Q-TRAN Q-SET+QZ-30 Direct Burial Transformer Installation Guide
- June 13, 2024
- Q-TRAN
Table of Contents
INSTALLATION
Q-VAULT – Q-SET+QZ-ND
Q-SET+QZ-30 Direct Burial Transformer
| • 3426-94 Luminaires – Landscape Lighting Systems – Certified to UL – 1838
Standard.
• 3425-95 Luminaires – Low Voltage Lighting Systems – Certified to UL – 2108
Standard.
• 3425-96 Luminaires – Component Hydromassage – Certified to UL – 379 Pool &
Spa Standard.
---|---
| • 3426-04 Luminaires – Landscape Lighting Systems – Component (including
Hydromassage).
• 3425-15 Luminaires – Low Voltage Lighting Systems.
- For supply connections use wire rated for at least 90°C
- Suitable for in-ground installation.
- Use dimmers rated for magnetic or electronic low voltage load.
- Not for installation to conduit extending directly to an underwater pool light forming shell. In line Pool and Spa rated junction box required.
- Suitable for use with submersible luminaries
- Use dimmers rated for appropriate lighting load.
- Suitable for direct burial use.
- Warning: risk of fire – if installation involves running wiring through a building structure, special wiring methods are needed. Consult National and Local Codes.
Q-SET LOW VOLTAGE LUMINAIRE POWER SUPPLY
MODEL
NUMBER| OUTPUT
CLASS| MAX LAMP
LOAD| PRIMARY
VOLTS| LAMP
VOLTS
---|---|---|---|---
Q-SET+QZ-30
Q-SET+QZ-60
Q-SET+QZ-96| CLASS 2
CLASS 2
CLASS 2| 30W
60W
96W| 120V/277 (60Hz)
120V/277 (60Hz)
120V/277 (60Hz)| 24VDC
24VDC
24VDC
CSA LISTING
| | OUTDOOR Under 30 Volts = LV Wire Burried 0” to 6”
---|---|---
| Q-SET+QZ-30
Q-SET+QZ-60
Q-SET+QZ-96| Outdoor Landscape Lighting – Under 30 Volts
CSA Certified for both the U.S. and Canada to the UL-1838 Standard for
Landscape Lighting with in-ground enclosure and component power supply
operating at less than 30VDC. This listing allows for the LV Q-WIRE to be
installed 0” to 6” underground.
Pool & Spa – Under 30 Volts
CSA Certified for the U.S. to the UL-379 Pool & Spa Power Supply Standard.
This listing is intended for
power supplies used to power fountain, swimming pool and spa luminaires
operating at less than 30V.
| | OUTDOOR 15 to 30 Volts = LV Wire burried 18”
| Q-SET+QZ-30
Q-SET+QZ-60
Q-SET+QZ-96| Outdoor Landscape Lighting – 15 to 30 Volts CSA Certified for
both the U.S. and Canada to UL-2108 Standard with a listing of “Low Voltage
Luminaire Power Supply” for lamps operating at 12 or 24 volts where the
secondary voltage is between 15 to 30 volts. Please note that the secondary
wiring must be installed 18” below grade per the N.E.C.
| | INDOOR LV Lighting under 30 Volts
| Q-SET+QZ-30
Q-SET+QZ-60
Q-SET+QZ-96| Indoor Open Conductor Systems – Under 30V
CSA Certified for both the U.S. and Canada to UL-2108 Standard as a “Low
Voltage Luminaire Power Supply” for lamps operating at 12V or 24V allows for
live conductor lighting equipment mounted above 7 feet and other types of LV
Lighting equipment, per N.E.C. Article 411. When tested in conjunction with
open conductor lighting system.
NOTE: Refer to the last page.
Q-VAULT 120/277V (50/60HZ) – 24V
FOR CONDUIT CONNECTION
WARNING – RISK OF SHOCK. Install power unit 5 feet (1.5 m) or more from the
pool or spa and 10 feet (3.05 m) or more from a fountain. Where the power unit
is installed within 10 feet (3.05 m) of a pool or spa, connect unit to GFCI
protected branch circuit.
FOR POWER SUPPLY CORD CONNECTION
WARNING – RISK OF SHOCK. Installed power unit 5 feet (1.5M) or more from the
pool, spa, or fountain. Where the power unit is installed (a) indoors within
10 feet (3.05) of a pool, spa, or fountain or (B) outdoors, connect power unit
to a receptacle protected by a GFCI.
