Autonics CX6S Series LCD Display Counter Timer User Manual

June 17, 2024
Autonics

CX6S Series LCD Display Counter Timer

Product Information

Specifications:

  • Product Name: LCD Display Counter/Timer
  • Series: CX6S Series, CX6M Series

Product Usage Instructions

Safety Considerations:

  • Please observe all safety considerations for safe and proper
    product operation to avoid hazards. The symbol represents caution
    due to special circumstances in which hazards may occur.

  • Warning: Failure to follow these instructions
    may result in serious injury or death.

  • Caution: Failure to follow these instructions
    may result in personal injury or product damage.

Warning:

  1. Fail-safe device must be installed when using the unit with
    machinery that may cause serious injury or substantial economic
    loss. (e.g. nuclear power control, medical equipment, ships,
    vehicles, railways, aircraft, combustion apparatus, safety
    equipment, crime/disaster prevention devices, etc.) Failure to
    follow this instruction may result in fire, personal injury, or
    economic loss.

  2. Install on a device panel to use. Failure to follow this
    instruction may result in electric shock or fire.

  3. Do not connect, repair, or inspect the unit while connected to
    a power source. Failure to follow this instruction may result in
    electric shock or fire.

  4. Check ‘Connections’ before wiring. Failure to follow this
    instruction may result in fire.

  5. Do not disassemble or modify the unit. Failure to follow this
    instruction may result in electric shock or fire.

Caution:

  1. When connecting the power input and relay output, use AWG 20
    (0.50mm2) cable or over, and tighten the terminal screw with a
    tightening torque of 0.74 to 0.90N.m. Failure to follow this
    instruction may result in fire or malfunction due to contact
    failure.

  2. Use the unit within the rated specifications. Failure to follow
    this instruction may result in fire or product damage.

  3. Use the unit within the rated specifications. Failure to follow
    this instruction may result in shortening the life cycle of the
    unit or fire.

  4. Do not use the unit in the place where
    flammable/explosive/corrosive gas, humidity, direct sunlight,
    radiant heat, vibration, impact, or salinity may be present.
    Failure to follow this instruction may result in fire or
    explosion.

  5. Keep metal chip, dust, and wire residue from flowing into the
    unit. Failure to follow this instruction may result in fire or
    product damage.

Manual:

For detailed information and instructions, please refer to the
user manual and be sure to follow cautions. Visit our homepage
(www.autonics.com) to download
manuals.

Ordering Information:

CX 6 S – 1P 4 F

Signal input method:

  • No mark – Voltage input (PNP) / no-voltage input (NPN)
    selectable type

  • F – Free voltage input

Power supply:

  • 2 – 24VAC 50/60Hz, 24-48VDC
  • 4 – 100-240VAC 50/60Hz

Output:

  • Size Display digit Item
  • 1P – 1-stage setting
  • 2P – 2-stage setting
  • S – 6-digit

Unit Description:

  • CX6S Series
  • CX6M Series

Counting value display component:

RUN mode:

Displays counting value for counter operation or time progress
value for timer operation.

Function setting mode:

Displays parameter.

FAQ

Q: Where can I download the user manual?

A: You can download the user manual from our homepage at
www.autonics.com.

Q: What should I do if I notice metal chip, dust, or wire

residue flowing into the unit?

A: It is important to keep metal chip, dust, and wire residue
from flowing into the unit as it may result in fire or product
damage. Ensure the unit is placed in a clean environment and
regularly clean around the unit to prevent any debris from
entering.

DRW171461AB
LCD Display Counter/Timer
CX SERIES
INSTRUCTION MANUAL

CX6S Series

CX6M Series

Thank you for choosing our Autonics product. Please read the following safety considerations before use.

Safety Considerations
Please observe all safety considerations for safe and proper product operation to avoid hazards. symbol represents caution due to special circumstances in which hazards may occur.
Warning Failure to follow these instructions may result in serious injury or death.
Caution Failure to follow these instructions may result in personal injury or product damage.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster prevention devices, etc.) Failure to follow this instruction may result in fire, personal injury, or economic loss.
2. Install on a device panel to use. Failure to follow this instruction may result in electric shock or fire.
3. Do not connect, repair, or inspect the unit while connected to a power source. Failure to follow this instruction may result in electric shock or fire.
4. Check `Connections’ before wiring. Failure to follow this instruction may result in fire.
5. Do not disassemble or modify the unit. Failure to follow this instruction may result in electric shock or fire.
Caution
1. When connecting the power input and relay output, use AWG 20 (0.50mm2) cable or over, and tighten the terminal screw with a tightening torque of 0.74 to 0.90N.m. Failure to follow this instruction may result in fire or malfunction due to contact failure.
2. Use the unit within the rated specifications. Failure to follow this instruction may result in fire or product damage.
3. Use the unit within the rated specifications. Failure to follow this instruction may result in shortening the life cycle of the unit, or fire.
4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct sunlight, radiant heat, vibration, impact, or salinity may be present. Failure to follow this instruction may result in fire or explosion.
5. Keep metal chip, dust, and wire residue from flowing into the unit. Failure to follow this instruction may result in fire or product damage.
Manual
For the detail information and instructions, please refer to user manual and be sure to follow cautions. Visit our homepage (www.autonics.com) to download manuals.

