dwyer RHP-E N Series Wall Mount Humidity Temperature Dew Point Transmitter Instruction Manual
- June 15, 2024
- Dwyer
Table of Contents
- dwyer RHP-E N Series Wall Mount Humidity Temperature Dew Point
- Product Information – Series RHP-E/N Wall Mount
- Product Usage Instructions
- Series RHP-E/N Wall Mount Humidity/Temperature/Dew Point Transmitter
- INSTALLATION
- SPECIFICATIONS
- TROUBLESHOOTING
- MAINTENANCE
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
dwyer RHP-E N Series Wall Mount Humidity Temperature Dew Point
Transmitter
Product Information – Series RHP-E/N Wall Mount
Humidity/Temperature/Dew Point Transmitter
Specifications
- Dimensions : 1.10″ [27.96mm] x 4.50″ [114.30mm] x 3.65″ [92.72mm]
- Weight : 0.33 lbs [0.15 kg]
- Output Options : Humidity or Dew Point (current or voltage), Temperature (current, voltage, RTD, or thermistor)
- Temperature Range: Field selectable for models with current or voltage output
- Sensor Type : Capacitive polymer sensor
Product Usage Instructions
Installation
CAUTION: Disconnect power supply before installation or maintenance to avoid equipment damage.
- Refer to the job wiring diagram and ensure all connections are made in accordance with national and local electrical codes.
- Use copper conductors for all connections.
- Take electrostatic discharge precautions during installation and maintenance to prevent equipment damage. Use wrist straps if necessary.
- Avoid installing the transmitter in locations with severe shock or vibration, excessive moisture, or corrosive fumes.
- Ensure the device is not exposed to AC voltage operation if using the 4-20 mA models.
Operating Instructions
- After installation, ensure the power supply is connected.
- The transmitter has switches to select the temperature engineering units (e.g., Celsius, Fahrenheit) and the output type (humidity or dew point).
- Set the desired temperature engineering units using the appropriate switch.
- Choose the desired output type (humidity or dew point) using the corresponding switch.
- For models with a temperature output, select the desired output type (current, voltage, RTD, or thermistor) if applicable.
- Adjust any other settings or parameters as required.
Frequently Asked Questions (FAQ)
-
Q: What are the output options for the Series RHP-E/N Transmitter?
A: The transmitter can output either humidity or dew point, with options for current or voltage. It also offers temperature output options of current, voltage, RTD, or thermistor. -
Q: Can I use the 4-20 mA models with AC voltage?
A: No, the 4-20 mA models are not designed for AC voltage operation. Using them with AC voltage may result in permanent damage not covered by the warranty. -
Q: How sensitive is the sensor to electric shock?
A: The sensor is particularly sensitive to electric shock. It is recommended to take electrostatic discharge precautions, such as using wrist straps, during installation and maintenance to prevent equipment damage.
Series RHP-E/N Wall Mount Humidity/Temperature/Dew Point Transmitter
Specifications – Installation and Operating Instructions
The Series RHP-E/N
Wall Mount Humidity/Temperature/Dew Point Transmitter is the most versatile
room transmitter on the market. The stylish housing is well vented to provide
air flow across the sensor to improve measurement accuracy. An optional LCD
display can be integral to the transmitter or a remote display can be ordered
for building balancing or LEED® validation. The LCD display indicates the
ambient temperature along with the humidity or dew point. The transmitter has
internal dip switches to select the temperature engineering units and whether
the transmitter outputs humidity or dew point.
The humidity and the dew point are measured using a capacitive polymer sensor
that completely recovers from 100% saturation. The humidity and dew point can
have either a current or voltage output, while the optional temperature output
can be a current, voltage, RTD or thermistor. For models with current or
voltage for the temperature output, the temperature range is field selectable.
INSTALLATION
CAUTION Disconnect power supply before installation or maintenance.
Failure to do so may result in equipment damage.