WARNING – RISK OF FIRE. If installation requires running wire through a
building structure, special wiring methods are needed. Contact a qualified
electrician.
WARNING – Outdoor Cord-connected unit shall be connected to a GFCI
protected hooded flush type cover plate receptacle marked “Wet Location”.
WARNING – Do not use extension cords.
The main Secondary Wiring is intended for shallow burial – less than 6 inches
(152 mm)
For Supply connections use wire rated for at least 90C.
- SUITABLE FOR INDOOR / OUTDOOR USE
- SUITABLE FOR USE WITH SUBMERSIBLE LUMINAIRES OR SUBMERSIBLE PUMPS
- SUITABLE FOR USE WITH LOW VOLTAGE LANDSCAPE LUMINAIRES / FITTINGS
CONTACT YOUR LOCAL DISTRIBUTOR OR Q-TRAN FOR Q-WIRE, Q-CLIK OR PROPER ACCESSORY KITS.
ROUGH IN WIRING
-
Excavate a 14” x 30” x 16” deep hole for the Q-VAULT direct burial housing.
-
Dig trenches for primary & secondary wiring to Q-VAULT housing location.
-
Place drain pipe at a 30 degree angle at the lowest slope of land for proper drainage. Fill bottom of pit with a minimum of 4″ of gravel.
SEE DIAGRAM A
Note: Increase width to 30” x 30” when stabilizing bars are used. -
Bring all primary and secondary wiring into housing.
A: Entry location is provided at both the bottom and side of the Junction Box located on the Q-VAULT housing.
B: On the bottom of Junction Box there are: (4) 3/4” NPT and (2) 1/2” NPT KO’s. SEE DIAGRAM B
C: Using the Field Drill Guide Labels provided in the installation kit you are able to drill for various fitting sizes. Only knock out openings for conduits being utilized in installation. SEE DIAGRAM C
-
After all field wiring has been installed with proper lead lengths, tighten all fittings properly to assure they are water proof. All drilled entries require Q Click wire connectors to insure water tight connection. Use of other connectors voids warranty.
-
Coil and store field wiring in Junction Box area.
Note: Label all wiring for future reference.
FOR COMPLETE WATER TIGHT GUARANTEE
PRIMARY WIRING IN (120-277V)
Conduit – Use Installation Kit
- Step 1: Putty
- Step 2: Epoxy
- Step 3: Syringe
Non-conduit – use Q-CLIK NPT.75, Q.750-1E, Q-WIRE 12/2+GND
WARRANTY IS VOID IF THE CORRECT METHOD IS NOT USED.
SECONDARY WIRING OUT (12-24V)
Low voltage wire (non-conduit)
- Q-CLIK
- NPT-or knock outs in bottom of Q-VAULT, .5-.75
- MST to drill into the side of the housing, .5-1.25
- Q-WIRE low voltage marine grade UFB wire (recommended) 10-14AWG
- Standard Q-CLIK insert
Conduit – low voltage, requires Seal Kit (sold separately)
- Step 1: Putty
- Step 2: Epoxy
- Step 3: Syringe
7. Clean debris from the top perimeter and install gasket. SEE DIAGRAM D
8. Install door and tighten the 6 door bolts in the number sequence shown.
SEE DIAGRAM E
Note: Nut driver can be used to get bolts seated before final tightening.
Proper door bolt tightening must be done with a ratchet wrench using a 3/8“
socket at a maximum torque of 50 in-lbs.
9. Attach the provided Support Bars
to the Q-VAULT housing using the 6-32 X 5/8 screws. SEE DIAGRAM F
*OPTIONAL: Concrete Pour Ring Nut & Bolt Installation. SEE DIAGRAM G
10. Level housing and fill hole
with gravel to 4“ of below grade. Add soil to surface. SEE DIAGRAM H
All wire entry/exits other than conduit entries MUST use Q-CLIK connectors.
Failure to use them will void warranty.
11. Remove cover if installed, be
sure to store cover and cover gasket in a clean and dry location.
12. Move field wiring out of the way.
13. Place Q-SET+QZ low voltage luminaire power supply cassette into the
Q-VAULT housing.
14. Landscape Lighting: Landscape Lighting: Bring primary field wiring
directly into the Cassette’s primary terminal block through open hole.