Ordering Information

CX 6 S – 1P 4 F

Signal input method

No mark

Voltage input (PNP) /no-voltage input (NPN) selectable type

F

Free voltage input

Power supply

2

24VAC 50/60Hz, 24-48VDC

4

100-240VAC 50/60Hz

Output
Size Display digit Item

1P

1-stage setting

2P

2-stage setting

S

DIN W48×H48mm

M

DIN W72×H72mm

6

999999 (6-digit)

CX

LCD Display Counter/Timer

Unit Description
CX6S Series

CX6M Series

1

7

2

1

8

9

3

7

4

10

5

8

2

11

6

9

3

12 13 14

10

4 5

11

6

1. Counting value display component (red) RUN mode

12 13

14

: Displays counting value for counter operation or time progress value for timer operation.

Function setting mode: Displays parameter.

2. Setting value display component (green)

RUN mode: Displays setting value.

Function setting mode: Displays parameter setting value.

3. Time unit indicator (h:m:s): Turns ON for time unit for timer.

4. Key lock indicator ( ): Turns ON for key lock setting.

5. Reset input indicator (RST): Turns ON for reset key input or reset signal input.

6. INH indicator (INH)

: For the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ),

it turns ON for INHIBIT signal input.

(In case of CX6S Series and timer mode, it turns ON for INB/INH signal input.)

For free voltage input model (CX6 – F), it turns ON for INB/INH signal input for timer.

7. Output indicator (OUT1, OUT2): Turns ON for the dedicated control output ON.

8. SV checking and changing indicator (SET, SET1, SET2) (green)

: Turns ON when checking and changing SV.

9. COUNTER indicator (COUNTER): Turns ON for counter operation. 10. TOTAL indicator1 (TOTAL)

: In case of TOTAL counter display mode, it turns ON with the COUNTER indicator.

11. TIMER indicator (TIMER)

: Flashes (progressing time) or Turns ON (stopping time) for timer operation.

12. RESET key

RUN mode, Function setting mode

: Press the RESET key to reset the counting value and turn OFF the output. TOTAL counter display mode1: Press the RESET key to reset the counting value of TOTAL counter.

key

RUN mode: Hold the Press the

key over 3 sec to enter function setting mode. key to select SV2 (SET2)/SV1 (SET1)/TOTAL counter1 display for

counter operation.

Function setting mode: Hold the

key over 3 sec to return RUN mode.

Press the

key to save the SV and enter the next setting.

Function setting check mode: Hold the

key over 1 sec to return RUN mode.

Changing SV mode: Press the

key to save SV and return RUN mode.

14. , key

  1. key

RUN mode: Press the key to change SV and move SV (SET, SET1, SET2) digits.

Changing SV mode: Press the key to change digits.

  1. key

Changing SV mode: Increases SV.

Function setting mode: Changes the settings.

1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ).

Specifications

Model

CX6S-1P

CX6S-2P

CX6M-1P

CX6M-2P

Display digits

6-digit

Display method

7-segment (1st, 2nd digits of counting value display: white, setting value display: green) LCD method, 11-segment (the other digits of counting value display: white) LCD method, Operation display part: yellow LCD method

Character Counting value size (W×H) Setting value

Power supply

AC voltage AC/DC voltage

4.1×10.1mm
3.3×8.1mm 100-240VAC 50/60Hz 24VAC 50/60Hz, 24-48VDC

6.2×15.2mm 5×12.3mm

Permissible voltage range 90 to 110% of rated voltage

Power consumption

AC

CX6 –

Max. 6.4VA

voltage CX6 – F Max. 4.2VA

Max. 6.7VA Max. 4.9VA

Max. 7.1VA Max. 4.7VA

Max. 7.5VA Max. 5.4VA

AC/DC CX6 voltage CX6 –

AC: max. 5.5VA AC: max. 5.6VA AC: max. 6.2VA AC: max. 6.3VA DC: max. 3.5W DC: max. 3.6W DC: max. 4W DC: max. 4.1W

F

AC: DC:

max. max.

3.6VA 2.5W

AC: max. 4.0VA DC: max. 2.8W

AC: max. 3.9VA DC: max. 2.9W

AC: max. 4.5VA DC: max. 3.3W

Max. INA/INB CX6 –

counting

speed

CX6 –

Selectable among 1cps/30cps/300cps/1kcps/5kcps F 20cps

Counter

Counting range

-99999 to 999999

Scale

Decimal point up to fifth digit

Min. signal CX6 –

RESET, TOTAL RESET signal: selectable among 1ms/20ms

width

CX6 – F RESET signal: 25ms

Time range

999.999s, 9999.99s, 99999.9s, 999999s, 99m59.99s, 999m59.9s, 9999m59s, 99999.9m, 999999m, 99h59m59s, 9999h59m, 99999.9h

Operation mode

Up, Down

Timer

Min. signal CX6 –

INA, INHIBIT, RESET, TOTAL RESET signal: selectable among 1ms/20ms

width

CX6 – F INA, INH, RESET signal: 25ms

Repeat error Set error Voltage error Temp. error

[CX6 [CX6 –

]-In case of power ON start: max. ±0.01% ±0.05s In case of signal ON start: max. ±0.01% ±0.03s
F]-In case of power ON start: max. ±0.01% ±0.08s In case of signal ON start: max. ±0.01% ±0.06s

Input method

CX6 CX6 –

Selectable among voltage input (PNP)/no-voltage input (NPN) [Voltage input (PNP)]-input impedance: 10.8k,
H: 5-30VDC, [L]: 0-2VDC [No-voltage input (NPN)]-short-circuit impedance: max. 1k,
short-circuit residual voltage: max. 2VDC

[Free voltage input]-INA (START) , INB (INHIBIT) input

F

24-240VDC/24-240VAC 50/60Hz, [L]: 0-10VDC/VAC input]-RESET input, short- circuit impedance: max. 1k,

short-circuit residual voltage: max. 2V

One-shot output time 0.01 to 99.99s setting

Control

Contact

Type Capacity

SPDT (1c): 1 Max. 250VAC

SPST (1a): 2 SPDT (1c): 1 3A, 30VDC 3A resistive load

SPDT (1c): 2

output Solid state

Type

Capacity

NPN open

NPN open

collector: 1

collector: 2

Max. 30VDC 100mA

External power supply1 Max. 12VDC ±10%, 100mA

Memory retention

Approx. 10 years (non-volatile memory)

Insulation resistance

Over 100M (at 500VDC megger)

Dielectric strength

3,000VAC 50/60Hz for 1 min

Noise AC voltage Square-wave noise by noise simulator (pulse width 1) ±2kV immunity AC/DC voltage Square-wave noise by noise simulator (pulse width 1) ±500V

Mechanical Vibration
Malfunction

0.75mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour 0.5mm amplitude at frequency 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 minutes

Shock

Mechanical 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times Malfunction 100m/s² (approx. 10G) in each X, Y, Z direction for 3 times

Relay life Mechanical Min. 5,000,000 operations

cycle

Malfunction Min. 100,000 operations

Protection structure

Front part: IP50 (IEC standard)

Environ- Ambient temp. -10 to 55, storage: -25 to 65

ment

Ambient humi. 35 to 85%RH, storage: 35 to 85%RH

Approval

AC voltage

CX6 CX6 –

Approx. 157g (approx. 112g)

F

Approx. 155g (approx. 110g)

Approx. 162g (approx. 117g) Approx. 160g (approx. 115g)

Approx. 235g (approx. 170g) Approx. 233g (approx. 168g)

Approx. 240g (approx. 175g) Approx. 238g (approx. 173g)

Weight2

AC/DC voltage

CX6 CX6 –

Approx. 156g (approx. 111g)

F

Approx. 154g (approx. 109g)

Approx. 161g (approx. 116g) Approx. 159g (approx. 114g)

Approx. 234g (approx. 169g) Approx. 232g (approx. 167g)

Approx. 239g (approx. 174g) Approx. 237g (approx. 172g)

1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ). 2: The weight includes packaging. The weight in parenthesis is for unit only. Environment resistance is rated at no freezing or condensation.

The above specifications are subject to change and some models may be discontinued without notice.
Be sure to follow cautions written in the instruction manual, user manual and the technical descriptions (catalog, homepage).

45+00.6

68+00.7

Dimensions

48

6

64.5

72

6

64.5

44.8 Min. 65

(unit: mm)
Panel cut-out
Min. 65
45+00.6
Min. 91
68+00.7

67.5 Min. 91

4 3.3

Bracket
CX6S Series 48.6±0.2 45 +00.2

30.6 20 5

16

+0.3 0

CX6M Series 46

+0.2 -0.05

36

44.9

37.5 40.5

55

15

21

12

23.9

56

Terminal cover (sold separately)

CX6S Series (RSA-COVER, 48×48mm)
22

3

48.4

13

CX6M Series (RMA-COVER, 72×72mm)

4

70

10

64

68.5

18 22
41 45

13

Connections

CX6S Series

1. Voltage input (PNP)/no-voltage input (NPN) selectable model

CX6S-1P CONTACT OUT: 250VAC 3A, 30VDC 3A RESISTIVE LOAD

CX6S-2P2 CONTACT OUT1/OUT2: 250VAC 3A, 30VDC 3A RESISTIVE LOAD

CX6S-2P4 CONTACT OUT1/OUT2: 250VAC 3A, 30VDC 3A RESISTIVE LOAD

1

7 INA

1 OUT2 7 INA

1

7 INA

2 OUT 8 INB/INH

3

9 12VDC 100mA

2

8 INB/INH

3 OUT1 9 12VDC 100mA

2

8 INB/INH

OUT2

3

9 12VDC 100mA

4 1
5

10 0VDC 11 RESET

4

10 0VDC

5

11 RESET

4

10 0VDC

OUT1

5

11 RESET

6

12 TOTAL RESET

6

12 TOTAL RESET

6

12 TOTAL RESET

SOURCE: 100-240VAC 50/60Hz 6.4VA 24VAC 50/60Hz 5.5VA 24-48VDC 3.5W

SOURCE: 24VAC 50/60Hz 5.6VA 24-48VDC 3.6W

SOURCE: 100-240VAC 50/60Hz 6.7VA

2. Free voltage input model

CX6S-1P F CONTACT OUT : 250VAC 3A, 30VDC 3A RESISTIVE LOAD SIGNAL INPUT : 24-240VAC 50/60Hz, 24-240VDC

CX6S-2P2F CONTACT OUT1/OUT2 : 250VAC 3A, 30VDC 3A RESISTIVE LOAD SIGNAL INPUT : 24-240VAC 50/60Hz, 24-240VDC

CX6S-2P4F CONTACT OUT1/OUT2 : 250VAC 3A, 30VDC 3A RESISTIVE LOAD SIGNAL INPUT : 24-240VAC 50/60Hz, 24-240VDC

1

7

INA

OUT2

1

7

INA

1

7

INA

2

8

INB/INH

2

8

INB/INH

2

8

OUT2

INB/INH

3 OUT

9

INPUT

4 1
5

10 11
RESET

3

9

OUT1

4

10

INPUT

5

11

RESET

3
4 OUT1
5

9
10
11 RESET

INPUT

6

12

0VDC

6

12

0VDC

6

12

0VDC

SOURCE: 100-240VAC 50/60Hz 4.2VA SOURCE: 24VAC 50/60Hz 4.0VA

24VAC 50/60Hz 3.6VA

24-48VDC 2.8W

24-48VDC 2.5W

SOURCE: 100-240VAC 50/60Hz 4.9VA

CX6M Series

1. Voltage input (PNP)/no-voltage input (NPN) selectable model

CX6M-1P CONTACT OUT: 250VAC 3A, 30VDC 3A RESISTIVE LOAD

CX6M-2P CONTACT OUT1/OUT2: 250VAC 3A, 30VDC 3A RESISTIVE LOAD

1 2 OUT 3 4

10 INA
11 INB
12 12VDC 100mA 0VDC
13

1 2 OUT2 3 4

10 INA
11 INB 12 12VDC 100mA 0VDC 13

5

14 RESET

5 OUT1

14 RESET

6

15 INHIBIT

6

15 INHIBIT

7 1
8
9

SOLID STATE OUT: 30VDC 100mA

16 TOTAL RESET 17 18

7 1
8
9

SOLID OUT1 16 TOTAL RESET

STATE

OUT:

17

30VDC

100mA

18

OUT2

SOURCE: 100-240VAC 50/60Hz 7.1VA 24VAC 50/60Hz 6.2VA 24-48VDC 4W

SOURCE: 100-240VAC 50/60Hz 7.5VA 24VAC 50/60Hz 6.3VA 24-48VDC 4.1W

2. Free voltage input model CX6M-1P F
CONTACT OUT: 250VAC 3A, 30VDC 3A RESISTIVE LOAD
SIGNAL INPUT: 24-240VAC 50/60Hz, 24-240VDC

CX6M-2P F CONTACT OUT1/OUT2: 250VAC 3A, 30VDC 3A
RESISTIVE LOAD SIGNAL INPUT: 24-240VAC 50/60Hz, 24-240VDC

1 2 OUT 3 4

10 INA
11 INB/INH
12 SIGNAL INPUT
13

1 2 OUT2 3 4

10 INA
11 INB/INH
12 SIGNAL INPUT
13

5

14

5 OUT1

14

6 7 1 8
9

15

0VDC RESET

16

SOLID

STATE

OUT:

17

30VDC

100mA

18

6 7 1 8
9

15

0VDC RESET

16 SOLID

STATE

OUT: 30VDC

OUT1 17

100mA OUT2 18

SOURCE: 100-240VAC 50/60Hz 4.7VA 24VAC 50/60Hz 3.9VA 24-48VDC 2.9W
1: AC voltage: 100-240VAC 50/60Hz AC/DC voltage: 24VAC 50/60Hz, 24-48VDC

SOURCE: 100-240VAC 50/60Hz 5.4VA 24VAC 50/60Hz 4.5VA 24-48VDC 3.3W

Operations
1. Operation and setting (counter/timer)

(RUN mode)

(CX6 – )

TOTAL counter
RESET
Reset TOTAL counter

SET 1 value

SET 2 value

(CX6 – F)

[Counter]

Function setting mode

3 sec 3 sec
RUN mode

1 sec

Changing SV
mode
Function setting 1 sec check mode

(RUN mode)

RESET PV RESET

12:30:25

OUT 1

OUT 2 1:25:47

SET 2

TIMER

Display PV Display SET 2

1-1. Function setting mode

12:34:56

OUT 1

OUT 2 SET 1

5:43:50

TIMER

Display PV Display SET 1

[Timer]

Hold the

key over 3 sec to enter function setting mode in RUN mode.

Set the function by the , keys.

Hold the

key over 3 sec to return RUN mode in function setting mode.

1-2. Function setting check mode

Hold the key over 1 sec to enter function setting check mode in RUN mode.

When checking the saved parameters, press the , key to check next item..

Hold the

key over 1 sec at function setting check mode and it returns to RUN mode.

1-3. RESET

In RUN mode, function setting mode, press the RESET key to reset the current value and the output

turns OFF.

At TOTAL counter display mode1, press the RESET key to reset TOTAL counter counting value and

the current counting value.

1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ).

TOTAL counter display mode is only for counter operation.

2. Function setting

RUN mode

3 sec

Function setting mode

3 sec

Counter [COUNT]

Timer [TIME] Counter/Timer [C-T]

Input mode [InM] Output mode [OUtM]

Up/Down mode [U-D] Output mode [OUtM]

(In case of OND, ONdI, ONd2, ONd3, FLk1, FLk2, INT, INt1, INt2, OFD, INTG, TOTAL1, ONtD)

Max. counting speed1 [CPS] OUT 2 output time [OUT2]

(In case of FLK, NFD, NFdI)
Output ON time range [OnRNG]

Time range [tRNG]

OUT output time

[OUtT]

OUT 1 output time [OUT1]

Decimal point [DP]

Min. reset time1 [RESET]

Output OFF time range [OFfRNG] OUT 2 output time [OUT2] OUT 1 output time [OUT1]

(2-stage output model)

(1-stage output model)

OUT output time [OUtT]

Input logic1 [SIG]

Input logic1 [SIG]

Prescale decimal point [SClDP] Prescale value [SCL] TOTAL counter2 [TOTAL] Start point value [START] Memory protection [DATA] Key lock [LOCK]

Input signal time1 [IN-T]

Memory protection2 [ D A T A ]

Key lock [LOCK] 1: In case of free voltage input model (CX6 – F), these parameters do not appear due to fixed setting.
2:This parameter is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ).
: When changing the setting of shaded parameters, all output turn OFF. When returning RUN mode, PV is reset.

Counter Mode
1. Parameter setting (

key: Moves parameters, key: Changes parameter setting value)

Parameter Parameter setting value

Counter/Timer [C-T]

COUNT

TIME

COUNT: Counter TIME: Timer

Input mode [InM]

UP UP-1 UD-C1

UP-2 UP-3 DN DN-1 UD-B1 UD-A DN-3 DN-2

Input mode is UP, UP-1, UP-2, UP-3 or DN, DN-1, DN-2, DN-3, F N [ RKPQA

Output mode Input mode is UD-A, UD-B1, UD-C1

[OUtM]

F N [ RKPQASTD

If max. counting speed is 5kcps, and output mode is D, max. counting speed is automatically changed as 30cps, factory default.

Max. counting 30 300 1K 5K 1 speed2 [CPS]

Max. counting speed is when duty ratio of INA or INB input signal is 1:1.
It is applied for INA, or INB input as same. When output mode is D, set max. counting speed
one among 1cps, 30cps, 300cps, or 1kcps.

OUT 2

Set one-shot output time of OUT 2.

output time3 Setting range: 00.01 to 99.99 sec

[OUT2]

W hen output mode is F, N, S, T, D, this parameter does not appear. (fixed as HOLD)

OUT 1 output time3 [OUT1]

Set one-shot output time of OUT 1. Setting range: 00.01 to 99.99 sec, Hold When number of tens digit is flashing, press the key once and HOLD appears. When output mode is S, T, D, this parameter does not appear. (fixed as HOLD)

OUT output time3 [OUtT]

Setting range: 00.01 to 99.99 sec When output mode is F, N, S, T, D, this parameter does not appear. (fixed as HOLD)

Decimal point4 —— —–.- —-.– —.—

[DP] Decimal point is applied to PV and SV.

Min. reset time2 1

20, unit: ms

[RESET]

Set min. width of external reset signal input.

Input logic2 [SIG]

NPN: No-voltage input, PNP: Voltage input

–.—-

-.—–

Prescale

-.—– —–.- —-.– —.— –.—-

decimal point4

[SClDP]

Decimal point of prescale should not set smaller than decimal point [DP].

Prescale

Setting range: 0.00001 to 99999.9

value [SCL] Setting range of prescale is linked with prescale decimal point [SClDP] setting.

TOTAL counter1 ON [TOTAL]

OFF

Start point value [START]

Setting range of start point value is linked with decimal point [DP] setting. (0.00000 to 999999)
WheninputmodeisDN, DN-1, DN-2, this parameter doesnotappear. WhentotalcountfunctionisON,thisparameter does not appear.1

Memory protection CLR [DATA]

CLR: Resets the counting value when power OFF.

REC

REC: Maintains the counting value when power OFF.

(memory protection)

Key lock [LOCK]

lOFF: Unlock keys, key lock indicator turns OFF

lOFF LOc1

LOc1: Locks RESET key, key lock indicator turns ON

LOc3 LOc2 LOc2: Locks , keys, key lock indicator turns ON LOc3: Locks , RESET , keys, key lock indicator turns ON

1: For voltage input (PNP), no-voltage input (NPN) model (CX6 – ). 2: For free voltage input model(CX6 – F), these parameters do not appear due to fixed setting. 3: For 1-stage setting model (CX6 -1P ), OUT1 does not appear.
The OUT2 output time is displayed as OUtT.
4: Decimal point and prescale decimal point -Decimal point: Set the decimal point for display value regardless of prescale value.
-Prescale decimal point
: Set the decimal point for prescale value of counting value regardless of display value.

2. Input mode

Input mode Counting chart

Operation

INA

H L

No counting

Up [UP]

INB

H L

No counting

4

Count 1

2

3

0

When INA is counting input,

5

67

INB is no counting input. When INB is counting input,

INA is no counting input.

Up-1 [UP-1]

INA

H L

INB

H L

Count 0

2 1

No counting 3

When INA input signal is

rising ( ) , it counts.

4

5 INA: Counting input

INB: No counting input

Up-2 [UP-2]

INA

H L

INB

H L

Count

1

0

When INA input signal is

falling ( ) , it counts.

No counting 2

3

4

INA: Counting input

INB: No counting input

INA

H L

Up-3

INB

H L

When INA or INB input signal is rising ( ) , it counts.

[UP-3]

Count

3

5

6 INA: Counting input INB: Counting input

1

2

0

Down [DN]

INA

H L

INB

H L

n n-1

Count

0

No counting n-2

No counting

n-3 n-4 n-5

n-6

When INA is counting input, INB is no counting input. When INB is counting input, INA is no counting input.
n-7

Down-1 [DN-1]

INA

H L

INB

H L

n n-1

n-2

Count

0

No counting n-3

When INA input signal is rising ( ) , it counts.
INA: Counting input INB: No counting input
n-4 n-5

Down-2 [DN-2]

INA

H L

INB

H L

n n-1

Count

0

No counting n-2

When INA input signal is

falling ( ) , it counts.

INA: Counting input

n-3

INB: No counting input

n-4

n-5

INA

H L

Down-3 [DN-3]

INB

H L

n

n-1

Count

n-2

0

When INA or INB input signal

is rising ( ) , it counts.

INA: Counting input

n-3

INB: Counting input

n-5

n-6

INA

H L

Up/Down-A [UD-A]

INB

H L

4

3

Count

2

1

0

INA: Counting input

INB: Counting command input

When INB is “L”,

4 counting command is up.

3 2

1

2

3

When INB is “H”, counting command is down.

INA

H L

Up/Down-B1 [UD-B]

INB

H L

4 3

Count

2 1

0

INA: Up counting input

INB: Down counting input

3

3

4

When INA and INB input signals are rising ( ) at

22

the same time, it maintains

previous counting value.

INA

H L

Up/Down-C1 [UD-C]

INB

H L

Count

0

3

2

2

1

1

When connecting encoder

output A, B phase with

counter input, INA, INB, set

3 2

input mode [InM] as phase different input [UD-C] for

counter operation.

1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ).

A: over min. signal width, B: over than 1/2 of min. signal width. If the signal is smaller than these width, it may cause counting error (±1).