Make sure all connections are in accordance with the job wiring diagram and in
accordance with national and local electrical codes. Use copper conductors
only.
NOTICE Use electrostatic discharge precautions (e.g., use of wrist
straps) during installation and maintenance to prevent equipment damage. The
sensor is particularly sensitive to electric shock.
NOTICE Avoid locations where severe shock or vibration, excessive
moisture, or corrosive fumes are present.
NOTICE Do not exceed ratings of this device; permanent damage not covered
by warranty may result. The 4-20 mA models are not designed for AC voltage
operation.
SPECIFICATIONS
- Relative Humidity Range : 0 to 100% RH.
- Temperature Range: -40 to 140°F (-40 to 60°C) for thermistor and RTD sensors. – 20 to 140°F (-28.9 to 60°C) for solid state band gap temperature sensors.
- Dew Point Temperature Range : -20 to 140°F (-28.9 to 60°C); 0 to 100°F (-17.8 to 37.8°C); 40 to 90°F (4.4 to 32.3°C); -4 to 140°F (-20 to 60°C) field-selectable ranges.
- Accuracy : RH: Model RHP-2XXX ±2% 10 to 90% RH @ 25°C; Model RHP-3XXX ±3% 20 to 80% RH @ 25°C; Model RHP-5XXX ±5% 20 to 80% RH @ 25°C; Thermistor temperature sensor: ±0.36°F @ 77°F (±0.2°C @ 25°C); RTD temperature sensor: DIN Class B; ±0.54°F @ 32°F (±0.3°C @ 0°C);
- Solid state band gap temperature sensor : ±0.9°F @ 77°F (±0.3°C @ 25°C).
- Hysteresis : ±0.8%.
- Repeatability : ±0.1% typical.
- Temperature Limits : Operating: -40 to 140°F (-40 to 60°C);
- Storage: -40 to 176°F (-40 to 80°C).
- Compensated Temperature Range : -4 to 140°F (-20 to 60°C).
- Power Requirements : 4-20 mA loop powered outputs: 10-35 VDC; 0-5/10V outputs: 15-35 VDC or 15-29 VAC.
- Output Signals : 4-20 mA loop powered outputs: 4-20 mA, 2 channels for humidity/solid state temperature sensor models (loop powered on RH). Switch selectable RH/dew point. Switch selectable normal or reverse output; 0-5/10V outputs: 5 mA max., 2 channels for humidity/solid state temperature sensor models. Switch selectable 0-10 V/2-10 V or 0-5 V/1-5 V output. Switch selectable RH/dew point.
- Switch selectable normal or reverse output.
- Solid State Band Gap Temperature Sensor Output Ranges: Switch selectable, – 20 to 140°F (-28.9 to 60°C); 0 to 100°F (-17.8 to 37.8°C); 40 to 90°F (4.4 to 32.3°C); -4 to 140°F (-20 to 60°C).
- Response Time: 8 s.
- Electrical Connections: Screw terminal block.
- Drift : <0.25% RH/year.
- RH Sensor : Capacitance polymer.
- Enclosure Material : Polycarbonate.
- Enclosure Rating : IP20.
- Display : Optional LCD; Switch selectable %RH or dew point, °F/°C.
- Display Resolution : RH: 1%; Temperature: 0.1°F (0.1°C); Dew point: 1°F (1°C). Weight: 4.4 oz (125 g).
- Compliance : CE.
- Push tab on top and bottom of the back plate and lift the cover from the back plate. (See Figure 1).
- Select the mounting location, away from diffusers, lights, or any external influences.
- Mount transmitter on a vertical surface to a standard electrical box using the two #6 M2C type screws provided.
- Pull wires through the sub base hole and make the necessary connections.
- Reattach cover to back plate.
Wiring
Use maximum 18 AWG wire for wiring to terminals. Refer to Figures 2 and 3 for
wiring information.