Primary Connections:
- Ground to ground labeled on terminal block
- Neutral to neutral labeled on terminal block
- Hot to hot labeled on terminal block
SEE DIAGRAM I
HOUSING
HOUSING DOOR: Underside View
HOUSING: Outside View
Hole Drill Guide Label: Refer to sticker instructions
INSTALLING Q-SET+QZ
Determine proper lengths and trim to correct length.
Q-SET+QZ Low Voltage Connections:
Connect red wire to +24V on low voltage terminal block.
Connect black wire to – on low voltage terminal block .
SIMPLE AS 1, 2, 3
-
Use putty provided to seal wires in potting well. It is important that the well is liquid tight so that when the re-enterable epoxy is poured, it does not escape out the bottom. Be sure the putty is put into the very bottom of the well to allow ample room for the epoxy. SEE DIAGRAM O
-
A: The 3M-8882 re-enterable epoxy takes several hours to set. When set it will form a into a water tight “jello” consistency.
B: Mix the two part epoxy together per 3M instructions located on the epoxy packaging.
C: Push all the mixed epoxy together to one end of the bag. Cut the corner of the bag. -
A: Using the syringe pull the mixed epoxy into the syringe by pulling the plunger out slowly.
B: Slowly dispense the mixed epoxy from the syringe into the utilized potting wells. SEE DIAGRAM P
Note: Potting is now complete
LAST STEP
Final Door Installation
Gasket and door installed only in one direction
- Clean housing area where door gasket will rest
- Reinstall clean door gasket.
Before Door is Installed
Put velcro desiccant bag in place. Attach the two velcro loop coins on the desiccant bag to the two velcro hook coins on the underside of the housing door.
SEE DIAGRAM Q
Note: Install door and tighten the 6 door bolts NOT TO EXCEED 50 IN-LBS. Door bolt tightening must be done with a ratchet wrench using a 3/8” socket.
NEC CODE & UL STANDARDS FOR LIGHTING
Systems Operating at 30 Volts or Less
QVAULT-5 USE ONLY WITH Q-TRAN QSET+QZ POWER SUPPLY
A. 3426-94 Luminaires – Landscape Lighting Systems – Certified to UL – 1838
Standard.
B. 3425-95 Luminaires – Low Voltage Lighting Systems – Certified to UL – 2108
Standard.
C. 3425-96 Luminaires – Component Hydro massage – Certified to UL – 379 Pool &
Spa Standard.
1. 3426-04 Luminaires – Landscape Lighting Systems – Component (including
Hydro massage).
2. 3425-15 Luminaires – Low Voltage Lighting Systems.
INDEPENDENT 0-10V DIMMER, MLV/ELV DIMMER, DMX CONTROL, OR DALI
FOR SUPPLY CONNECTIONS USE WIRE RATED FOR AT LEAST 90°C
SUITABLE FOR GROUND INSTALLATION
NOT FOR INSTALLATION TO A CONDUIT EXTENDING DIRECTLY TO AN UNDERWATER POOL
LIGHT FORMING SHELL
PRIMARY TERMINAL MARKED WITH IDENTIFICATION MARKINGS BLACK FOR LINE, WHITE FOR
NEUTRAL, GREEN FOR GROUND
SUITABLE FOR USE WITH SUBMERSIBLE LUMINARIES
SUITABLE FOR INDOOR & OUTDOOR USE
SUITABLE FOR WET LOCATIONS
WARNING: RISK OF FIRE – IF INSTALLATION INVOLVES RUNNING WIRING THROUGH A
BUILDING STRUCTURE, SPECIAL WIRING METHODS ARE NEEDED. CONSULT A QUALIFIED
ELECTRICIAN.
CAUTION
USE ONLY WITH MAXIMUM 30 WATT LAMP LOAD FOR MODELS Q-SET+QZ-30
USE ONLY WITH MAXIMUM 60 WATT LAMP LOAD FOR MODELS Q-SET+QZ-60
USE ONLY WITH MAXIMUM 96 WATT LAMP LOAD FOR MODELS Q-SET+QZ-96, Q-SET+QZ-
DW-96, Q-SET+QZ-DMX-96, Q-SET+QZ-DALI-96
READ INSTALLATION INSTRUCTIONS • WWW.Q-TRAN.COM, MILFORD,CT 06460
© 2023 Q-Tran Inc. All rights reserved
155 Hill St. Milford, CT 06460 |
203-367-8777
sales@q-tran.com |
www.q-tran.com
Specification subject to change. Rev-10-04-23