INA H (INB) L

ON OFF ON OFF T.on T.off

T

T.on, T.off: Min. signal width

The meaning of “H”, “L”

Input Voltage

method input

Character

(PNP)

No-voltage input (NPN)

H

5-30VDC Short

L

0-2VDC Open

Min. signal width by counting speed

CX6 –

CX6 –

Counting Min. signal

speed

width

Counting speed

1cps

500ms

20cps

30cps

16.7ms

300cps 1.67ms

1kcps

0.5ms

5kcps

0.1ms

F
Min. signal width 25ms

3. Prescale function This function is to set and display calculated unit for actual length, liquid, position, etc. It is called “prescale value” for measured length, liquid, or position, etc per 1 pulse. For example, when moving L, the desired length to be measured, and P, the number of pulses per 1 revolution of a rotary encoder, occurs, prescale value is L/P. E.g.) Positioning control by counter and encoder
Pulley
Cutter

Rotary encoder

Motor

Motor conlrol system

Counter

[Diameter (D) of pulley connected with encoder=22mm, the number of pulses by 1 rotation of

encoder=1,000]

*Prescale value

=

× Diameter (D) of pulley

The number of pulses by 1

= 3.1416 × 22 1000

= 0.069mm/pulse

rotation of encoder

Set decimal point [DP] as [—–.-], prescale decimal point [SClDP] as [—.—], and prescale value [SCL] as [)069] at function setting mode. It is available to control conveyor position by 0.1mm unit.

Timer Mode

1. Parameter setting (

key: Moves parameters, key: Changes parameter setting value)

Parameter

Parameter setting value

Counter/Timer [C-T]

COUNT

TIME

COUNT: Counter TIME: Timer

Up/Down mode [U-D]

UP

DN

UP: Time progresses from ‘0’ to the setting time. DN: Time progresses from the setting time to ‘0’.

Output mode [OUtM]

OND ONd1 ONd2 ONd3 FLK FLk1 FLk2 INT ONtD TOTAL1 INTG NFd1 NFD OFD INt22 INt1

Time range [tRNG]3
output ON TIME range [OnRNG]4, output OFF TIME range [OFfRNG]4

999.999

TIMER

s

99999.9 TIMER h

9999.99

TIMER

s

9999:59

TIMER

h:m

99999.9

TIMER

s

99:59:59 TIMER h:m:s

999999

TIMER

s

999999

TIMER

m

99:59.99

TIMER

m:s

99999.9

TIMER

m

999:59.9

TIMER

m:s

9999:59

TIMER

m:s

OUT 2 output time5
[OUT2]

Set one-shot output time of OUT 2. Setting range: 00.01 to 99.99 sec, Hold When number of tens digit is flashing, press the

key once and HOLD appears.

OUT 1 output time5
[OUT1]

Set one-shot output time of OUT 1. Setting range: 00.01 to 99.99 sec, Hold When number of tens digit is flashing, press the

key once and HOLD appears.

OUT output time5 [OUtT] Input logic6 [SIG]

Setting range: 00.01 to 99.99 sec, Hold When number of tens digit is flashing, press the key once and HOLD appears. NPN: No-voltage input, PNP: Voltage input

Input signal time6
[IN-T]

1

20, unit: ms

Set min. width of INA, INHIBIT, RESET, TOTAL RESET signal

Memory protection [DATA]

CLR

REC

CLR: Resets the counting value when power OFF.

REC: Maintains the counting value when power OFF. (memory protection)

lOFF: Unlock keys, key lock indicator turns OFF

Key lock

lOFF LOc1

LOc1: Locks RESET key, key lock indicator turns ON

[LOCK]

LOc3 LOc2 LOc2: Locks , keys, key lock indicator turns ON LOc3: Locks , RESET , keys, key lock indicator turns ON

1: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ).

2: INt2 mode is available only for 2-stage setting model(CX6 -2P ). 3: When output mode is OND, ONd1, ONd2, ONd3, FLk1, FLk2, INT, INt1, INt2, OFD, INTG,

TOTAL, ONtD, set time range [tRNG]. 4: When output mode is FLK, NFD, NFD.1, set output ON TIME range [OnRNG] and output OFF

TIME range [OFfRNG]. 5: In case of 1-stage setting model (CX6 -1P ), OUT1 output time does not appear.

OUT2 output time is displayed as OUtT. 6: In case of free voltage input model (CX6 – F), this parameter does not appear due to fixed

setting.

One-shot output (0.01 to 99.99 sec) Retained output

One-shot output

Retained output

2. Timer ‘0’ time setting

2-1. Timer output mode for ‘0’ time setting [OND, ONd1, ONd2, ONd3, NFD, NFd1] 2-2. Operations by output mode (‘0’ time setting)

A. OND (Signal ON Delay) mode [OND]

Set ‘0’ for setting time 1.

Up mode

Down mode

Set `0′ for setting time 2.

