| Thermistor or thermistor connection is disconnected, or the motor is too hot.
12| Torque limit| X| X| –| Torque exceeds value set in either parameter 4-16 Torque Limit

Motor Mode or parameter 4-17 Torque Limit Generator Mode.

13| Overcurrent| X| X| X| Inverter peak current limit is exceeded. For J1–J6 units, if this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals.
14| Ground fault| –| X| X| Discharge from output phases to ground.
16| Short circuit| –| X| X| Short circuit in motor or on motor terminals. For J7 units, if this alarm occurs on power-up, check whether power cables are mistakenly connected to the motor terminals.
17| Control word timeout| X| X| –| No communication to the drive.
18| Start failed| –| X| –| –
25| Brake resistor short- circuited| –| X| X| Brake resistor is short- circuited, thus the brake function is disconnected.
26| Brake overload| X| X| –| The power transmitted to the brake resistor over the last 120 s exceeds the limit. Possible corrections: Decrease brake energy via lower speed or longer ramp time.
27| Brake IGBT/Brake chopper short-circuited| –| X| X| Brake transistor is short-circuited, thus brake function is disconnected.
28| Brake check| –| X| –| Brake resistor is not connected/working.
30| U phase loss| –| X| X| Motor phase U is missing. Check the phase.
31| V phase loss| –| X| X| Motor phase V is missing. Check the phase.
32| W phase loss| –| X| X| Motor phase W is missing. Check the phase.
34| Fieldbus fault| X| X| –| PROFIBUS communication issues have occurred.
Number| Description| Warning| Alarm| Trip lock| Cause
---|---|---|---|---|---
35| Option fault| –| X| –| Fieldbus or option B detects internal faults.
36| Mains failure| X| X| –| This warning/alarm is only active if the supply voltage to the drive is lost and parameter 14-10 Mains Failure is NOT set to [0] No Fun ction.
38| Internal fault| –| X| X| Contact the local supplier.
40| Overload T27| X| –| –| Check the load connected to terminal 27 or remove short-circuit connection.
41| Overload T29| X| –| –| Check the load connected to terminal 29 or remove short-circuit connection.
46| Gate drive voltage fault| –| X| X| –
47| 24 V supply low| X| X| X| 24 V DC may be overloaded.
50| AMA calibration| –| X| –| –
51| AMA check Unom and Inom| –| X| –| Wrong setting for motor voltage and/or motor current.
52| AMA low Inom| –| X| –| Motor current is too low. Check the settings.
53| AMA big motor| –| X| –| The power size of the motor is too large for the AMA to operate.
54| AMA small motor| –| X| –| The power size of the motor is too small for the AMA to operate.
55| AMA parameter range| –| X| –| The parameter values of the motor are outside of the acceptable range. AMA does not run.
56| AMA interrupt| –| X| –| The AMA is interrupted.
57| AMA timeout| –| X| –| –
58| AMA internal| –| X| –| Contact the local supplier.
59| Current limit| X| X| –| The drive is overloaded.
60| External Interlock| –| X| –| –
61| Encoder loss| X| X| –| –
63| Mechanical brake low| –| X| –| Actual motor current has not exceeded release brake current within start delay time window.
65| Control card temp| X| X| X| The cutout temperature of the control card is 80 °C (176 °F).
67| Option module configuration has changed| –| X| –| One or more options have either been added or removed since the last power-down.
69| Power card temp| X| X| X| –
70| Illegal FC config| –| X| X| –
80| Drive initialized to default value| –| X| –| All parameter settings are initialized to default settings.
87| Auto DC brake| X| –| –| Occurs in IT mains when the drive coasts and the DC voltage is higher than 830 V. Energy on DC-link is consumed by the motor. This function can be enabled/disabled in parameter 0-07 Auto DC Braking.
88| Option detection| –| X| –| A change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen configuration and the option layout has been changed.

  • To apply the change, enable option layout changes in parameter 14-89 Option Detection.
  • Alternatively, restore the correct option configuration.

90| Feedback monitor| X| X| –| A feedback fault is detected by option B.
95| Broken belt| X| X| –| –
99| Locked rotor| –| X| –| –
101| Flow/pressure information missing| –| X| X| –
120| Position control fault| –| X| –| –
124| Tension limit| –| X| –| –
126| Motor rotating| –| X| –| –
127| Back EMF too high| X| –| –| Try to start PM motor which is rotating in an abnormal high speed.
250| New spare part| –| X| X| –
251| New type code| –| X| X| –

Note:
(1) These faults may be caused by mains distortions. Installing a Danfoss line lter may rectify this problem.
(2) An (X) marked in the above table indicates that the warning or alarm has occurred. A warning precedes an alarm.

Accessories and Spare Parts

Accessories and spare parts| Code number| Accessories and spare parts| Code number
---|---|---|---
(1)| VLT® PROFIBUS DP MCA 101| 134B6778| (6)| VLT® graphical control panel LCP 23| 132B0801
(2)| VLT® PROFINET MCA 120| 134B6779| (7)| VLT® numeric control panel LCP 21| 132B0254
(3)| VLT® encoder input MCB 102| 132B0282| (8)| Remote mounting kit for LCP with cable, 3 m| 132B0102
(4)| VLT® resolver input MCB 103| 132B0283| (9)| LCP remote mounting cable, 3 m| 132B0132
(5)| VLT® 24 V DC supply MCB 107| 130B1208| (10)| Control card for FC 360 J8-J9| 132G0279

Note: (1) – (9) are accessories, and (10) is spare part. For more spare parts, contact Danfoss.

Technical Documentation

Scan the QR code to access more technical documents for the drive. Or, after scanning the QR code, click Global English on the website to select your local region’s website, search FC 360 to and the documents with your own languages.

Customer Support

Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
drives.danfoss.com

Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material.
Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without sub sequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.
Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals