HK INSTRUMENTS Indoor air quality transmitters Siro-MOD series Instruction Manual

June 6, 2024
HK INSTRUMENTS

Indoor air quality transmitters Siro-MOD series
Instruction Manual

INTRODUCTION

Thank you for choosing an HK Instruments Siro-MOD series indoor air quality transmitter. The Siro-MOD series transmitters are intended for use in building automation systems in the HVAC/R industry.

Siro-MOD is an indoor air quality transmitter with a modern design. The transmitter is available with several optional air quality sensors. The modular device can be equipped with CO2 concentration and VOC (Volatile Organic Compounds) measurements or alternatively PM (Particulate Matter) measurement and in addition temperature and humidity measurements. It offers easy installation and adjustment, several different model options, and various output signals that are configurable separately for each measurement parameter.

The Siro-MOD series devices are available with a user interface that includes an LCD display and buttons making the configuration of the device quick and easy.  An external configuration tool is necessary for commissioning preparations for Siro-MOD without a user interface. Configuration is also possible via the Modbus network. Siro-MOD utilizes the industry-standard NDIR measurement principle with self-calibrating ABC logic™  for CO2 measurement.

WARNING

  • READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS DEVICE.
  • Failure to observe safety information and comply with instructions can result in PERSONAL INJURY, DEATH, AND/OR PROPERTY DAMAGE.
  • To avoid electrical shock or damage to equipment, disconnect power before installing or servicing and use only wiring with insulation rated for full device operating voltage.
  • To avoid potential fire and/or explosion do not use in potentially flammable or explosive atmospheres.
  • Retain these instructions for future reference.
  • This product, when installed, will be part of an engineered system whose specifications and performance characteristics are not designed or controlled by  HK Instruments. Review applications and national and local codes to assure that the installation will be functional and safe. Use only experienced and knowledgeable technicians to install this device.

APPLICATIONS

Siro-MOD series devices are commonly used to monitor and control:

  • indoor air quality in offices, public spaces, meeting rooms, and classrooms
  • CO2 and VOC concentration to regulate demand-controlled ventilation and to keep the indoor air quality at a good level
  • PM concentration to measure the size and amount of particulates in the indoor air for example to assess the performance of air filters
  • temperature and humidity in the HVAC/R environment

SPECIFICATIONS

Performance
Measurement ranges:

CO²: 0-2000 ppm / 400-2000 ppm (selectable via jumper)
VOC: CO2eq: 400-2000 ppm

TVOC ppm: 0-30.0 ppm
TVOC kg/m3: 0-10000 p.g/m3 IAQ index: 1-5 (UBA rating)
PM1/PM2.5/PM10:| 0-50 jig/m3 / 0-500 Rg/m3 (selectable via jumper)
IAQ index: 1-5 (WHO rating)
Temperature:| 0…50 °C
Relative humidity:| 0-100 %rH

Accuracy:

CO2:| ±30 ppm + 3 % of reading (typical), an additional ±60 ppm for the first weeks
---|---
VOC:| 15 % of reading (typical)
VOC sensor is tuned for typical IAQ Mix of 22 VOCs as defined by Mølhave et al. (1997)
PM:
0…100 µg/m3:
PM2.5:
PM1/PM10:| ±15 µg/m³ (at 25 ⁰C ±5 ⁰C)
±25 µg/m³ (at 25 ⁰C ±5 ⁰C)
100…1000 µg/m3:
PM2.5:
PM1/PM10
:| ±15 % (at 25 ⁰C ±5 ⁰C)
±25 % (at 25 ⁰C ±5 ⁰C)
*PM1 and PM10 values are calculated from PM2.5 measurement reading with the default particle distribution.
Temperature:| ±0.4 ⁰C (typical at 20 ⁰C)
Relative humidity:| ±2.2 %rH (typical at 20 ºC, 30 %rH)

Technical Specifications
Media compatibility:
Dry air or non-aggressive gases
Measuring units:

CO₂:
VOC:| ppm
CO2 eq: ppm
TVOC: ppm, µg/m³
---|---
PM:| PM1/PM2.5/PM10: µg/m³
Temperature:| °C/°F
Relative humidity:| %rH

Measuring element:

CO2: Non-dispersive infrared (NDIR)
VOC: Complementary Metal Oxide Semiconductor (CMOS)
PM: Laser-based light scattering particle sensing
Temperature: Integrated to CMOS
Relative humidity: Thermoset polymer capacitive sensing element

Calibration: Automatic self-calibration ABC LogicTMfor CO2 measurement
Environment: Operating temperature: 0…50 °C
Storage temperature: -20…70 °C
Humidity: 0 to 95 %rH, non condensing

Physical

Dimensions: Case: 95 x 103 x 30 mm (width x height x depth)
Weight: 130 g
Mounting: 2 screw holes slotted, distance c/c 60 mm Materials:
Case: ABS
Protection standard: I P20
Display (optional) Monochrome LCD, 38 x 23 mm
Electrical connections: 10-pin spring-loaded terminal block 0.2…1.5 mm2 (16-24 AWG)

Electrical

Input: 24 VAC or VDC, ±10 %
Power consumption: 2 W max + 25 mW for each voltage output or 50 mW for each current output

Outputs:
4 outputs, have to select voltage or current Voltage outputs: 0–10 V 2–10 V / 0–5 V (optional, display or configuration tool required)

Current output: 4–20 mA (optional)
Output signal limits: Voltage outputs: R > 1 kΩ
Current output: R > 20 Ω, R < 500 Ω

Communication
Protocol: MODBUS over Serial Line
Transmission Mode: RTU
Interface: RS485
Byte format 11 bits (10 bits if parity none): Coding System: 8-bit binary
Bits per Byte: 1 start bit 8 data bits, the least significant bit sent first 1 bit for parity 1 stop bit

Baud rate: selectable in configuration Modbus address: 1−247 addresses selectable in the configuration menu

Conformance
Meets requirements for CE marking:
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
WEEE Directive 2012/19/EU

COMPANY WITH
MANAGEMENT SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 = ISO 14001 =

SCHEMATICS

HK INSTRUMENTS Indoor air quality transmitters Siro MOD series -
SCHEMATICS

  1. Pin header Description

    Open Connected
    Open Connected| CO2 / PM output range selection 400…2000 ppm (CO2 models) 0…2000 ppm (CO2 models)
    0…500 p.g/m3(PM models) 0…50 p.g/m3 (PM models)

  2. Pin header Description

    Open
    Connected| Menu lock
    Menu lock disabled
    Menu lock enabled

  3. Pin header Description

    OUT1
    OUT2
    OUT3
    OUT4
    GND| Voltage / current output selection
    • Current output is an optional
    Output 1
    Output 2
    Output 3
    Output 4
    Ground

  4. Pin header Description

    Open
    Connected| Modbus termination
    Not terminated
    Terminated

  5. Connector Description
    A+ B- RS485 Modbus/RTU slave DATA+

    DATA-
    24 V GND GND| Power supply
    24 VAC/DC ±-10 %
    Ground
    Ground

  6. Connector Description

    OUT1
    OUT2
    OUT3
    OUT4
    GND| Voltage / current outputs
    • Output settings can be modified from the display menu
    • See the lid label for factory default settings.
    Output 1
    Output 2
    Output 3
    Output 4
    Ground

DIMENSIONAL DRAWINGS

HK INSTRUMENTS Indoor air quality transmitters Siro MOD series - DIMENSIONAL
DRAWINGS

INSTALLATION

  1. Mount the device in the desired location (see step 1).
  2. Route the cables and connect the wires (see step 2).
  3. Connect the display cable to the display connector on the PCB. (See schematics)
  4. The device is now ready for configuration.

WARNING! Apply power only after the device is properly wired.

Opening/closing the lid

HK INSTRUMENTS Indoor air quality transmitters Siro MOD series - closing the
lid

  1. Open the lid by pressing the center from the bottom of the lid as in the figure.
  2. Close the lid by inserting the top of the lid into the grooves first and pushing the bottom edge as in the figure.

STEP 1: MOUNTING THE DEVICE

  1. Select a mounting location on the wall at 1.2–1.8 m (4–6 ft) above the floor and at least 50 cm (20 in) from the adjacent wall. Do not block device air vents from any direction and leave at least a 20 cm (8 in) gap to other devices. Locate the unit in an area with good ventilation and an average temperature,  where it will be responsive to changes in the room conditions. The Siro-MOD should be mounted on a flat surface.

Do not locate the Siro-MOD where it can be affected by:

  • Direct sunlight
  • Drafts or dead areas behind doors
  • Radiant heat from appliances
  • Concealed pipes or chimneys
  • Outside walls or unheated/uncooled areas
  1. Use the device as a template and mark the screw holes.
  2. Mount the wall plate with screws.

CAUTION! Incorrect installation may cause a shift in measurements.

HK INSTRUMENTS Indoor air quality transmitters Siro MOD series - MOUNTING
THE DEVICEHK INSTRUMENTS Indoor air quality transmitters Siro MOD series -
MOUNTING THE DEVICE 2

STEP 2: WIRING DIAGRAMS

CAUTION!

  • For CE compliance, a properly grounded shielding cable is required.
  • Use copper wire only. Insulate or wire nut all unused leads.
  • Care should be used to avoid electrostatic discharge to the device.
  • This unit has configuration jumpers. You may need to reconfigure this device for your application.
  1. Route the cables through the opening in the backplate or for surface wiring select a knockout on the bottom of the wall plate, as shown in Figure 2a.
  2. Connect the wires as shown in Figures 2b and 2c.

HK INSTRUMENTS Indoor air quality transmitters Siro MOD series - WIRING
DIAGRAMS

NOTE! When using long connection wires it may be necessary to use a separate GND wire for voltage output current to prevent measurement distortion.  The need for an extra GND wire depends on the cross-section and length of the used connection wires. If long and/or small cross-section wires are used,  supply current and wire resistance may generate a voltage drop in the common GND wire resulting in a distorted output measurement.
When using an AC power supply, make sure that the ground potential of the signal is the same as the ground potential of the supply voltage to avoid shorting a circuit through the additional GND wire.

It is recommended to use a shielded twisted pair cable for Modbus cabling.
The cable shield must be earthed only at one point, normally, at the end of the main cable.

HK INSTRUMENTS Indoor air quality transmitters Siro MOD series - WIRING
DIAGRAMS 2

STEP 3: CONFIGURATION

Configuration of the Siro-MOD series device consists of:

  1. Configuring the jumpers (see step 4).
  2. Configuration menu options.
    (Display (-D) or configuration tool required. See the user manual for further details.)

STEP 4: Jumper settings

HK INSTRUMENTS Indoor air quality transmitters Siro MOD series - Jumper
settings

  1. Configuration of the output modes:
    Select the output mode, current (4–20 mA) (optional), or voltage (0–10 V) for each output (1-4) by installing jumpers as shown in Figure 4.
    On a display version of the device, the output scale can be changed via the configuration menu. An external configuration tool is available for devices without a user interface.
    First, select the output mode by jumper, then select the output scale (4– 20 mA (optional) / 0–10 V / 2–10 V / 0–5 V) via the configuration menu.
    Please see the user manual for more details.
    NOTE! When using mA output, do not use Vout scalings from the menu.
    Using 2-10 V output in some applications it is critical to know immediately if the wire is broken or the device is damaged. In these cases, a 2-10 voltage output is recommended.
    HK INSTRUMENTS Indoor air quality transmitters Siro MOD series - Jumper
settings 2

  2. Output range selection with CO2- and PM models:
    Install jumper 1 (figure 3) to change the output range. This feature is intended to use only on devices without display. On a display version of the device, the output range can be selected via the configuration menu.
    Please see the user manual for more details. Pin header| Description
    ---|---
    Open Connected
    Open Connected| CO2 / PM output range selection
    400…2000 ppm (CO2 models) 0…2000 ppm (CO2 models)
    0…500 mg/m3 (PM models) 0…50 mg/m3 (PM models)

  3. Locking the display:
    Install jumper 2 (figure 3) to lock the display to prevent access to the configuration menu after installation is completed.

  4. Modbus termination:
    Install a jumper 4 (figure 3) to terminate Modbus.
    In order to avoid signal reflections, a Modbus termination jumper must be installed in case the device is the last one on the bus.

STEP 5: Modbus registers

Function code 03 – Read holding registers, Function code 06 – Write single register, Function code 16 – Write multiple registers, Broadcast supported with address 0

Register| Parameter description| Data type| Min value| Max value| Range
---|---|---|---|---|---
4×0001| Offset CO2| 16 bit| -200| 200| -200..200 ppm
4×0002| Offset Humidity| 16 bit| -100| 100| -10.0..10.0 %
4×0003| Offset Celsius 1| 16 bit| -50| 50| -5.0..5.0 °C
4×0004| Offset Fahrenheit
1| 16 bit| -90| 90| -9.0..9.0 °F
4×0005| Offset TVOC ppm| 16 bit| -300| 300| -3.00..3.00 ppm
4×0006| Offset TVOC ug/m3| 16 bit| -1000| 1000| -1000..1000 ug/m3
4×0007| Offset CO2 EQ| 16 bit| -200| 200| -200..200 ppm
4×0008| Offset PM| 16 bit| 30| 200| 0.3..2.0 coefficient
4×0009| Backlight intensity| 16 bit| 0| 100| 0..100%
4×0010| Display Celsius ‘2| 16 bit| 0| 6| Position number, 0=not used
4×0011| Display Fahrenheit 2| 16 bit| 0| 6| Position number, 0=not used
4×0012| Display Humidity| 16 bit| 0| 6| Position number, 0=not used
4×0013| Display CO2| 16 bit| 0| 6| Position number, 0=not used
4×0014| Display CO2 EQ| 16 bit| 0| 6| Position number, 0=not used
4×0015| Display PM2.5 hour| 16 bit| 0| 6| Position number, 0=not used
4×0016| Display PM10 hour| 16 bit| 0| 6| Position number, 0=not used
4×0017| Display IAQ| 16 bit| 0| 6| _ Position number. 0=not used

1=Celsius and Fahrenheit limits are interdependent, and thus a change in one limit of measurement will also change the limits of the other measurement. Use Function code 06 (write single register) for Celsius or Fahrenheit.
2= Use Function code 16 (write multiple registers) for display configuration. Valid value (0 / 1…6) is needed for all display configuration registers. (see Siro User Guide STEP 1.1: Display view)

Modbus registers continued

Function code 04 – Read input register

Register Parameter description Data type Min value Max value Range
3×0001 Program version 16 bit 1 9999 0.01..99.99
3×0002 CO2 reading 16 hit 0 2500 0..2500 ppm
3×0003 RH reading 16 bit 0 1000 0.0..100.0 %
3×0004 Temperature Celsius 16 bit 0 500 0 0 50.0 °C
3×0005 Temperature Fahrenheit 16 bit 320 1220 32.0..122.0 °F
3×0006 TVOC ppm reading 16 bit 0 3200 0.00..32.00 ppm
3×0007 TVOC ug/m3 reading 16 bit 0 10000 0..10000 ug/m3
3×0008 CO2_eq reading 16 bit 0 12000 0..12000 ppm
3×0009 IAQ reading TVOC 16 bit 1 5 1..5 IAQ index
3×0010 IAQ reading PM 16 bit 1 5 1..5 IAQ index
3×0011
3×0012 PM1 reading 16 bit 0 1000 0..1000 ug/m3
3×0013 PM2.5 reading 16 bit 0 1000 0 1000 ug/m3
3×0014 PM10 reading 16 bit 0 1000 0..1000 ug/m3
3×0015 PM2.5 1h average 16 bit 0 10000 0.0..1000.0 ug/m3
3×0016 PM2.5 24h average 16 bit 0 10000 0.0..1000.0 ug/m3
3×0017 PM10 1h average 16 bit 0 10000 0 0 1000.0 ug/m3
3×0018 PM10 24h average 16 bit 0 10000 0.0..1000.0 ug/m3
3×0019
3×0020 Error status 16 bit 0 65535 See table below

3×0020 Error status bits

Bit 0 temperature sensor detected, 0 = not detected, 1=detected
Bit 1 humidity sensor detected, 0 = not detected, 1=detected
Bit 2 cot sensor detected, 0 = not detected, 1=detected
Bit 3 voc sensor detected, 0 = not detected, 1=detected
Bit 4 pm sensor detected, 0 = not detected, 1=detected
Bit 5 display module detected, 0 = not detected, 1=detected
Bit 6 current(mA) module detected, 0 = not detected, 1=detected
Bit 8 sensor warm up 0 = normal operation, 1 = warm up
Bit 9 rht status 0 = normal operation, >0 reading error
Bit 10 CO2 status 0 = normal operation, >0 reading error
Bit 11 pm status 0 = normal operation, >0 reading error
Bit 12 voc status 0 = normal operation, >0 reading error

RECYCLING/DISPOSAL

The parts left over from installation should be recycled according to your local instructions. Decommissioned devices should be taken to a recycling site that specializes in electronic waste.

WARRANTY POLICY

The seller is obligated to provide a warranty of five years for the delivered goods regarding material and manufacturing. The warranty period is considered to start on the delivery date of the product. If a defect in raw materials or a production flaw is found, the seller is obligated, when the product is sent to the seller without delay or before the expiration of the warranty, to amend the mistake at his/her discretion either by repairing the defective product or by delivering free of charge to the buyer a new flawless product and sending it to the buyer. Delivery costs for the repair under warranty will be paid by the buyer and the return costs by the seller. The warranty does not comprise damages caused by accident, lightning, flood or another natural phenomenon, normal wear and tear, improper or careless handling, abnormal use, overloading, improper storage,  incorrect care or reconstruction, or changes and installation work not done by the seller. The selection of materials for devices prone to corrosion is the buyer’s responsibility unless otherwise is legally agreed upon. Should the manufacturer alter the structure of the device, the seller is not obligated to make comparable changes to devices already purchased. Appealing for a warranty requires that the buyer has correctly fulfilled his/her duties arising from the delivery and stated in the contract. The seller will give a new warranty for goods that have been replaced or repaired within the warranty, however only to the expiration of the original product’s warranty time. The warranty includes the repair of a defective part or device, or if needed, a new part or device, but not installation or exchange costs. Under no circumstance is the seller liable for damages compensation for indirect damage.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

HK INSTRUMENTS User Manuals

Related Manuals