INA (START) Setting time 2

INA (START) Setting time 1

0 OUT 1

OUT 2

B. OND.1 (Signal ON Delay 1) mode [ONd1]

Set `0′ for setting time 1.

Up mode

Down mode

INA (START)

RESET Setting time 2

0 OUT 1 OUT 2
Set `0′ for setting time 2.
INA (START) RESET
Setting time 1

0

OUT 1

OUT 2

C. OND.2 (Power ON Delay) mode [ONd2]

Set `0′ for setting time 1.

Up mode

Down mode

POWER RESET Setting time 2

0 OUT 1 OUT 2
Set `0′ for setting time 2. Up mode
POWER RESET Setting time 1

0 OUT 1

OUT 2

D. OND.3 (Power ON Delay) mode [ONd3]

Set `0′ for setting time 1.

Up mode

Down mode

POWER
RESET Setting time 2

0 OUT 1 OUT 2
Set `0′ for setting time 2. Up mode
POWER RESET Setting time 1

0

OUT1

OUT2
E. NFD (ON-OFF Delay) mode [NFD] Set ‘0’ for Off_Delay setting time.

INA (START) RESET

UP DISPLAY DOWN

On_Delay 0
On_Delay 0

OUT 2 (OUT)
F. NFD.1 (ON-OFF Delay1) mode [NFd1] Set `0′ for Off_Delay setting time.

INA (START) RESET

UP DISPLAY DOWN

On_Delay 0
On_Delay 0

OUT 2 (OUT)

0 OUT1 OUT2

Set `0′ for On_Delay setting time.

INA (START) RESET

UP

Off_Delay

DISPLAY

0

DOWN Off_Delay

0

OUT 2 (OUT)

Set `0′ for On_Delay setting time.

INA (START) RESET

UP

Off_Delay

DISPLAY

0

DOWN Off_Delay

0

OUT 2 (OUT)

Factory Default

Parameter

Factory default CX6 –

CX6 – F

InM

UD-C

UD-A

OUtM

F

F

CPS

30

OUT2 (OUtT1) OUT11

HOLD (fixed) 0)10

HOLD (fixed) 0)10

DP

——

——

Counter

RESET

20ms

SIG

NPN

SClDP

-.—–,

-.—–,

SCL

!00000

!00000

TOTAL2

OFF

START

000000

000000

DATA

CLR

CLR

U-D

UP

UP

OUtM

OND

OND

OUT2 (OUtT1)

HOLD

HOLD

Timer

OUT11

0)10

0)10

tRNG

99(999s

99(999s

SIG2

NPN

IN-T

20ms

LOCK

lOFF

lOFF

SET1

1000

1000

SET2

5000

5000

1: For 1-stage setting model (CX6 -1P ), OUT1 does not appear.
The output time of OUT2 is displayed as OUtT. 2: This is for the voltage input (PNP)/no-voltage input (NPN) selectable model (CX6 – ).

Error Display and Output Operation

Error Display

Error description

Troubleshooting

ERR0

Setting value is 0.

Change the setting value anything but 0.

When error occurs, the output turns OFF. When 1st setting value is set as 0 (zero), OUT1 maintains OFF.
When 2nd setting value is smaller than 1st setting value, 1st setting value is ignored and only OUT2 output operates.
Indicator model does not have error display function.

Cautions during Use
1. Follow instructions in Cautions during Use’. Otherwise, it may cause unexpected accidents. 2. In case of 24-48VDC, 24VAC model, power supply should be insulated and limited voltage/ current or Class 2, SELV power supply device. 3. Use the product, 0.1 sec after supplying power. 4. When supplying or turning off the power, use a switch or etc. to avoid chattering. 5. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the power. 6\. Keep away from high voltage lines or power lines to prevent inductive noise. In case installing power line and input signal line closely, use line filter or varistor at power line and shielded wire at input signal line. Do not use near the equipment which generates strong magnetic force or high frequency noise. 7\. This unit may be used in the following environments. Indoors (in the environment condition rated inSpecifications’) Altitude max. 2,000m Pollution degree 2 Installation category II

Major Products

Photoelectric Sensors

Temperature Controllers

Fiber Optic Sensors

Temperature/Humidity Transducers

Door Sensors

SSR/Power Controllers

Door Side Sensors

Counters

Area Sensors

Timers

Proximity Sensors

Panel Meters

Pressure Sensors

Tachometer/Pulse (Rate) Meters

Rotary Encoders

Display Units

Connector/Sockets

Sensor Controllers

Switching Mode Power Supplies

Control Switches/Lamps/Buzzers

I/O Terminal Blocks & Cables

Stepper Motors/Drivers/Motion Controllers

Graphic/Logic Panels

Field Network Devices

Laser Marking System (Fiber, Co, Nd: YAG)

Laser Welding/Cutting System

http://www.autonics.com