Models with Selectable Current or Voltage Outputs (RHP-X(E or N)44)
These models may be wired for current or voltage output. Note that both
outputs must be wired either for current or voltage. It is not possible to
wire one output for current, and the other for voltage.
Prior to wiring, verify that the Current/Voltage select switch shown in Figure
4 is set to current or voltage as desired. Refer to “Setting the
Current/Voltage Select Switch”.
Current Output Selected: Wire as shown in Figure 2. Current outputs must be powered with 10-35 VDC. If the RH output is not required, wire the negative terminal of the power supply to terminal 1 of the transmitter. All units come with 4-20 mA RH and Temperature outputs. If the 4-20 mA temperature output is not used it maybe left disconnected. If the unit has a passive temperature sensor, wire to terminals 7 and 8.
Voltage Output Selected: Voltage outputs may be powered with 15-35 VDC or 15-29 VAC. Note polarity when using DC power. Wire the RH voltage output as shown in Figure 3. If the unit has a voltage temperature output, wire the temperature receiver between terminal 6 and the negative terminal of the power supply. All units come with RH and Temperature voltage outputs. If the temperature or RH voltage output is not used it may be left disconnected. If the unit has a passive temperature sensor, wire to terminals 7 and 8.
Setting the Current/Voltage Select Switch
Remove the cover of the unit as shown in Figure 1. The Current/Voltage select
switch is located on the back of the circuit board. Set the switch “IOUT” for
current, “VOUT” for voltage.
DIP SWITCH
SETTINGS
To access the DIP SWITCH, remove the cover of the unit as shown in Figure 1.
The DIP SWITCH is located on the back of the circuit board as shown in Figure
4.
-
ALL DIP SWITCHES are factory set to “ON”
5 V/10 V Output Select (Applies only to Voltage Output units)- DIP SWITCH#1 OFF : Output = 0-5 V
- DIP SWITCH#1 ON: Output = 0-10 V
-
Zero Suppression (Applies only to Voltage Output Units)
- DIP SWITCH#2 OFF : Output range = 1-5 V or 2-10 V, depending on output range DIP SWITCH#2 ON : Output range = 0-5 V or 0-10 V, depending on output range
-
Upper Display reads RH or DEW POINT
- DIP SWITCH#3 OFF: Upper Display reads Dew Point
- DIP SWITCH#3 ON: Upper Display reads RH
-
RH OUTPUT, Normal or Invert
- DIP SWITCH#4 OFF : Output is inverted
- DIP SWITCH#4 ON: Output is Normal
When set to normal output, the output increases as the RH increases. When set to inverted output, the output decreases as the RH increases.
Example : Normal 4-20 mA output, 0% RH = 4 mA, 100% RH = 20 mA
Inverted 4-20 mA output, 0% RH = 20 mA, 100% RH = 4 mA
-
TEMP OUTPUT, Normal or Invert
- DIP SWITCH#5 OFF: Output is inverted
- DIP SWITCH#5 ON: Output is Normal
When set to normal output, the output increases as the temperature increases. When set to inverted output, the output decreases as the temperature increases. Example: Normal 4-20 mA output, -20°F = 4 mA, +140°F = 20 mA
-
Inverted 4-20 mA output, -20°F = 20 mA, +140°F = 4 mA
°F/°C Select- DIP SWITCH#6 OFF : °C
DIP SWITCH#6 ON: °F
TEMPERATURE OUTPUT RANGE SELECT
Range| Dip Switch 7| Dip Switch 8
-4 to +140°F (-20 to +60°C)| OFF| OFF
+40 to +90°F (+4.4 to +32.2°C)| OFF| ON
0 to +100°F (-17.8 to +37.8°C)| ON| OFF
-20 to +140°F (-28.9 to +60°C)| ON| ON
The temperature range applies only to the current or voltage output. If the unit has a display, it will display temperature from -40 to +140°F (-40 to +60°C). If the unit is set to read DEW POINT, the output range of the DEW POINT will be the same as the Temperature Output Range.
Note: The display will indicate temperature even if the unit does not have a temperature output.
TROUBLESHOOTING
Verify that the unit is mounted in the correct position.
4-20 mA Models
Verify appropriate supply voltage. The transmitter requires a minimum of 10
and a maximum of 35 VDC at its connection for proper operation. Choose a power
supply with a voltage and current rating which meets this requirement under
all operating conditions. If the power supply is unregulated, make sure
voltage remains within these limits under all power line conditions. Ripple on
the supply should not exceed 100 mV.
Loop Resistance – The maximum allowable loop resistance depends on the
power supply voltage. Maximum loop voltage drop must not reduce the
transmitter voltage below the 10 VDC minimum. Maximum loop resistance can be
calculated with the following equation. Vps is the power supply voltage.
Some receivers, particularly loop powered indicators, may maintain a fixed
loop voltage to power the device. This voltage drop must also be subtracted
from the power supply voltage when calculating the voltage margin for the
transmitter. The following equation takes this into account. Vrec is the
receiver fixed voltage. 0-10 V Output Models
Verify appropriate supply voltage. The 0-10 V output models require a DC
supply of 15-35 V or an AC supply of 15-29 V for proper operation maximum.
Maximum output load is 5 mA.
Remote Display
For models that are ordered without an integral LCD display, remote display
Model A-449 or A-449A can be used to display the temperature and humidity or
dew point. The mini USB plug of the remote display plugs into the receptor on
the side of the housing. After a short warm up time, the display will begin to
show the current temperature and humidity or dew point measurements. Humidity
or dew point can be selected via the internal dip switches as described
earlier in this manual.
MAINTENANCE
Upon final installation of the Series RHP-E/N Temperature/Humidity/Dew Point Transmitter and the companion receiver, no routine maintenance is required. A periodic check of the system calibration is recommended. Except for sensor replacement, t he Series RHP-E/N is not field serviceable and should be returned if repair is needed (field repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a return goods authorization number before shipping.
This symbol indicates waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with your Local Authority or retailer for recycling advice.
MODEL CHART
Example| RHP| 2| N| 4| A| LCD| RHP-2N4A-
LCD
Series| RHP| | | | | | RH/passive temperature sensor transmitter
Accuracy| | 2
3
5
| | | | | 2% accuracy
3% accuracy
5% accuracy
Housing Type| | | N
E
| | | | North American wall mount
European wall mount
RH Output| | | | 4| | | 0-10 V/0-5 V/4-20 mA
Temperature Sensor/ Output| | | | | A B C D E F 0
4
| |
- 10K @ 25°C thermistor Dwyer curve A 10K @ 25°C thermistor Dwyer curve B 3K @ 25°C thermistor Dwyer curve C 100Ω RTD DIN 385
- 1KΩ RTD DIN 385
- 20KC 25°C thermistor curve F NONE
- 0-10 V/0-5 V/4-20 mA solid state sensor
Option| | | | | | Blank LCD FC NIST|
- No options LCD display
- Factory test report
- NIST calibration test certificate
RESISTANCE VS TEMPERATURE TABLE
Temperature| Resistance Curves (in Ω)
°C| °F| A| B| C| D| E| F
-55| -67.0| 607800.00| 963849.00| 289154.70| 78.32| 783.2| 2394000.00
-50| -58.0| 441200.00| 670166.00| 201049.80| 80.31| 803.1| 1646200.00
-45| -49.0| 323600.00| 471985.00| 141595.50| 82.29| 822.9| 1145800.00
-40| -40.0| 239700.00| 336479.00| 100943.70| 84.27| 842.7| 806800.00
-35| -31.0| 179200.00| 242681.00| 72804.30| 86.25| 862.5| 574400.00
-30| -22.0| 135200.00| 176974.00| 53092.20| 88.22| 882.2| 413400.00
-25| -13.0| 102900.00| 130421.00| 39126.30| 90.19| 901.9| 300400.00
-20| -4.0| 78910.00| 97081.00| 29.124.30| 92.16| 921.6| 220600.00
-15| 5.0| 61020.00| 72957.00| 21887.10| 94.12| 941.2| 163.500.00
-10| 14.0| 47540.00| 55329.00| 16598.70| 96.09| 960.9| 122280.00
-5| 23.0| 37310.00| 42327.00| 12698.10| 98.04| 980.4| 92240.00
0| 32.0| 29490.00| 32650.00| 9795.00| 100.00| 1000.0| 70160.00
5| 41.0| 23460.00| 25392.00| 7617.60| 101.95| 1019.5| 53780.00
10| 50.0| 18780.00| 19901.00| 5970.30| 103.90| 1039.0| 41560.00
15| 59.0| 15130.00| 15712.00| 4713.60| 105.85| 1058.5| 32340.00
20| 68.0| 12260.00| 12493.00| 3747.90| 107.79| 1077.9| 25360.00
25| 77.0| 10000.00| 10000.00| 3000.00| 109.74| 1097.4| 20000.00
30| 86.0| 8194.00| 8057.00| 2417.10| 111.67| 1116.7| 15892.00
35| 95.0| 6752.00| 6531.00| 1959.30| 113.61| 1136.1| 12704.00
40| 104.0| 5592.00| 5326.00| 1597.80| 115.54| 1155.4| 10216.00
45| 113.0| 4655.00| 4368.00| 1310.40| 117.47| 1174.7| 8264.00
50| 122.0| 3893.00| 3602.00| 1080.60| 119.40| 1194.0| 6722.00
55| 131.0| 3271.00| 2986.00| 895.80| 121.32| 1213.2| 5498.00
60| 140.0| 2760.00| 2488.00| 746.40| 123.24| 1232.4| 4520.00
65| 149.0| 2339.00| 2083.00| 624.90| 125.16| 1251.6| 3734.00
70| 158.0| 1990.00| 1752.00| 525.60| 127.08| 1270.8| 3100.00
75| 167.0| 1700.00| 1480.00| 444.00| 128.99| 1289.9| 2586.00
80| 176.0| 1458.00| 1255.00| 376.50| 130.90| 1309.0| 2166.00
85| 185.0| 1255.00| 1070.00| 321.00| 132.80| 1328.0| 1822.60
90| 194.0| 1084.00| 915.50| 274.65| 134.71| 1347.1| 1540.00
95| 203.0| 939.30| 786.60| 235.98| 136.61| 1366.1| 1306.40
100| 212.0| 816.80| 678.60| 203.58| 138.51| 1385.1| 1112.60
105| 221.0| 712.60| 587.60| 176.28| 140.40| 1404.0| 951.00
110| 230.0| 623.60| 510.60| 153.18| 142.29| 1422.9| 815.80
115| 239.0| 547.30| 445.30| 133.59| 144.18| 1441.8| 702.20
120| 248.0| 481.80| 389.60| 116.88| 146.07| 1460.7| 606.40
125| 257.0| 425.30| 341.90| 102.57| 147.95| 1479.5| 525.60
130| 266.0| 376.40| 301.00| 90.30| 149.83| 1498.3| N/A
135| 275.0| 334.00| 265.80| 79.74| 151.71| 1517.1| N/A
140| 284.0| 297.20| 235.30| 70.59| 153.58| 1535.8| N/A
145| 293.0| 265.10| 208.90| 62.67| 155.46| 1554.6| N/A
150| 302.0| 237.00| 186.10| 55.83| 157.33| 1573.3| N/A
©Copyright 2023 Dwyer Instruments, LLC
Printed in U.S.A. 12/23
LEED® is a registered trademark of the U.S. Green Building Council. FR#
444141-00 Rev. 6
- DWYER INSTRUMENTS, LLC
- P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
- Phone: 219-879-8000
- Fax: 219-872-9057
- www.dwyer-inst.com